| Plan Review Stops For Permit 01051593 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-02-28 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-28 00:00:00 | REVISIONS ON SHEET A1.0 SEALED DATE | | | 2/14/02 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2002-01-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-07 |
Time |
17:58 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-07 00:00:00 | REVISIONS #1, #2 DEC.10/01 | | | DENIED!!!! | | | 1)- HANDICAPPED STALLS, FL ACC CODE | | | 4.17.3 FIG. 30 "E" REQUIRES THE WATER | | | CLOSET SHALL BE LOCATED IN THE CORNER | | | DIAGONAL TO THE DOOR!!!!!AS PER THE | | | FIRST SET OF REVISIONS!!!!! | | | | | | 2)- FRONT ENTRY,(FOYER) SBC 1019.2.3 | | | REMOVAL OF PERMANENT BARRIER SEPERATING | | | THE WAITING AREA FROM THE REQUIRED CLEAR | | | WIDTH FOR EXITS. | | | | | | 3)- DELETION OF 2 HR.HORIZONTAL PASSAGE | | | WAY. BEHIND STORAGE UNIT # 1!!!!!! | | | | | | 4)- BAR AREA # 2, SHOW EGRESS PATH , | | | CLEAR FLOOR AREA. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-28 |
Time |
09:46 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2001-09-28 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | PROVISO: 9/28/01 | | | 1997 FLORIDA ACCESSIBILITY CODE: | | | | | | 1)- STAGE PLATFORM VERTICAL ACCESS- | | | IBILITY 4.1.3. WILL REQUIRE VERTICAL | | | ACCESSIBILITY EITHER BY RAMP OR LIFT. | | | | | | 2)- FL ACC. CODE 4.8.5 HANDRAILS WILL | | | BE REQUIRED ON THE RAMP IF IT IS OVER | | | 6" IN HEIGTH. | | | | | | THIS INFORMATION WILL BE REQUIRED BY THE | | | FRAMING INSPECTION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EXT 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-17 |
Time |
17:42 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-09-17 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2001-09-17 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT #01051593 | | | 550 S ROSEMARY # 250 | | | ACCESS CONSTRUCTION TEAM | | | | | | 1)- STAGE (PLATFORM) VERTICAL ACCESSIBIL | | | ITY 4.1.3 RAMPS ARE PERMISSIBLE. | | | 2)- FL ACC CODE 4.8.5 HANDRAILS IF THE | | | PLATFORM IS OVER 6" HIGH. | | | 3)- PROVIDE PRODUCT APPROVAL FOR ALL | | | GLAZED EXTERIOR OPENINGS. IF THE GLAZED | | | OPENIINGS DO NOT HAVE LARGE MISSLE | | | RESISTANCE TESTING STORM SHUTTERS WILL | | | BE REQUIRED PRODUCT APPROVAL WILL BE | | | REQUIRED. | | | 4)- FL ACCESS CODE 4.1.7.3(2) THE ACCESS | | | IBLE WATER CLOSET SHALL BE LOCATED IN | | | THE CORNER DIAGONAL TO THE DOOR. | | | 5)- SHEET A2.2. DETAIL D BENCH & COUNTER | | | SECTION STORAGE COMPARTMENT , MAY | | | REQUIRE FIRE SPRINKLERS. | | | 6)- RAISED PLATFORMS AND RAMPS TO COMPLY | | | WITH SBC 403.2.4.1/403.2.4.2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-30 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-07-31 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2001-07-30 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01051593 | | | 550 S ROSEMARY AVE # 250 | | | ACCESS CONSTRUCTION TEAM | | | (813) 274-7770 | | | | | | SBC= STANDARD BUILDING CODE | | | SBC*= STANDARD BUILDING CODE AMENDMENTS | | | FL ACC= 1997 FLORIDA ACCESSIBILITY CODE | | | | | | 1)- SHOWROOM LEVELS 2.0, 2.1, 2.2 & | | | LEVEL 3.0 ARE IN AN ASSEMBLY OCCUPANCY | | | OCCUPANCY. SBC 1019.8: IN BUILDINGS OF | | | GROUP A OCCUPANCY, FLIGHTS OF LESS THAN | | | (3) THREE RISERS SHALL NOT BE USED IN | | | INTERIOIR OR EXTERIOR STAIRWAYS, EXIT | | | PASSAGE WAYS, AISLES, AT ENTRANCES OR | | | ELSEWHERE IN CONNECTION WITH REQUIRED | | | EXITS. TO OVERCOME LESSER DIFFERENCES | | | IN LEVEL, RAMPS MAY BE USED. | | | | | | 2)- WHERE THERE IS A ELEVATION CHANGE, | | | LEVEL 2.0, 2.1, 2.2 & 3.0 VERTICAL | | | ACCESSIBILITY MUST BE PROVIDED. FL | | | ACCESSIBILITY CODE 4.1.3 THE STAGE ALSO | | | MUST MEET THE VERTICAL ACCESSIBILITY | | | REQUIREMENTS BUT DEPENDING ON THE HEIGTH | | | OF THE STAGE HANDRAIL REQUIUREMENTS | | | FL ACC. 4.8.2. | | | | | | 3)- FL ACCESSIBILITY CODE: 4.8.3 CLEAR | | | WIDTH, RAMPS THAT ARE USED AS A MEANS OF | | | EGRESS SHALL NOT BE LESS THAN 44" WIDE. | | | | | | 4)- FL ACC CODE RAMPS 4.8.4 (LEVEL 2.2) | | | ALL LANDINGS ON RAMPS SHALL BE NOT LESS | | | THAN 60" CLEAR, AND THE BOTTOM OF EACH | | | RAMP SHALL HAVE NOT LESS THAN 72" OF | | | STRAIGHT AND LEVEL SURFACE. | | | | | | 5)_ FL ACC CODE 4.8.5 HANDRAILS: IF A | | | RAMP HAS A RISE GREATER THAN 6" OR A | | | HORIZONTAL PROJECTION GREATER THAN 72", | | | THEN IT SHALL HAVE HANDRAILS ON BOTH | | | SIDES. | | | | | | 6)- SHEET E.5 INDICATES THAT THE 225KVA | | | TRANSFORMER IS IN THE ELECTRIC ROOM, | | | WHAT IS SUPPORTING THE TRANSFORMER? | | | | | | 7)- REVISE THE LIFE SAFETY PLAN TO | | | INCLUDE LEVEL 2.2 64 PEOPLE FOR FIXED | | | SEATING AND 64' OF BAR @ 2' PER PERSON | | | OR ANOTHER 32 PEOPLE. | | | | | | 8)- THE CORRIDOR BEHIND THE KITCHEN WILL | | | NEED TO BE AN EXIT CORRIDOR, SINCE THIS | | | IS AN ASSEMBLY OCCUPANCY THE TABLE | | | 705.1.2 OF THE SBC REQUIRES A 2 HR. | | | RATING ON WALLS CEILING AND FLOOR. ALL | | | OPENINGS WILL REQUIRE AN 1 1/2 HR. OPEN- | | | ING PROTECTION, AND THE CORRIDOR HAS TO | | | EXTEND TO THE EXTERIOR OF THE BUILDING. | | | | | | 9)- PROVIDE PRODUCT APPROVAL ON ALL | | | EXTERIOR GLAZING, TO INDICATE CONFORMITY | | | WITH IMPACT REQUIREMENTS FOR HURRICANE | | | PROTECTION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-06-18 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2001-06-18 |
Time |
12:40 |
Rev Time |
3.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-18 00:00:00 | BUILDING PLAN REVIEW COMMENTS 6/18. | | | 1. PAY IMPACT FEES, PALM BEACH COUNTY TO | | | STAMP PLANS. | | | 2. SHEET A1.0, PROVIDE LIFE SAFETY PALN | | | FOR LOUNGE, DINING 1 AND 2, BAR AND | | | EXTERIOR SEATING AREAS. INDICATE EXIT | | | ILES FOR ALL AREAS. | | | 3. INDICATE HANDICAPPED ACCESS FOR | | | LEVELS 2 AND 2.1. RAMPS REQUIRED SEE | | | SBC 1019.8 AND FLORIDA ACCESSABILITY | | | CODE 4.1.3. | | | | | | 4. SHEETS A1.1, A1.2 AND A2.1 WHERE | | | REVIWED WITHOUT APPROVAL OF DESIGNER OF | | | RECORD INITIALS AND DATE. | | | 5. SHEET E.5 PROVIDE ENGINEERING ON 225 | | | KVA TRASNSFORMER SUSPENDED FROM BOTTOM | | | COURD OF ROOF TRUSSES. | | | 5. SHEET AC.2 ENGINNER TO PROVIDE DESIGN | | | FOR FAN COIL SUPPORT ATTACHED TO BOTTOM | | | COURD OF ROOF TRUSSES. | | | 6. PROVIDE INFORMATION ON FIRE STOPPING | | | SYSTEMS TO BE USED ON ALL FIRE RATED | | | HORZONTIALL AND VERTICAL PENATRATIONS. | | | 7. ASSEMBLEY OCCUPANCY, PROVIDE FIRE | | | RATING INFORMATION ON ALL WALL AND | | | FLOORS | | | 8. INFORMATION SUBMITTED IS NOT | | | SUFFICIENT TO DETERMINE CLASS OF | | | OCCUPANCY MAY BE LARGE ASSEMBLEY (OVER | | | ONE THOUSAND PEOPLE). | | | 9. SHEET AC.2 KITCHEN HOOD DETAIL | | | PENETRATES THE FIRE RATED WALL SHOWN ON | | | SHEET A1.1 AND 2, WALL REQUIRES UL | | | LISTING, DAMPERS ETC. | | | 10. PROVIDE INFORMATION ON ALL EXTERIOR | | | GLAZING TO INDICATE CONFORMITY WITH | | | IMPACT REQUIREMENTS FOR HURRICANE | | | PROTECTION. | | | | | | PLANS LACK MINUMIM INFORMATION REQUIRED | | | TO BE CONSIDERED FOR PERMIT ISSUANCE. | | | CALL BILL STAPLES AT 561-659-8096 EXT. | | | 8315 FOR ASSISTANCE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2002-07-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-12 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-12 |
Time |
07:21 |
Sent To |
P |
|
| Notes |
| 2002-07-12 00:00:00 | ********* NOTE ********** | | | | | | 1)NOTE: PLEASE NOTE NEW SHEETS FOR | | | ELECTRICAL RISER. PLEASE NOTE THAT | | | FIELD INSPECTION IS STILL REQ`D. NO | | | ELECTRICAL FINAL DONE. | | | MADE PLANS INTO ALL NEW SETS FOR RECORD | | | AND FIELD SET. | | | KEEP OLD PLANS UNTIL AFTER C.O. FOR | | | RECORD. SEE DV PALMER FOR ANY QUESTIONS. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2002-05-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-16 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-16 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2002-05-16 00:00:00 | ************ UNSAT 4TH TIME ********** | | | | | | 1)NOTE: PLEASE NOTE THAT THE PLANS DO | | | NOT CORRELATE. THESE HAVE BEEN THE | | | SAME COMMENTS FOR THE LAST FOUR SUBMITT- | | | -ALS FOR ELECTRICAL REVISIONS. | | | PLEASE NOTE THAT A 4X FEE IS NOW ASSESS- | | | ED PER FS.553-80(2B) TO THE DESIGN | | | PROFESSIONAL. PLANS WILL NOT BE RELEASED | | | UNTIL FEE IS PAID. THEN PLANS MAY GO | | | BACK OUT. IF PLANS COME IN AGAIN WITH | | | THE SAME COMMENTS, THEN I WILL BE FORCED | | | TO TURN THE DESIGN PROFESSIONAL INTO THE | | | STATE. | | | PLEASE NOTE AS OF TODAYS DATE, THE | | | DESIGN PROFESSIONAL HAS NOT CONTACTED | | | ME FOR ANY COMMENTS/QUESTIONS ETC. | | | | | | PLEASE CORRELATE PLANS AND SUBMIT FOR | | | REVIEW. ONCE AGAIN, IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2002-04-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-12 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-12 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2002-04-12 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PANELS STILL | | | DO NOT CORRELATE!!!! | | | PLEASE NOTE THAT TOP OF PANELS NOW | | | SHOW 200A MCB BUT CONDUCTOR SIZES BELOW | | | PANEL SCHEDULES STILL SHOW WIRE FOR | | | 150A`S> | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT RISER | | | DIAGRAM WAS NOT REVISED. PLEASE NOTE, | | | RISER DIAGRAM DOES NOT CORRELATE EITHER. | | | | | | 3)NOTE: PLEASE CORRECT AND PUT SETS OF | | | PLANS TOGETHER INTO TWO WORKING SETS. | | | PLEASE NOTE THAT THERE ARE REVISED SHEET | | | -S NOT PLACE IN SETS ETC. | | | | | | 4)NOTE: PLEASE NOTE THAT UNDER FS/ FAC | | | THESE PLANS HAVE BEEN DENIED FOR THE | | | SAME COMMENTS FOR THREE TIMES AND ARE | | | SUBJECT TO FOUR TIMES THE PLAN REVIEW | | | FEE!!!! PLEASE SEE SEC 553-80 FAC. | | | IF PLANS COME BACK IN AND ARE NOT | | | CORRECTED COMPLETELY, THERE WILL BE A | | | FOUR TIMES FEE AND A RED TAG WILL BE | | | WRITTEN IN VIOLATION OF TCO/CO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-19 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-19 |
Time |
06:36 |
Sent To |
|
|
| Notes |
| 2002-02-19 00:00:00 | ****************** UNSAT ************ | | | | | | PLEASE NOTE THAT THESE PLANS ARE FOR | | | FINAL/CO.PLEASE NOTE THAT PLANS NEED TO | | | CORRELATE COMPLETELY WITH JOBSITE. | | | | | | 1)NOTE: PLEASE NOTE/VERIFY THAT ALL | | | PANELS ARE 200AMP. PLEASE NOTE THAT PER | | | FEILD INSPECTIONPANELS 'C,D,E,F' ARE | | | ALL 200A MCB. | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT SOME | | | PANELS ARE SHOWN AS RECESSED? PLEASE | | | NOTE THAT 'A,B,C,D,E,F' ARE ALL SURFACE | | | MOUNTED. | | | | | | PLEASE VERFIY AND MAKE THE CHANGES AS | | | NEEDED.PLEASE SUBMIT FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2001-12-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-12 |
Time |
07:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-12 |
Time |
07:27 |
Sent To |
|
|
| Notes |
| 2001-12-12 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE, THAT AS PER CONVER- | | | -SATION WITH THE ELECTRICAL INSPECTOR, | | | PLEASE PROVIDE LAYOUT OF THE ELECTRICAL | | | ROOM ON PLANS AS IT IS IN THE FIELD. | | | | | | 2)NOTE: PLEASE NOTE, LOAD SHOWN FOR | | | PANEL "E IS DIFFERENT FROM LOAD CALCULA- | | | -TION FOR ALL PANELS. | | | | | | 3)NOTE: PLEASE PROVIDE LOAD ON LINE SIDE | | | OF TRANSFORMER. | | | | | | 4)NOTE: PLEASE CLARFIY HOW MANY CONDUITS | | | ARE COMING FROM LOAD SIDE OF TRANSFORMER | | | TO DISC AND FROM DISC TO 12"X12"X9' | | | GUTTER. PER ELECTRICAL INSPECTOR, THE | | | FIELD INSTALLATION HAS ONLY ONE 2 1/2" | | | CONDUIT INSTALLED WITH 4-3/0`S AND | | | SOME CONFUSION OF THE ELECTRICAL CONTRAC | | | TOR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND PERHAPS MEET WITH THE ELEC | | | CONTRACTOR AND/OR ELECTRICAL INSPECTOR | | | ON THE JOB. | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-09-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-19 |
Time |
22:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-19 |
Time |
22:12 |
Sent To |
|
|
| Notes |
| 2001-09-19 00:00:00 | *************** NOTES REDLINED ******** | | | PLEASE NOTE NOTES REDLINED ON PLANS FOR | | | ELECTRICAL CONTRACTOR AND INSPECTOR. | | | SOME ITEMS STILL NEED TO BE FIELD | | | VERIFIED. PLEASE NOTE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-07-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-22 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-22 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2001-07-22 00:00:00 | ****************UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW GROUNDING REQUIRED | | | FOR TRANSFORMER. TO WHERE? | | | | | | 2)NOTE: PLEASE NOTE THAT IN THE "96" NEC | | | IT NOTES UNDER 450-21B TRANSFORMERS TO | | | BE 80C OR HIGHER AND "99" NEC CLASS 155 | | | OR HIGHER. PLANS SHOW 80F? | | | WE ARE UNDER THE "99" NEC AND THEREFORE | | | NOTE FOR TRANSFORMER NEEDS TO CLASS 155. | | | | | | | | | 3)NOTE: PLEASE SUBMIT CLARIFICATION ON | | | 400A DISCONNECT FROM EXISTING ELEC ROOM. | | | IS IT FUSED AT 250A`S?? PLANS SHOW A | | | 400A DISC FEEDING AT 250A DISC W/ 250A | | | FUSES? PLEASE CLARIFY. | | | | | | 4)NOTE: PLEASE NOTE THAT NO AIC RATINGS | | | WERE SUBMITTED FOR LINE AND LOAD DISC`S | | | FOR TRANSFORMER. | | | | | | 5)NOTE: PLEASE NOTE THAT ALL PANEL | | | SCHEDULES SHOW PANELS BEING RECESSED, | | | AND PLAN ON E-1 SHOWS PANELS AS SURFACE | | | MOUNTED? PLEASE CLARIFY. | | | PLEASE NOTE THAT AS PER ELECTRICAL ROOM | | | LAYOUT ON E-1 AND SCALE SHOWN BELOW | | | AT 1/2" TO 1'. THE CLEARENCES DON'T SHOW | | | AS BEING ENOUGH. ALSO PLEASE NOTE THAT | | | DURING CONTRUCTION WE HAVE RUN INTO | | | MORE OFTEN THAN NOT THAT ELECTRICAL | | | ROOMS ARE NOT BUILT LARGE ENOUGH. | | | MANY WALL HAVE BEEN MOVED IN THE PAST TO | | | MEET CODE. PLEASE VERIFY THAT ALL | | | CLEARENCES MEET OR EXCEED REQ`D SPACES | | | FOR 110-26 AND 450-21. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-12 |
Time |
23:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-12 |
Time |
23:04 |
Sent To |
|
|
| Notes |
| 2001-06-12 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | NEEDS TO MEET LOCAL CODE PER ART 210-50 | | | STORAGE AREAS/ EVERY 20' OF | | | UNENCUMBEREDWALL SPACE AND OFFICE AREAS | | | EVERY 12" | | | THE AREAS WHERE PATRONS/PUBLIC LOOKS TO | | | BE AREA IN QUESTION. PLEASE NOTE EVERY | | | 20' AND PLACE BRANCH CIRCUIT #`S ON | | | PLANS THAT CORRELATE WITH PANEL SCHEDULE | | | | | | | | | 2)NOTE: PLEASE NOTE THAT PANEL"C" PANEL | | | SCHEDULE SHOWS MLO AND RISER SHOWS MCB. | | | PLEASE CALRIFY. | | | | | | 3)NOTE: PLEASE NOTE THAT GROUNDING FOR | | | TRANSFORMER NEEDS TO BE CLARIFIED. PER | | | 450-5 AND 450-10 | | | | | | 4)NOTE: PLEASE NOTE 450-13 FOR ACESS. | | | PLEASE SHOW TRANSFORMER LOCATION ON | | | PLANS.PLANS NOTE TRANSFORMER HANGING | | | FROM CEILING BUT NOT WHERE. | | | PLEASE ALSO NOTE THAT ART 450-21B FOR | | | TRANSFORMERS OVER 112.5 KVA NEED TO BE | | | INSTALLED IN A TRANSFORMER VAULT. | | | | | | 5)NOTE: PLEASE NOTE WIRE SIZE SHOWN FOR | | | PANEL "B" ON E-5AS 4-1/0`S FOR 200A. | | | PLEASE CORRECT. | | | | | | 6)NOTE: PLEASE NOTE ACCESSABLITY FOR | | | ALL DISCONNECTS AND CLEARENCES PER | | | 11-26. PLEASE CLARIFICATION FOR DISCO- | | | -NNECTS FOR TRANSFORMER// LINE AND LOAD. | | | | | | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATING WAS | | | SUBMITTED FOR PANELS, BUT NOT FOR MAIN | | | OR DISC. | | | | | | 8)NOTE: PLEASE FEILD VERIFY SIZE OF | | | EXSITING CONDUCTORS SHOWN FOR MAIN. | | | PLEASE CLARIFY FOR ART 240-3B | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-19 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-19 |
Time |
12:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2001-12-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-12 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-12 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-25 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-25 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-07-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-07-19 |
Time |
09:59 |
Rev Time |
0.25 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-19 00:00:00 | SEPARATE FIRE SPRINKLER PERMIT#01070931 | | | ISSUED AND APPROVED PER MEC LS | | | OTHER ITEMS ADDRESSED BY MEC NOT APPROVE | | | D AS OF THIS DATE LSWILL GIVE BACK TO | | | RETT TO LOOK AT. LS |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-05 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-05 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2001-07-05 00:00:00 | 1) PREVIOUS PLAN REVIEW COMMENTS FROM | | | DESIGNER NOT ATTACHED TO PLANS. | | | 2) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 3) EXITS NOT SEPARATED 1/2 THE DIAGONAL | | | DISTANCE IN THE SHOWROOM LEVEL ONE. | | | 4) STORAGE TWO HAS WHAT FIRE SEPARATION | | | FROM THE EXIT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-06-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-01 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-01 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2001-06-01 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. PLEASE PROVIDE FIRE | | | SPRINKLER DRAWINGS. | | | 2) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 3) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED WITH PLANS. | | | 4) PANIC HARDWARE REQUIRED ON ALL | | | EXIT DOORS SINCE OCCUPANCY IS EXPECTED | | | TO BE OVER 100 PERSONS. FIRE EXIT PANIC | | | HARDWARE REQUIRED FOR ALL FIRE DOORS. | | | 5) NO SEATING SHOWN FOR LOUNGE OR DINING | | | ROOM NUMBER 2. | | | 6) PLEASE EXPLAIN EXITING RATIONALE TO | | | THIS OFFICE. THE STAIRWELL EXIT DOOR | | | NEAR OFFICE NUMBER 2 IS SHARED WITH | | | ANOTHER ASSEMBLY OCCUPANCY. ONLY HALF | | | CREDIT WILL BE GIVEN FOR THIS STAIR | | | SINCE IT IS SHARED. THE FOUR SWINGING | | | DOORS FROM SHOWROOM LEVEL ONE OPEN | | | INTO LOUNGE WHERE ONLY TWO SWINGING | | | DOORS ARE PROVIDED TO ENTER THE FOYER | | | AREA. PLEASE INDICATE ON PLANS WHERE THE | | | MAIN EXIT IS PROVIDED TO ACCOMODATE | | | AT LEAST FIFTY PERCENT OF THE TOTAL | | | OCCPANT LOAD. | | | 7) NO BAR STOOLS SHOWN FOR BAR NUMBER | | | ONE. | | | 8) PLEASE PROVIDE A LIFE SAFETY PLAN TO | | | THIS OFFICE WITH THE NEXT SUBMITTAL. | | | 9) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE HOOD,DUCT AND EXTINGUISHING | | | SYSTEMS. | | | 10) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE FIRE ALARM SYSTEM REMODEL. | | | 11) PLEASE INDICATE CONSTRUCTION TYPE | | | FOR STAGE. | | | 12) PLEASE INDICATE NUMBER OF STAFF | | | PERSONS SO THEY CAN BE INCLUDED IN | | | OCCUPANT LOAD | | | 13) NO EXIT SIGNS SHOWN NEAR DOUBLE | | | DOORS FROM SHOWROOM NUMBER ONE. | | | 14) ANY CHANGES IN ELEVATION LESS THAN | | | TWENTY ONE INCHES SHALL BE BY RAMPS. | | | 15) PLEASE INDICATE IF THERE ARE ANY | | | WAITING SPACES IN THE SPACE. | | | 16) PLEASE EXPLAIN US OF NEW PATIO. | | | 17) PLEASE IDENTIFY IF A COLUMN IS | | | PRESENT NEAR EXIT DOOR NEAR BAR NUMBER | | | ONE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2002-04-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-10 |
Time |
08:18 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-04-10 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2002-04-10 00:00:00 | NO MECHANICAL REVISIONS WERE SUBMITTED | | | AT THIS TIME. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-25 |
Time |
08:32 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-09-25 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2001-09-25 00:00:00 | *******************PROVISO************** | | | | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, AND WALK-IN | | | COOLER/FREEZER.PLEASE SUBMIT PLANS | | | AND MANUFACURER INFORMATION WITH PERMIT | | | APPLICATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-07-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-09 |
Time |
16:34 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-07-09 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2001-07-09 00:00:00 | *******************DENIED*************** | | | | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION AND WALK-IN COOLERS. | | | PLEASE PROVIDE PLANS WITH MANUFACTURER | | | SUBMITTAL DATA WITH PERMIT APPLICATIONS. | | | | | | PROVIDE LOCATION OF THE FLUE PIPE FOR | | | GAS WATER HEATER. | | | | | | SUPPLY DUCT TO STORAGE ROOM APPEARS TO | | | PENETRATE A RATED WALL, FIRE DAMPER IS | | | REQUIRED.PLEASE PROVIDE MANUFACTURER | | | DETAILS FOR COMPLIANCE WITH 1997 SMC | | | 610.1.2.LOCATIONS OF FIRE DAMPERS | | | NEEDTO BE INDICATED ON PLAN. | | | | | | NOTE:NO COMBUSTIBLES ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS 659-8096 EXT. 8338. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-06-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-09 |
Time |
08:36 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-06-09 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2001-06-09 00:00:00 | ********************DENIED************** | | | | | | | | | NOTE:ADDITIONAL PLANS AND PERMITS | | | REQUIRED FOR HOOD SYSTEM, FIRE | | | SUPRESSION AND WALK-IN COOLERS. | | | PLEASE SUBMIT PLANS AND | | | MANUFACTURER DETAILS WITH PERMIT | | | APPLICATION. | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULAIONS | | | AS PER ASHRAE 62-89. | | | | | | INDICATE ACCESS FOR FAN COILS FOR | | | MAINTENANCE/SERVICIBLITY. | | | | | | PLEASE INDICATE FIRE DAMPER LOCATIONS ON | | | PLAN. | | | | | | CLARIFY WHERE CONDENSATE TERMINATES. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2002-07-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-12 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-12 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2002-07-12 00:00:00 | REVISION OK - SANT. RISER DIAGRAM - FLAT | | | DRAWING FOR KITCHEN - BAR AREAS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2002-05-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-12 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-16 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2002-05-16 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEWS, SHTS P1/P2 | | | BAR AREA 3 COMPARTMENT SINK SHALL DRAIN | | | INDIRECTLY INTO A FLOOR SINK. FLOOR SINK | | | UNDER ICE BIN SHALL NOT HAVE FUNNEL AS | | | SHOWN ON RISER DIAGRAM. | | | 2) SHT P-1 FLOOR SINK TO BE UNDER FIX- | | | TURE AT ICE BINS. PLEASE SHOW PIPING ON | | | FLAT DRAWING FOR FLOOR SINK AND HAND | | | SINK AS REQUIETED IN LAST TWO REVIEWS. | | | 3RD REQUEST. | | | 3) SHTS P1/P2 RISER DIAGRAM AND FLOOR | | | PLAN STILL DO NOT MATCH. LAVS AND FLOOR | | | DRAIN SHALL COME OFF BLDG DRAIN ON RISER | | | DIAGRAM THE SAME AS ON THE FLOOR PLAN. | | | 3RD REQUEST. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2002-04-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-24 |
Time |
20:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-24 |
Time |
20:53 |
Sent To |
|
|
| Notes |
| 2002-04-24 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEW, SHTS P-1/P-2 | | | BAR AREA 3 COMPARTMENT SINK STILL DRAINS | | | INTO THE FLOOR DRAIN. FLOOR SINK UNDER | | | ICE BIN IS A SAFE WASTE WHICH IS NOT | | | APPROVED. DOUBLE TRAPING IS NOT ALLOWED. | | | VENT FLOOR SINKS PROPERLY. | | | 2) SHT P-1 FLOOR SINK TO BE UNDER FIX- | | | TURE AT ICE BINS. PLEASE SHOW PIPING ON | | | FLAT DRAWING FOR FLOOR SINK AND HAND | | | SINK AS REQUESTED IN LAST REVIEW. 2ND | | | REQUEST. | | | 3) SHTS P-1/P-2 RISER DIAGRAM AND FLOOR | | | PLAN STILL DO NOT MATCH. LAVS AND FLOOR | | | DRAIN SHALL COME BLDG DRAIN ON RISER | | | DIAGRAM THE SAME AS ON THE FLOOR PLAN. | | | THIS COMMENT FROM LAST REVIEW. SEE RED | | | LINE MARKS ON PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-19 |
Time |
10:38 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-02-19 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2002-02-19 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 - SGC-97 | | | REVISION - REVIEW | | | 1) SHTS P-1/P-2 W/C IN WOMENS RESTROOM | | | THAT WAS MOVED NOT SHOWN ON RISER DIAG. | | | 2) SHTS P-1/P-2 BAR AREA. 3 COMP SINK TO | | | AND ICE MACKINE TO DRAIN TO FLOOR SINK | | | UNDER FIXTURE. FLOOR PLAN SHOWS A FLOOR | | | DRAIN. A FLOOR SINK SHALL BE ADDED AND | | | SHALL BE LOCATED UNDER FIXTURE FOR IN- | | | DIRECT WASTE TO DRAIN INTO. | | | 3) SHT P-1 FLOOR SINK TO BE UNDER FIX- | | | TURE AT ICE BINS. PLEASE SHOW PIPING ON | | | FLAT DRAWING FOR FLOOR SINK AND HAND | | | SINK. | | | 4) SHTS P-1/P-2 RISER DIAGRAM DOES NOT | | | MATCH FLOOR PLAN DRAWING. LAVS AND FLOOR | | | DRAIN SHALL COME OFF BLDG DRAIN ON RISER | | | DIAGRAM THE SAME AS ON FLOOR PLAN. | | | 5) PLEASE CLOUD ALL CHANGES FOR EACH RE- | | | VISION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2002-01-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-04 |
Time |
19:23 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-01-04 |
Time |
19:22 |
Sent To |
|
|
| Notes |
| 2002-01-04 00:00:00 | PLUMBING LAYOUT CHANGED ON SHT A 1.0 | | | BUT NO PLUMBING REVISIONS INCLUDED FOR | | | RISER DIAGRAMS OR PLUMBING SHEETS. KS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-09-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-09-21 |
Time |
14:25 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-15 00:00:00 | PLUMBING PLAN REVIEW RE-SUB APPROVED, | | | WITH PROVISO, SEE PLUMBING PLANS. PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-07-14 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-07-14 |
Time |
11:25 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-14 00:00:00 | PLUMBING PLAN REVIEW DENIED,SEE NOTES: | | | PREVIOUS COMMENTS NOT ADDRESSED 6-3-01 | | | (1) PLUMBING PLAN REVIEW CAN NOT BE | | | COMPLETED WITHOUT DEPT OF HOTEL BUSINESS | | | REGULATION PLAN REVIEW.954-958-5520. | | | (3) SHT A1.2 SHOW CLEAR FLOOR SPACE IN | | | FRONT OF URINAL,FACBC-97 SEC4.18.3 | | | (8) SHT P-2,SEE ATTACHED GAS PERMIT APPL | | | CATION REQUIRMENTS,NOT ADDRESSED (12) | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS 562-659-8096 X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-06-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-03 |
Time |
09:39 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-03 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) DEPT OF HOTEL BUSINESS REGULATION | | | PLAN REVIEW REQUIRED BEFORE PLUMBING | | | PLAN REVIEW, CONTACT 954-958-5520. | | | (2)SHT A1.0,OCCUPANCY AT 356 PERSONS, NO | | | SEATING SHOWN FOR LOUNGE,DINING RM'S 1,2 | | | ALSO NUMBER OF EMPLOYEES, THIS MAY | | | CHANGE THE NUMBER OF FACILITIES REQUIRED | | | COMPLY W/FACBC 4.1.3(19)(A),AREAS OF | | | ASSEMBLY WITH FIXED SEATING,SPC TAB 407. | | | (3) SHT A1.2 WOMENS REST RM COMPLY WITH | | | FACBC 97 FOR THE FOLLOWING.SEC 4.22.4 | | | WHEN 6 OR MORE STALLS ARE PROVIDE, ONE | | | MUST BE ACCESSIBLE,GRAB BARS,DOOR SWING. | | | W/C FLUSH HANDLE,MOUNTING SIDE SEC4.16.5 | | | W/C GRAB BARS BACK SIDE 36" SEC4.17.6 | | | DOORS SHALL NOT SWING INTO CLEAR FLOOR | | | SPACE OF ANY FIXTURE SEC 4.23.2 | | | ONE OF THE LAVATORIES OUTSIDE OF THE H/C | | | STALL IN THE MEN'S ,WOMEN'S REST RM | | | SHALL COMPLY W/SEC 4.23.6 & 4.19 | | | (4) SHT P-1 MEN'S REST RM,H/C STALL | | | FLR DRAIN REQ,SPC 94 SEC 409.4 | | | (5) SHT P-1 DISH WASHER,TO SANITARY | | | SEWER. LOCAL ORD #2838-96 WPB RSTP. | | | (6) SHT P-2 ITEMS #6,10,29 TO FLR SINKS | | | SPC 94, SEC 921.4,HORZONTAL WASTE VENT. | | | (7) SHT P-2ITEMS #4,27,30 NO RUNNING | | | TRAPS,SPC 94 SEC 1001.8.3 INDIVIDUAL | | | TRAPS FOR EACH COMPARTMENT. | | | (8) SHT P-2,SEE ATTACHED GAS PERMIT | | | APPLICATION REQUIRMENTS,SGC97, SEC 104.3 | | | ADDRESS EACH OF NINE ITEMS. | | | (9) SHT P-1,PLBG NOTE 2.1 & SHT P-3, | | | AIR CHAMBERS, SPC 94, SEC 607.8.3 TO BE | | | ACCESSIBLE & RECHARGEABLE. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-07-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-07-19 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|