Plan Review Details - Permit 01051544
Plan Review Stops For Permit 01051544
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-06 Cont ID  
Sent By mcarsill Date 2001-06-06 Time 10:07 Rev Time 0.00
Received By mcarsill Date 2001-06-06 Time 10:07 Sent To  
Notes
2001-06-06 00:00:001) THE ABOVEGROUND FUEL TANK IS TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 30,
 THE FLAMMABLE AND COMBUSTIBLE LIQUIDS
 CODE. THE ROOM WHERE THIS STORAGE TANK
 IS TO BE INSTALLED IS TO BE AT LEAST
 TWO HOUR FIRE RATED, BE EQUIPPED WITH A
 FOUR INCH SILL, BE EQUIPPED WITH FIRE
 SPRINKLERS, AND HAVE AT LEAST A B
 LABELED FIRE DOOR WITH A CLOSER. TANK
 IS TO BE LABELED BY UL OR FM.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-01 Cont ID  
Sent By mcarsill Date 2001-06-01 Time 11:35 Rev Time 0.00
Received By mcarsill Date 2001-06-01 Time 11:35 Sent To  
Notes
2001-06-01 00:00:001) NO DRAWINGS PROVIDED WITH PLANS.
 DRAWINGS NEED TO BE PROVIDED SINCE A
 SEPARATE PERMIT APPLICATION HAS BEEN
 APPLIED FOR.
 2) NO CUT SHEETS OR PRODUCT APPROVALS
 PROVIDED FOR TANKS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-12 Cont ID  
Sent By pkrauss Date 2001-06-06 Time 16:49 Rev Time 0.45
Received By pkrauss Date 2001-06-06 Time 16:49 Sent To  
Notes
2001-06-06 00:00:00******************PROVISO***************
  
  
 SHALL COMPLY WITH 1997 SMC CHAPTER 14.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-01 Cont ID  
Sent By ndenmark Date 2001-06-01 Time 13:28 Rev Time 0.25
Received By ndenmark Date 2001-06-01 Time 13:28 Sent To  
Notes
2001-06-01 00:00:00PROVIDE INFORMATION AS REQUIRED ON FIRE
 REVIEW