Plan Review Details - Permit 01051593
Plan Review Stops For Permit 01051593
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-02-28 Cont ID  
Sent By hpiskura Date 2002-02-28 Time 13:45 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-02-28 00:00:00REVISIONS ON SHEET A1.0 SEALED DATE
 2/14/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2002-01-07 Cont ID  
Sent By jwitmer Date 2002-01-07 Time 17:58 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-07 00:00:00REVISIONS #1, #2 DEC.10/01
 DENIED!!!!
 1)- HANDICAPPED STALLS, FL ACC CODE
 4.17.3 FIG. 30 "E" REQUIRES THE WATER
 CLOSET SHALL BE LOCATED IN THE CORNER
 DIAGONAL TO THE DOOR!!!!!AS PER THE
 FIRST SET OF REVISIONS!!!!!
  
 2)- FRONT ENTRY,(FOYER) SBC 1019.2.3
 REMOVAL OF PERMANENT BARRIER SEPERATING
 THE WAITING AREA FROM THE REQUIRED CLEAR
 WIDTH FOR EXITS.
  
 3)- DELETION OF 2 HR.HORIZONTAL PASSAGE
 WAY. BEHIND STORAGE UNIT # 1!!!!!!
  
 4)- BAR AREA # 2, SHOW EGRESS PATH ,
 CLEAR FLOOR AREA.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-09-28 Cont ID  
Sent By jwitmer Date 2001-09-28 Time 09:46 Rev Time 2.00
Received By jwitmer Date 2001-09-28 Time 09:45 Sent To  
Notes
2001-09-28 00:00:00PROVISO: 9/28/01
 1997 FLORIDA ACCESSIBILITY CODE:
  
 1)- STAGE PLATFORM VERTICAL ACCESS-
 IBILITY 4.1.3. WILL REQUIRE VERTICAL
 ACCESSIBILITY EITHER BY RAMP OR LIFT.
  
 2)- FL ACC. CODE 4.8.5 HANDRAILS WILL
 BE REQUIRED ON THE RAMP IF IT IS OVER
 6" IN HEIGTH.
  
 THIS INFORMATION WILL BE REQUIRED BY THE
 FRAMING INSPECTION.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EXT 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-09-17 Cont ID  
Sent By jwitmer Date 2001-09-17 Time 17:42 Rev Time 1.50
Received By jwitmer Date 2001-09-17 Time 17:42 Sent To  
Notes
2001-09-17 00:00:00BUILDING PLAN REVIEW
 PERMIT #01051593
 550 S ROSEMARY # 250
 ACCESS CONSTRUCTION TEAM
  
 1)- STAGE (PLATFORM) VERTICAL ACCESSIBIL
 ITY 4.1.3 RAMPS ARE PERMISSIBLE.
 2)- FL ACC CODE 4.8.5 HANDRAILS IF THE
 PLATFORM IS OVER 6" HIGH.
 3)- PROVIDE PRODUCT APPROVAL FOR ALL
 GLAZED EXTERIOR OPENINGS. IF THE GLAZED
 OPENIINGS DO NOT HAVE LARGE MISSLE
 RESISTANCE TESTING STORM SHUTTERS WILL
 BE REQUIRED PRODUCT APPROVAL WILL BE
 REQUIRED.
 4)- FL ACCESS CODE 4.1.7.3(2) THE ACCESS
 IBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER DIAGONAL TO THE DOOR.
 5)- SHEET A2.2. DETAIL D BENCH & COUNTER
 SECTION STORAGE COMPARTMENT , MAY
 REQUIRE FIRE SPRINKLERS.
 6)- RAISED PLATFORMS AND RAMPS TO COMPLY
 WITH SBC 403.2.4.1/403.2.4.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-07-30 Cont ID  
Sent By jwitmer Date 2001-07-30 Time 19:14 Rev Time 0.00
Received By jwitmer Date 2001-07-31 Time 07:08 Sent To  
Notes
2001-07-30 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01051593
 550 S ROSEMARY AVE # 250
 ACCESS CONSTRUCTION TEAM
 (813) 274-7770
  
 SBC= STANDARD BUILDING CODE
 SBC*= STANDARD BUILDING CODE AMENDMENTS
 FL ACC= 1997 FLORIDA ACCESSIBILITY CODE
  
 1)- SHOWROOM LEVELS 2.0, 2.1, 2.2 &
 LEVEL 3.0 ARE IN AN ASSEMBLY OCCUPANCY
 OCCUPANCY. SBC 1019.8: IN BUILDINGS OF
 GROUP A OCCUPANCY, FLIGHTS OF LESS THAN
 (3) THREE RISERS SHALL NOT BE USED IN
 INTERIOIR OR EXTERIOR STAIRWAYS, EXIT
 PASSAGE WAYS, AISLES, AT ENTRANCES OR
 ELSEWHERE IN CONNECTION WITH REQUIRED
 EXITS. TO OVERCOME LESSER DIFFERENCES
 IN LEVEL, RAMPS MAY BE USED.
  
 2)- WHERE THERE IS A ELEVATION CHANGE,
 LEVEL 2.0, 2.1, 2.2 & 3.0 VERTICAL
 ACCESSIBILITY MUST BE PROVIDED. FL
 ACCESSIBILITY CODE 4.1.3 THE STAGE ALSO
 MUST MEET THE VERTICAL ACCESSIBILITY
 REQUIREMENTS BUT DEPENDING ON THE HEIGTH
 OF THE STAGE HANDRAIL REQUIUREMENTS
 FL ACC. 4.8.2.
  
 3)- FL ACCESSIBILITY CODE: 4.8.3 CLEAR
 WIDTH, RAMPS THAT ARE USED AS A MEANS OF
 EGRESS SHALL NOT BE LESS THAN 44" WIDE.
  
 4)- FL ACC CODE RAMPS 4.8.4 (LEVEL 2.2)
 ALL LANDINGS ON RAMPS SHALL BE NOT LESS
 THAN 60" CLEAR, AND THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF
 STRAIGHT AND LEVEL SURFACE.
  
 5)_ FL ACC CODE 4.8.5 HANDRAILS: IF A
 RAMP HAS A RISE GREATER THAN 6" OR A
 HORIZONTAL PROJECTION GREATER THAN 72",
 THEN IT SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 6)- SHEET E.5 INDICATES THAT THE 225KVA
 TRANSFORMER IS IN THE ELECTRIC ROOM,
 WHAT IS SUPPORTING THE TRANSFORMER?
  
 7)- REVISE THE LIFE SAFETY PLAN TO
 INCLUDE LEVEL 2.2 64 PEOPLE FOR FIXED
 SEATING AND 64' OF BAR @ 2' PER PERSON
 OR ANOTHER 32 PEOPLE.
  
 8)- THE CORRIDOR BEHIND THE KITCHEN WILL
 NEED TO BE AN EXIT CORRIDOR, SINCE THIS
 IS AN ASSEMBLY OCCUPANCY THE TABLE
 705.1.2 OF THE SBC REQUIRES A 2 HR.
 RATING ON WALLS CEILING AND FLOOR. ALL
 OPENINGS WILL REQUIRE AN 1 1/2 HR. OPEN-
 ING PROTECTION, AND THE CORRIDOR HAS TO
 EXTEND TO THE EXTERIOR OF THE BUILDING.
  
 9)- PROVIDE PRODUCT APPROVAL ON ALL
 EXTERIOR GLAZING, TO INDICATE CONFORMITY
 WITH IMPACT REQUIREMENTS FOR HURRICANE
 PROTECTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-18 Cont ID  
Sent By bstaples Date 2001-06-18 Time 12:40 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-06-18 00:00:00BUILDING PLAN REVIEW COMMENTS 6/18.
 1. PAY IMPACT FEES, PALM BEACH COUNTY TO
 STAMP PLANS.
 2. SHEET A1.0, PROVIDE LIFE SAFETY PALN
 FOR LOUNGE, DINING 1 AND 2, BAR AND
 EXTERIOR SEATING AREAS. INDICATE EXIT
 ILES FOR ALL AREAS.
 3. INDICATE HANDICAPPED ACCESS FOR
 LEVELS 2 AND 2.1. RAMPS REQUIRED SEE
 SBC 1019.8 AND FLORIDA ACCESSABILITY
 CODE 4.1.3.
  
 4. SHEETS A1.1, A1.2 AND A2.1 WHERE
 REVIWED WITHOUT APPROVAL OF DESIGNER OF
 RECORD INITIALS AND DATE.
 5. SHEET E.5 PROVIDE ENGINEERING ON 225
 KVA TRASNSFORMER SUSPENDED FROM BOTTOM
 COURD OF ROOF TRUSSES.
 5. SHEET AC.2 ENGINNER TO PROVIDE DESIGN
 FOR FAN COIL SUPPORT ATTACHED TO BOTTOM
 COURD OF ROOF TRUSSES.
 6. PROVIDE INFORMATION ON FIRE STOPPING
 SYSTEMS TO BE USED ON ALL FIRE RATED
 HORZONTIALL AND VERTICAL PENATRATIONS.
 7. ASSEMBLEY OCCUPANCY, PROVIDE FIRE
 RATING INFORMATION ON ALL WALL AND
 FLOORS
 8. INFORMATION SUBMITTED IS NOT
 SUFFICIENT TO DETERMINE CLASS OF
 OCCUPANCY MAY BE LARGE ASSEMBLEY (OVER
 ONE THOUSAND PEOPLE).
 9. SHEET AC.2 KITCHEN HOOD DETAIL
 PENETRATES THE FIRE RATED WALL SHOWN ON
 SHEET A1.1 AND 2, WALL REQUIRES UL
 LISTING, DAMPERS ETC.
 10. PROVIDE INFORMATION ON ALL EXTERIOR
 GLAZING TO INDICATE CONFORMITY WITH
 IMPACT REQUIREMENTS FOR HURRICANE
 PROTECTION.
  
 PLANS LACK MINUMIM INFORMATION REQUIRED
 TO BE CONSIDERED FOR PERMIT ISSUANCE.
 CALL BILL STAPLES AT 561-659-8096 EXT.
 8315 FOR ASSISTANCE.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-07-12 Cont ID  
Sent By dpalmer Date 2002-07-12 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2002-07-12 Time 07:21 Sent To P
Notes
2002-07-12 00:00:00********* NOTE **********
  
 1)NOTE: PLEASE NOTE NEW SHEETS FOR
 ELECTRICAL RISER. PLEASE NOTE THAT
 FIELD INSPECTION IS STILL REQ`D. NO
 ELECTRICAL FINAL DONE.
 MADE PLANS INTO ALL NEW SETS FOR RECORD
 AND FIELD SET.
 KEEP OLD PLANS UNTIL AFTER C.O. FOR
 RECORD. SEE DV PALMER FOR ANY QUESTIONS.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2002-05-16 Cont ID  
Sent By dpalmer Date 2002-05-16 Time 06:51 Rev Time 0.00
Received By dpalmer Date 2002-05-16 Time 06:51 Sent To  
Notes
2002-05-16 00:00:00************ UNSAT 4TH TIME **********
  
 1)NOTE: PLEASE NOTE THAT THE PLANS DO
 NOT CORRELATE. THESE HAVE BEEN THE
 SAME COMMENTS FOR THE LAST FOUR SUBMITT-
 -ALS FOR ELECTRICAL REVISIONS.
 PLEASE NOTE THAT A 4X FEE IS NOW ASSESS-
 ED PER FS.553-80(2B) TO THE DESIGN
 PROFESSIONAL. PLANS WILL NOT BE RELEASED
 UNTIL FEE IS PAID. THEN PLANS MAY GO
 BACK OUT. IF PLANS COME IN AGAIN WITH
 THE SAME COMMENTS, THEN I WILL BE FORCED
 TO TURN THE DESIGN PROFESSIONAL INTO THE
 STATE.
 PLEASE NOTE AS OF TODAYS DATE, THE
 DESIGN PROFESSIONAL HAS NOT CONTACTED
 ME FOR ANY COMMENTS/QUESTIONS ETC.
  
 PLEASE CORRELATE PLANS AND SUBMIT FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-04-12 Cont ID  
Sent By dpalmer Date 2002-04-12 Time 06:34 Rev Time 0.00
Received By dpalmer Date 2002-04-12 Time 06:34 Sent To  
Notes
2002-04-12 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PANELS STILL
 DO NOT CORRELATE!!!!
 PLEASE NOTE THAT TOP OF PANELS NOW
 SHOW 200A MCB BUT CONDUCTOR SIZES BELOW
 PANEL SCHEDULES STILL SHOW WIRE FOR
 150A`S>
  
 2)NOTE: PLEASE ALSO NOTE THAT RISER
 DIAGRAM WAS NOT REVISED. PLEASE NOTE,
 RISER DIAGRAM DOES NOT CORRELATE EITHER.
  
 3)NOTE: PLEASE CORRECT AND PUT SETS OF
 PLANS TOGETHER INTO TWO WORKING SETS.
 PLEASE NOTE THAT THERE ARE REVISED SHEET
 -S NOT PLACE IN SETS ETC.
  
 4)NOTE: PLEASE NOTE THAT UNDER FS/ FAC
 THESE PLANS HAVE BEEN DENIED FOR THE
 SAME COMMENTS FOR THREE TIMES AND ARE
 SUBJECT TO FOUR TIMES THE PLAN REVIEW
 FEE!!!! PLEASE SEE SEC 553-80 FAC.
 IF PLANS COME BACK IN AND ARE NOT
 CORRECTED COMPLETELY, THERE WILL BE A
 FOUR TIMES FEE AND A RED TAG WILL BE
 WRITTEN IN VIOLATION OF TCO/CO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-02-19 Cont ID  
Sent By dpalmer Date 2002-02-19 Time 07:49 Rev Time 0.00
Received By dpalmer Date 2002-02-19 Time 06:36 Sent To  
Notes
2002-02-19 00:00:00****************** UNSAT ************
  
 PLEASE NOTE THAT THESE PLANS ARE FOR
 FINAL/CO.PLEASE NOTE THAT PLANS NEED TO
 CORRELATE COMPLETELY WITH JOBSITE.
  
 1)NOTE: PLEASE NOTE/VERIFY THAT ALL
 PANELS ARE 200AMP. PLEASE NOTE THAT PER
 FEILD INSPECTIONPANELS 'C,D,E,F' ARE
 ALL 200A MCB.
  
 2)NOTE: PLEASE ALSO NOTE THAT SOME
 PANELS ARE SHOWN AS RECESSED? PLEASE
 NOTE THAT 'A,B,C,D,E,F' ARE ALL SURFACE
 MOUNTED.
  
 PLEASE VERFIY AND MAKE THE CHANGES AS
 NEEDED.PLEASE SUBMIT FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-12-12 Cont ID  
Sent By dpalmer Date 2001-12-12 Time 07:27 Rev Time 0.00
Received By dpalmer Date 2001-12-12 Time 07:27 Sent To  
Notes
2001-12-12 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, THAT AS PER CONVER-
 -SATION WITH THE ELECTRICAL INSPECTOR,
 PLEASE PROVIDE LAYOUT OF THE ELECTRICAL
 ROOM ON PLANS AS IT IS IN THE FIELD.
  
 2)NOTE: PLEASE NOTE, LOAD SHOWN FOR
 PANEL "E IS DIFFERENT FROM LOAD CALCULA-
 -TION FOR ALL PANELS.
  
 3)NOTE: PLEASE PROVIDE LOAD ON LINE SIDE
 OF TRANSFORMER.
  
 4)NOTE: PLEASE CLARFIY HOW MANY CONDUITS
 ARE COMING FROM LOAD SIDE OF TRANSFORMER
 TO DISC AND FROM DISC TO 12"X12"X9'
 GUTTER. PER ELECTRICAL INSPECTOR, THE
 FIELD INSTALLATION HAS ONLY ONE 2 1/2"
 CONDUIT INSTALLED WITH 4-3/0`S AND
 SOME CONFUSION OF THE ELECTRICAL CONTRAC
 TOR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND PERHAPS MEET WITH THE ELEC
 CONTRACTOR AND/OR ELECTRICAL INSPECTOR
 ON THE JOB.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-09-19 Cont ID  
Sent By dpalmer Date 2001-09-19 Time 22:12 Rev Time 0.00
Received By dpalmer Date 2001-09-19 Time 22:12 Sent To  
Notes
2001-09-19 00:00:00*************** NOTES REDLINED ********
 PLEASE NOTE NOTES REDLINED ON PLANS FOR
 ELECTRICAL CONTRACTOR AND INSPECTOR.
 SOME ITEMS STILL NEED TO BE FIELD
 VERIFIED. PLEASE NOTE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-07-22 Cont ID  
Sent By dpalmer Date 2001-07-22 Time 09:03 Rev Time 0.00
Received By dpalmer Date 2001-07-22 Time 08:48 Sent To  
Notes
2001-07-22 00:00:00****************UNSAT ***************
  
 1)NOTE: PLEASE SHOW GROUNDING REQUIRED
 FOR TRANSFORMER. TO WHERE?
  
 2)NOTE: PLEASE NOTE THAT IN THE "96" NEC
 IT NOTES UNDER 450-21B TRANSFORMERS TO
 BE 80C OR HIGHER AND "99" NEC CLASS 155
 OR HIGHER. PLANS SHOW 80F?
 WE ARE UNDER THE "99" NEC AND THEREFORE
 NOTE FOR TRANSFORMER NEEDS TO CLASS 155.
  
  
 3)NOTE: PLEASE SUBMIT CLARIFICATION ON
 400A DISCONNECT FROM EXISTING ELEC ROOM.
 IS IT FUSED AT 250A`S?? PLANS SHOW A
 400A DISC FEEDING AT 250A DISC W/ 250A
 FUSES? PLEASE CLARIFY.
  
 4)NOTE: PLEASE NOTE THAT NO AIC RATINGS
 WERE SUBMITTED FOR LINE AND LOAD DISC`S
 FOR TRANSFORMER.
  
 5)NOTE: PLEASE NOTE THAT ALL PANEL
 SCHEDULES SHOW PANELS BEING RECESSED,
 AND PLAN ON E-1 SHOWS PANELS AS SURFACE
 MOUNTED? PLEASE CLARIFY.
 PLEASE NOTE THAT AS PER ELECTRICAL ROOM
 LAYOUT ON E-1 AND SCALE SHOWN BELOW
 AT 1/2" TO 1'. THE CLEARENCES DON'T SHOW
 AS BEING ENOUGH. ALSO PLEASE NOTE THAT
 DURING CONTRUCTION WE HAVE RUN INTO
 MORE OFTEN THAN NOT THAT ELECTRICAL
 ROOMS ARE NOT BUILT LARGE ENOUGH.
 MANY WALL HAVE BEEN MOVED IN THE PAST TO
 MEET CODE. PLEASE VERIFY THAT ALL
 CLEARENCES MEET OR EXCEED REQ`D SPACES
 FOR 110-26 AND 450-21.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-12 Cont ID  
Sent By dpalmer Date 2001-06-12 Time 23:05 Rev Time 0.00
Received By dpalmer Date 2001-06-12 Time 23:04 Sent To  
Notes
2001-06-12 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT OUTLET SPACING
 NEEDS TO MEET LOCAL CODE PER ART 210-50
 STORAGE AREAS/ EVERY 20' OF
 UNENCUMBEREDWALL SPACE AND OFFICE AREAS
 EVERY 12"
 THE AREAS WHERE PATRONS/PUBLIC LOOKS TO
 BE AREA IN QUESTION. PLEASE NOTE EVERY
 20' AND PLACE BRANCH CIRCUIT #`S ON
 PLANS THAT CORRELATE WITH PANEL SCHEDULE
  
  
 2)NOTE: PLEASE NOTE THAT PANEL"C" PANEL
 SCHEDULE SHOWS MLO AND RISER SHOWS MCB.
 PLEASE CALRIFY.
  
 3)NOTE: PLEASE NOTE THAT GROUNDING FOR
 TRANSFORMER NEEDS TO BE CLARIFIED. PER
 450-5 AND 450-10
  
 4)NOTE: PLEASE NOTE 450-13 FOR ACESS.
 PLEASE SHOW TRANSFORMER LOCATION ON
 PLANS.PLANS NOTE TRANSFORMER HANGING
 FROM CEILING BUT NOT WHERE.
 PLEASE ALSO NOTE THAT ART 450-21B FOR
 TRANSFORMERS OVER 112.5 KVA NEED TO BE
 INSTALLED IN A TRANSFORMER VAULT.
  
 5)NOTE: PLEASE NOTE WIRE SIZE SHOWN FOR
 PANEL "B" ON E-5AS 4-1/0`S FOR 200A.
 PLEASE CORRECT.
  
 6)NOTE: PLEASE NOTE ACCESSABLITY FOR
 ALL DISCONNECTS AND CLEARENCES PER
 11-26. PLEASE CLARIFICATION FOR DISCO-
 -NNECTS FOR TRANSFORMER// LINE AND LOAD.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING WAS
 SUBMITTED FOR PANELS, BUT NOT FOR MAIN
 OR DISC.
  
 8)NOTE: PLEASE FEILD VERIFY SIZE OF
 EXSITING CONDUCTORS SHOWN FOR MAIN.
 PLEASE CLARIFY FOR ART 240-3B
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2002-02-19 Cont ID  
Sent By mcarsill Date 2002-02-19 Time 12:35 Rev Time 0.00
Received By mcarsill Date 2002-02-19 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-12-12 Cont ID  
Sent By mcarsill Date 2001-12-12 Time 11:16 Rev Time 0.00
Received By mcarsill Date 2001-12-12 Time 11:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 08:39 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 08:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-07-19 Cont ID  
Sent By lsmith Date 2001-07-19 Time 09:59 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-07-19 00:00:00SEPARATE FIRE SPRINKLER PERMIT#01070931
 ISSUED AND APPROVED PER MEC LS
 OTHER ITEMS ADDRESSED BY MEC NOT APPROVE
 D AS OF THIS DATE LSWILL GIVE BACK TO
 RETT TO LOOK AT. LS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 12:53 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 12:53 Sent To  
Notes
2001-07-05 00:00:001) PREVIOUS PLAN REVIEW COMMENTS FROM
 DESIGNER NOT ATTACHED TO PLANS.
 2) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 3) EXITS NOT SEPARATED 1/2 THE DIAGONAL
 DISTANCE IN THE SHOWROOM LEVEL ONE.
 4) STORAGE TWO HAS WHAT FIRE SEPARATION
 FROM THE EXIT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-01 Cont ID  
Sent By mcarsill Date 2001-06-01 Time 09:47 Rev Time 0.00
Received By mcarsill Date 2001-06-01 Time 09:47 Sent To  
Notes
2001-06-01 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS. PLEASE PROVIDE FIRE
 SPRINKLER DRAWINGS.
 2) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 3) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED WITH PLANS.
 4) PANIC HARDWARE REQUIRED ON ALL
 EXIT DOORS SINCE OCCUPANCY IS EXPECTED
 TO BE OVER 100 PERSONS. FIRE EXIT PANIC
 HARDWARE REQUIRED FOR ALL FIRE DOORS.
 5) NO SEATING SHOWN FOR LOUNGE OR DINING
 ROOM NUMBER 2.
 6) PLEASE EXPLAIN EXITING RATIONALE TO
 THIS OFFICE. THE STAIRWELL EXIT DOOR
 NEAR OFFICE NUMBER 2 IS SHARED WITH
 ANOTHER ASSEMBLY OCCUPANCY. ONLY HALF
 CREDIT WILL BE GIVEN FOR THIS STAIR
 SINCE IT IS SHARED. THE FOUR SWINGING
 DOORS FROM SHOWROOM LEVEL ONE OPEN
 INTO LOUNGE WHERE ONLY TWO SWINGING
 DOORS ARE PROVIDED TO ENTER THE FOYER
 AREA. PLEASE INDICATE ON PLANS WHERE THE
 MAIN EXIT IS PROVIDED TO ACCOMODATE
 AT LEAST FIFTY PERCENT OF THE TOTAL
 OCCPANT LOAD.
 7) NO BAR STOOLS SHOWN FOR BAR NUMBER
 ONE.
 8) PLEASE PROVIDE A LIFE SAFETY PLAN TO
 THIS OFFICE WITH THE NEXT SUBMITTAL.
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD,DUCT AND EXTINGUISHING
 SYSTEMS.
 10) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE ALARM SYSTEM REMODEL.
 11) PLEASE INDICATE CONSTRUCTION TYPE
 FOR STAGE.
 12) PLEASE INDICATE NUMBER OF STAFF
 PERSONS SO THEY CAN BE INCLUDED IN
 OCCUPANT LOAD
 13) NO EXIT SIGNS SHOWN NEAR DOUBLE
 DOORS FROM SHOWROOM NUMBER ONE.
 14) ANY CHANGES IN ELEVATION LESS THAN
 TWENTY ONE INCHES SHALL BE BY RAMPS.
 15) PLEASE INDICATE IF THERE ARE ANY
 WAITING SPACES IN THE SPACE.
 16) PLEASE EXPLAIN US OF NEW PATIO.
 17) PLEASE IDENTIFY IF A COLUMN IS
 PRESENT NEAR EXIT DOOR NEAR BAR NUMBER
 ONE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2002-04-10 Cont ID  
Sent By pkrauss Date 2002-04-10 Time 08:18 Rev Time 0.30
Received By pkrauss Date 2002-04-10 Time 07:57 Sent To  
Notes
2002-04-10 00:00:00NO MECHANICAL REVISIONS WERE SUBMITTED
 AT THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-09-25 Cont ID  
Sent By pkrauss Date 2001-09-25 Time 08:32 Rev Time 0.40
Received By pkrauss Date 2001-09-25 Time 08:32 Sent To  
Notes
2001-09-25 00:00:00*******************PROVISO**************
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, AND WALK-IN
 COOLER/FREEZER.PLEASE SUBMIT PLANS
 AND MANUFACURER INFORMATION WITH PERMIT
 APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-07-10 Cont ID  
Sent By pkrauss Date 2001-07-09 Time 16:34 Rev Time 0.40
Received By pkrauss Date 2001-07-09 Time 16:33 Sent To  
Notes
2001-07-09 00:00:00*******************DENIED***************
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS.
 PLEASE PROVIDE PLANS WITH MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATIONS.
  
 PROVIDE LOCATION OF THE FLUE PIPE FOR
 GAS WATER HEATER.
  
 SUPPLY DUCT TO STORAGE ROOM APPEARS TO
 PENETRATE A RATED WALL, FIRE DAMPER IS
 REQUIRED.PLEASE PROVIDE MANUFACTURER
 DETAILS FOR COMPLIANCE WITH 1997 SMC
 610.1.2.LOCATIONS OF FIRE DAMPERS
 NEEDTO BE INDICATED ON PLAN.
  
 NOTE:NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS 659-8096 EXT. 8338.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-09 Cont ID  
Sent By pkrauss Date 2001-06-09 Time 08:36 Rev Time 1.00
Received By pkrauss Date 2001-06-09 Time 08:31 Sent To  
Notes
2001-06-09 00:00:00********************DENIED**************
  
  
 NOTE:ADDITIONAL PLANS AND PERMITS
 REQUIRED FOR HOOD SYSTEM, FIRE
 SUPRESSION AND WALK-IN COOLERS.
 PLEASE SUBMIT PLANS AND
 MANUFACTURER DETAILS WITH PERMIT
 APPLICATION.
  
 PLEASE PROVIDE OUTSIDE AIR CALCULAIONS
 AS PER ASHRAE 62-89.
  
 INDICATE ACCESS FOR FAN COILS FOR
 MAINTENANCE/SERVICIBLITY.
  
 PLEASE INDICATE FIRE DAMPER LOCATIONS ON
 PLAN.
  
 CLARIFY WHERE CONDENSATE TERMINATES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-07-12 Cont ID  
Sent By kstevens Date 2002-07-12 Time 15:29 Rev Time 0.00
Received By kstevens Date 2002-07-12 Time 15:28 Sent To  
Notes
2002-07-12 00:00:00REVISION OK - SANT. RISER DIAGRAM - FLAT
 DRAWING FOR KITCHEN - BAR AREAS

Review Stop P PLUMBING
Rev No 7 Status F Date 2002-05-16 Cont ID  
Sent By dpalmer Date 2002-07-12 Time 07:21 Rev Time 0.00
Received By kstevens Date 2002-05-16 Time 11:12 Sent To  
Notes
2002-05-16 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) FROM PREVIOUS REVIEWS, SHTS P1/P2
 BAR AREA 3 COMPARTMENT SINK SHALL DRAIN
 INDIRECTLY INTO A FLOOR SINK. FLOOR SINK
 UNDER ICE BIN SHALL NOT HAVE FUNNEL AS
 SHOWN ON RISER DIAGRAM.
 2) SHT P-1 FLOOR SINK TO BE UNDER FIX-
 TURE AT ICE BINS. PLEASE SHOW PIPING ON
 FLAT DRAWING FOR FLOOR SINK AND HAND
 SINK AS REQUIETED IN LAST TWO REVIEWS.
 3RD REQUEST.
 3) SHTS P1/P2 RISER DIAGRAM AND FLOOR
 PLAN STILL DO NOT MATCH. LAVS AND FLOOR
 DRAIN SHALL COME OFF BLDG DRAIN ON RISER
 DIAGRAM THE SAME AS ON THE FLOOR PLAN.
 3RD REQUEST.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 6 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 20:53 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 20:53 Sent To  
Notes
2002-04-24 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) FROM PREVIOUS REVIEW, SHTS P-1/P-2
 BAR AREA 3 COMPARTMENT SINK STILL DRAINS
 INTO THE FLOOR DRAIN. FLOOR SINK UNDER
 ICE BIN IS A SAFE WASTE WHICH IS NOT
 APPROVED. DOUBLE TRAPING IS NOT ALLOWED.
 VENT FLOOR SINKS PROPERLY.
 2) SHT P-1 FLOOR SINK TO BE UNDER FIX-
 TURE AT ICE BINS. PLEASE SHOW PIPING ON
 FLAT DRAWING FOR FLOOR SINK AND HAND
 SINK AS REQUESTED IN LAST REVIEW. 2ND
 REQUEST.
 3) SHTS P-1/P-2 RISER DIAGRAM AND FLOOR
 PLAN STILL DO NOT MATCH. LAVS AND FLOOR
 DRAIN SHALL COME BLDG DRAIN ON RISER
 DIAGRAM THE SAME AS ON THE FLOOR PLAN.
 THIS COMMENT FROM LAST REVIEW. SEE RED
 LINE MARKS ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status F Date 2002-02-19 Cont ID  
Sent By kstevens Date 2002-02-19 Time 10:38 Rev Time 0.50
Received By kstevens Date 2002-02-19 Time 10:38 Sent To  
Notes
2002-02-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
 REVISION - REVIEW
 1) SHTS P-1/P-2 W/C IN WOMENS RESTROOM
 THAT WAS MOVED NOT SHOWN ON RISER DIAG.
 2) SHTS P-1/P-2 BAR AREA. 3 COMP SINK TO
 AND ICE MACKINE TO DRAIN TO FLOOR SINK
 UNDER FIXTURE. FLOOR PLAN SHOWS A FLOOR
 DRAIN. A FLOOR SINK SHALL BE ADDED AND
 SHALL BE LOCATED UNDER FIXTURE FOR IN-
 DIRECT WASTE TO DRAIN INTO.
 3) SHT P-1 FLOOR SINK TO BE UNDER FIX-
 TURE AT ICE BINS. PLEASE SHOW PIPING ON
 FLAT DRAWING FOR FLOOR SINK AND HAND
 SINK.
 4) SHTS P-1/P-2 RISER DIAGRAM DOES NOT
 MATCH FLOOR PLAN DRAWING. LAVS AND FLOOR
 DRAIN SHALL COME OFF BLDG DRAIN ON RISER
 DIAGRAM THE SAME AS ON FLOOR PLAN.
 5) PLEASE CLOUD ALL CHANGES FOR EACH RE-
 VISION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status F Date 2002-01-07 Cont ID  
Sent By kstevens Date 2002-01-04 Time 19:23 Rev Time 0.50
Received By kstevens Date 2002-01-04 Time 19:22 Sent To  
Notes
2002-01-04 00:00:00PLUMBING LAYOUT CHANGED ON SHT A 1.0
 BUT NO PLUMBING REVISIONS INCLUDED FOR
 RISER DIAGRAMS OR PLUMBING SHEETS. KS

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-09-21 Cont ID  
Sent By pschmitz Date 2001-09-21 Time 14:25 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-15 00:00:00PLUMBING PLAN REVIEW RE-SUB APPROVED,
 WITH PROVISO, SEE PLUMBING PLANS. PES

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-07-14 Cont ID  
Sent By pschmitz Date 2001-07-14 Time 11:25 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-14 00:00:00PLUMBING PLAN REVIEW DENIED,SEE NOTES:
 PREVIOUS COMMENTS NOT ADDRESSED 6-3-01
 (1) PLUMBING PLAN REVIEW CAN NOT BE
 COMPLETED WITHOUT DEPT OF HOTEL BUSINESS
 REGULATION PLAN REVIEW.954-958-5520.
 (3) SHT A1.2 SHOW CLEAR FLOOR SPACE IN
 FRONT OF URINAL,FACBC-97 SEC4.18.3
 (8) SHT P-2,SEE ATTACHED GAS PERMIT APPL
 CATION REQUIRMENTS,NOT ADDRESSED (12)
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 562-659-8096 X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-03 Cont ID  
Sent By pschmitz Date 2001-06-03 Time 09:39 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-03 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW REQUIRED BEFORE PLUMBING
 PLAN REVIEW, CONTACT 954-958-5520.
 (2)SHT A1.0,OCCUPANCY AT 356 PERSONS, NO
 SEATING SHOWN FOR LOUNGE,DINING RM'S 1,2
 ALSO NUMBER OF EMPLOYEES, THIS MAY
 CHANGE THE NUMBER OF FACILITIES REQUIRED
 COMPLY W/FACBC 4.1.3(19)(A),AREAS OF
 ASSEMBLY WITH FIXED SEATING,SPC TAB 407.
 (3) SHT A1.2 WOMENS REST RM COMPLY WITH
 FACBC 97 FOR THE FOLLOWING.SEC 4.22.4
 WHEN 6 OR MORE STALLS ARE PROVIDE, ONE
 MUST BE ACCESSIBLE,GRAB BARS,DOOR SWING.
 W/C FLUSH HANDLE,MOUNTING SIDE SEC4.16.5
 W/C GRAB BARS BACK SIDE 36" SEC4.17.6
 DOORS SHALL NOT SWING INTO CLEAR FLOOR
 SPACE OF ANY FIXTURE SEC 4.23.2
 ONE OF THE LAVATORIES OUTSIDE OF THE H/C
 STALL IN THE MEN'S ,WOMEN'S REST RM
 SHALL COMPLY W/SEC 4.23.6 & 4.19
 (4) SHT P-1 MEN'S REST RM,H/C STALL
 FLR DRAIN REQ,SPC 94 SEC 409.4
 (5) SHT P-1 DISH WASHER,TO SANITARY
 SEWER. LOCAL ORD #2838-96 WPB RSTP.
 (6) SHT P-2 ITEMS #6,10,29 TO FLR SINKS
 SPC 94, SEC 921.4,HORZONTAL WASTE VENT.
 (7) SHT P-2ITEMS #4,27,30 NO RUNNING
 TRAPS,SPC 94 SEC 1001.8.3 INDIVIDUAL
 TRAPS FOR EACH COMPARTMENT.
 (8) SHT P-2,SEE ATTACHED GAS PERMIT
 APPLICATION REQUIRMENTS,SGC97, SEC 104.3
 ADDRESS EACH OF NINE ITEMS.
 (9) SHT P-1,PLBG NOTE 2.1 & SHT P-3,
 AIR CHAMBERS, SPC 94, SEC 607.8.3 TO BE
 ACCESSIBLE & RECHARGEABLE.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-19 Cont ID  
Sent By lsmith Date 2001-07-19 Time 09:58 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***