Plan Review Details - Permit 01051483
Plan Review Stops For Permit 01051483
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-08-03 Cont ID  
Sent By rmcdouga Date 2001-08-03 Time 13:52 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-08-03 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE 15 LITE FRENCH DOORS AS SHOWN
 ON PLANS
  
 2) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS PRIOR TO
 INSTALLATION. (2 COPIES)
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-23 Cont ID  
Sent By rmcdouga Date 2001-06-23 Time 11:29 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-23 00:00:00*************BUILDING UNSAT*************
  
 1) STRUCTURE IS LOCATED IN AN A5 FLOOD
 ZONE WITH A BASE FLOOD ELEVATION OF (7)
 FEET. PROVIDE FINISH FLOOR ELEVATION OF
 EXISTING STRUCTURE. CITY CODE REQUIRES
 THAT ALL NEW CONSTRUCTION OR SUBSTANTIAL
 IMPROVEMENT OF ANY EXISTING RESIDENTIAL
 STRUCTURE SHALL HAVE THE LOWEST FLOOR
 ELEVATED TO SIX (6) INCHES ABOVE THE
 BASE FLOOD ELEVATION.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 * ALL EXTERIOR WINDOWS AND DOORS
 - DOUBLE FRENCH DOORS
 - WINDOWS (SINGLE HUNG,CASEMENT,ETC.)
 - SINGLE OUTSWING DOORS (ROOMS 115,119)
  
 5) MISSLE IMPACT PROTECTION IS REQUIRED
 FOR ALL EXTERIOR GLAZING.
 PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 6) PROVIDE DETAIL OF WINDOW AND DOOR
 BUCK CONNECTIONS CAPABLE OF RESISTING
 WINDLOADS.
  
 7) PROVIDE DETAIL INDICATING HOW JAMBS
 ARE TO BE "NARROWED-UP".
  
 8) PROVIDE DETAILS OF NEW EXTERIOR DOOR
 OPENING (ROOM 119) AND WINDOW OPENING
 REPLACING DOOR(ROOM 102).
  
 9) INDICATE LOCATION AND SIZE OF ATTIC
 ACCESS ON PLANS.
  
 10) PROVIDE DETAIL OF OPENING FOR DOUBLE
 DOORS BEING ADDED TO ROOM 102.
  
 11) INDICATE R VALUE FOR WALL AND
 CEILING INSULATION AT COVERED PORCH THAT
 IS BEING ENCLOSED.
  
 12)PROVIDE ENERGY CALCULATIONS AND
 MANUAL J CALCS. AS REQUIRED BY THE 97
 FLORIDA ENERGY CODE.
  
 13) PROVIDE CITY OF WPB DESIGN
 COMPLIANCE FORM FOR NEW EXTERIOR WALLS
 AT ENCLOSED PORCH.
  
 14) PROVIDE TOP AND BOTTOM CONNECTION
 DETAILS FOR NEW EXTERIOR METAL STUD
 WALLS. INDICATE BLOCKING FOR ATTACHMENT
 OF STORM PANELS.
  
 15) PROVIDE ONE BATH ROOM WITH A DOOR
 THAT HAS A 29 INCH CLEAR OPENING (2-8
 DOOR) PER 97 FLORIDA ACCESSIBILITY CODE.
  
 16) 97 SBC SECTION 2504.2 (ASTM C 926)
 REQUIRES EXTERIOR PORTLAND CEMENT
 PLASTER TO HAVE A NOMINAL THICKNESS OF
 7/8". PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-26 Cont ID  
Sent By dpalmer Date 2001-11-26 Time 07:04 Rev Time 0.00
Received By dpalmer Date 2001-11-26 Time 07:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-13 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 19:26 Rev Time 0.00
Received By dpalmer Date 2001-11-13 Time 19:26 Sent To  
Notes
2001-11-13 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT SERVICE HAS CHANGED
 FROM FIRST SET WHICH CONTAINED FUSED
 MAIN DISCONNECT. PLEASE NOTE THAT AIC
 RATINGS NEED TO BE SUBMITTED.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDCUTOR BETWEEN MAIN AND
 200A PANEL AND BETWEEN 200A PANEL AND
 100A PANEL. PLEASE CLARIFY. SIZE PER
 250-122
  
 3)NOTE: PLEASE NOTE THAT PLAN SHOW 3 3/0
 `S BEING INSTALLED IN A 1" CONDUIT?
 PLEASE NOTE THAT THIS DOES NOT MEET
 NEC FOR CONDUIT SIZING AND PIPE FILL.
 PLEASE CLARIFY 3/0`S FOR 100AMPS,??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 18:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 18:26 Sent To  
Notes
2001-06-04 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW INDICATION ON PANEL.
 PLANS SHOWS3-4/0`S AND 1-#2
 PLEASE NOTE THAT AN EQUIPMNET GROUND IS
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE NOTE THAT PLANS DO
 NOT SHOW WHAT SIZE THE SERVICE IS GOING
 TO BE?
 PLEASE NOTE LOAD CALCUALTIONS SHOWN
 EXCEED AND DO NOT CORRELATE W/NEC ART
 220.
 PLEASE INDICATE WIRE SIZES ON PANEL
 SCHEDULE TO CORRELATE W/ LOADS.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250-50. CWP/GROUND ROD.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-08-30 Cont ID  
Sent By lmartine Date 2001-08-30 Time 13:35 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-08-30 00:00:00PLANS APPROVED BY BY PATTY ON 7/31/01
 LM

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-07-30 Cont ID  
Sent By pkrauss Date 2001-07-30 Time 16:39 Rev Time 0.35
Received By pkrauss Date 2001-07-30 Time 16:39 Sent To  
Notes
2001-07-30 00:00:00******************PROVISO***************
  
  
 PLANS APPROVED - MECHANICAL PERMIT
 REQUIRED.
  
 MECHANICAL CONTRACTOR WAS NOT LISTED
 WITH FIRST SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-06-07 Cont ID  
Sent By pkrauss Date 2001-06-07 Time 10:18 Rev Time 0.25
Received By pkrauss Date 2001-06-07 Time 10:18 Sent To  
Notes
2001-06-07 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-31 Cont ID  
Sent By kstevens Date 2001-07-31 Time 11:29 Rev Time 0.50
Received By kstevens Date 2001-07-31 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-06 Cont ID  
Sent By kstevens Date 2001-06-06 Time 15:41 Rev Time 0.33
Received By kstevens Date 2001-06-06 Time 15:40 Sent To  
Notes
2001-06-06 00:00:00REVIEW NOTES:FAILED
  
 REFERENCE SPC-94
  
 SANITARY AND WATER RISER DIAGRAMS WILL
 BE REQUIRED FOR PLUMBING PLAN REVIEW PER
 SPC-94 104.2.1, 104.2.2 & 104.3.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-25 Cont ID  
Sent By sgraham Date 2001-06-25 Time 08:29 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***