Plan Review Details - Permit 01060035
Plan Review Stops For Permit 01060035
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2001-06-26 Cont ID  
Sent By lsmith Date 2001-06-26 Time 08:22 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2001-06-26 Cont ID  
Sent By lsmith Date 2001-06-26 Time 08:23 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-06-29 Cont ID  
Sent By mamini Date 2001-06-29 Time 13:47 Rev Time 5.00
Received By mamini Date 2001-06-29 Time 13:46 Sent To  
Notes
2001-06-29 00:00:00PASSED:
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 6-25-01 SATISFACTORY.
 PLANS HAVE BEEN REVISED PER REVIEW
 COMMENTS.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-06-25 Cont ID  
Sent By mamini Date 2001-06-25 Time 13:29 Rev Time 5.00
Received By mamini Date 2001-06-25 Time 13:10 Sent To  
Notes
2001-06-25 00:00:00FAILED :
 1. THE ISUES REGARDING THE ENTRANCE
 DRIVE WITH ZONING DEPARTMENT MUST BE
 RESOLVED BEFORE CIVIL PLAN BE APPROVED.
 2. PLEASE SUBMIT SURVEYING PLAN,SIGNED &
 SEALED.
 3. PLEASE PROVIDE A MIN. 20'- 0" CLEAR
 AT ALL ENTRANCES.
 4. PLEASE SHOW LOCATIONS OF THE CLEAN-
 OUTS.
 5. PLEASE SHOW LOCATIONS FOR THE
 BACKFLOW PREVENTERS.
 6. PLEASE VERIFY THE STRUCTURE'S
 NUMBERING THROUGHOUT.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-03 Cont ID  
Sent By lmartine Date 2001-07-03 Time 07:54 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-07-03 00:00:00OK PER MIKE C.
 7/3/01L.M.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-06-22 Cont ID  
Sent By mcarsill Date 2001-06-22 Time 14:12 Rev Time 0.00
Received By mcarsill Date 2001-06-22 Time 14:12 Sent To  
Notes
2001-06-22 00:00:001) GUARDHOUSE AND SECURITY FEATURES
 PLANNED ARE STILL NOT APPROVED. PREVIOUS
 PLAN REVIEW COMMENTS NOT ADDRESSED
 REFERENCE THE ENTRY SYSTEM AND
 APPURTENANCES.
 2) PLEASE BE ADVISED THAT CITY CODE
 SECTION 11-4 REQUIRES THAT NO
 OBJECTS BE PLACED WITHIN 18 FEET OF
 ANY FIRE HYDRANTS.
 3) ALL UNDERGROUND FIRE MAINS ARE TO BE
 LISTED FOR FIRE SERVICE AND COMPLY WITH
 NFPA 24.
 4) WHERE ARE THE BACKFLOW DEVICES
 LOCATED.
 5) PLEASE EXPLAIN PURPOSE OF ALL WATER
 VALVES SHOWN ON THE DRAWING. ARE SOME
 OF THESE VALVES REDUNDANT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By mcarsill Date 2001-06-07 Time 08:15 Rev Time 0.00
Received By mcarsill Date 2001-06-07 Time 08:15 Sent To  
Notes
2001-06-07 00:00:001) FIRE AND PARAMEDICAL ACCESS INTO
 THE COMPLEX SHALL BE AT LEAST TWENTY
 FEET IN CLEAR WIDTH AS REQUIRED BY
 FIRE CODES
 2) HOW ARE SECURITY FEATURES AFFECTED
 WHEN LOSS OF POWER OCCURS.
 3) IS THE GUARD HOUSE STAFFED FULL TIME
 AND IF NOT HOW IS FIRE RESCUE TO ENTER
 THE PROPERTY.
 4) A MINIMUM OF 13'- 6" IS TO BE
 PROVIDED FOR FIRE AND PARAMEDICAL
 EQUIPMENT IF THEY HAVE TO PASS
 UNDERNEATH A CANOPY.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-06-26 Cont ID  
Sent By lsmith Date 2001-06-26 Time 08:22 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-06-26 Cont ID  
Sent By lsmith Date 2001-06-26 Time 08:23 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-21 Cont ID  
Sent By lsmith Date 2001-06-21 Time 10:17 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-06-21 00:00:00PER SG 6/21/01