Plan Review Details - Permit 01051470
Plan Review Stops For Permit 01051470
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-15 Cont ID  
Sent By jgomez Date 2004-11-15 Time 13:34 Rev Time 0.00
Received By jgomez Date 2004-11-15 Time 13:34 Sent To  
Notes
2004-11-15 00:00:00UPDATED GARAGE DOOR PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-03 Cont ID  
Sent By jgomez Date 2004-11-03 Time 09:47 Rev Time 0.00
Received By jgomez Date 2004-11-03 Time 13:33 Sent To PC
Notes
2004-11-03 00:00:00CHECKLIST:
 1-PRODUCT APPROVAL SUBMITTAL SUBMITTED
 FOR GARAGE DOOR WAS EXPIRED OVER A
 YEAR AGO(8-14-03). NEED CURRENT
 PRODUCT APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2004-11-30 Cont ID  
Sent By dpalmer Date 2004-11-30 Time 11:49 Rev Time 0.50
Received By dpalmer Date 2004-11-30 Time 11:49 Sent To  
Notes
2004-11-30 00:00:00REVISED RISER ONLY ON FULL SHEET.
 REDLINED 60A FEED FOR PANEL "D".

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 06:00 Rev Time 0.50
Received By dpalmer Date 2003-01-24 Time 06:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-07 Time 16:46 Rev Time 1.00
Received By dpalmer Date 2003-01-07 Time 16:46 Sent To  
Notes
2003-01-07 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE RISER DIAGRAM AND
 PANEL SCHEDULE NEED TO CORRELATE.
 PLEASE SHOW SIZES OF PANELS AND MATCH
 UP WITH RISER.("D").
  
 2)NOTE: PLEASE SEE PANEL SCHEDULES AND
 CORRELATE WIRE/PANELS/OCP. NOTE 200A
 BRKR ON #3AWG. PLEASE ALSO SEE SOME
 OTHER WIRE SIZES TOO SMALL FOR OCP.
  
 3)NOTE: PLEASE NOTE AHU #1 SHOWN W/ #8
 AWG. PLEASE NOTE WIRE IS SIZED PER KW
 OF UNIT AND NOT PER 65% DERATING.424-3
 SHOWN AS #6 ON PANEL SCHEDULE.
 4)NOTE: PLEASE NOTE PANEL "F" FEEDS "G"
 AND LOAD EXCEEDS 80% RATING OF BRKR?/
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE LOAD FOR RANGE AND
 CLARIFY LOAD AT 3KW?
  
 PLEASE GO OVER PLANS AND SUBMIT THE
 ABOVE INFOMRATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 6)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. 210-8-A-6

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-02-25 Cont ID  
Sent By dpalmer Date 2002-02-25 Time 10:29 Rev Time 0.00
Received By dpalmer Date 2002-02-25 Time 10:29 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-06 Cont ID  
Sent By dpalmer Date 2001-11-06 Time 21:27 Rev Time 0.00
Received By dpalmer Date 2001-11-06 Time 21:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 13:09 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 13:09 Sent To  
Notes
2001-09-18 00:00:00*********** REVISION REQUESTED *********
  
 PLEASE NOTE THAT NOT ALL ITEMS WERE
 CHANGED ON THE PLANS BY ARCHITECT OF
 RECORD. PLEASE NOTE MANY ITEMS WERE
 REDLINED ON PLANS. THESE WERE COMMENTS
 FROM FIRST TWO REVIEWS.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 NOW THAT TWO MAIN DISCONNECTS ARE BEING
 INSTALLED TO MEET GROUPING OF MAINS PER
 230-72. PLEASE SUBMIT AIC RATINGS FOR
 MAINS.
  
 2)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 NEEDS TO BE REVISED TO INCLUDE NEW MAIN
 DISCONNECTS AND WIRING.
  
 3)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNING CONDUCTORS PER 250-122 BETWEEN
 MAIN AND PANELS.
  
 4)NOTE: PLEASE NOTE THAT PANELS NOW ONLY
 NEED TO BE SHOWN AS "MLO".
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 7) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL.
 PER 250-50.
  
 8)NOTE: PLEASE NOTE MISSING OUTLETS AND
 LTS REQ`D FOR AHU`S AND OUTLETS FOR
 COND UNITS. 210-8/210-63/210-70/309.1
  
 PLEASE SUBMIT THE ABOVE AS A REVISION
 FOR REVIEW, BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. PLEASE ALSO
 NOTE THAT THERE WILL BE A FEE DUE FOR
 REVISION. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-08-29 Cont ID  
Sent By dpalmer Date 2001-08-29 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2001-08-29 Time 19:55 Sent To  
Notes
2001-08-29 00:00:00***************** UNSAT ****************
  
 PLEASE SEE THE FOLLOW NOTES, NOT ALL
 NOTES WERE ADRESSED FROM FIRST REVIEW.
  
 1)NOTE: PLEASE NOTE THAT ONE LINE DIA-
 -GRAM SHOWS TWO PANELS, ONE LH AND ONE
 RH. PLEASE CLARIFY LOCATIONS OF PANELS.
 MAINS NEED TO BE GROUPED PER 230-72.
 PLANS SHOW ONLY ONE PANEL IN GARAGE?
 WHERE IS THE OTHER PANEL?
  
 2)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO BE SHOWN AS
 GFI/GFI PROTECTED PER 210-8-A-6.
 PLEASE NOTE THAT OUTLET SPACING NEEDS TO
 MEET 210-52-C-1. WITHIN 2' OF COUNTER
 END AND EVRY 4' THER-AFTER.
  
 3)NOTE: PLEASE NOTE MISSING REQ`D LIGHT
 AND RECEPT FOR ALL AHU`S IN ATTIC SPACES
 PER 210-70 AND 210-63.
 PLEASE ALSO NOTE MISSING OUTLET FOR
 COND UNITS PER 309-1 OF THE MECH CODE.
  
 4)NOTE: PLEASE NOTE MISSING SOME OUTLETS
 PER 210-52 UPSTAIRS.
  
 5)NOTE: PLEASE NOTE THAT BLDG/FOOTER
 STEEL IS REQ`D PER 250-50 FOR GROUNDING
 ELECTRODE SYSTEM.
  
 PLEASE NOTE THAT SOME OF THE ITEMS ABOVE
 COULD HAVE BEEN REDLINED ON PLANS BUT
 MAIN SERVICE PANEL LOCATION ON PLANS
 MUST BE GROUPED, GROUNDING ELECTRODE
 TO BLDG. STEEL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-12 Cont ID  
Sent By dpalmer Date 2001-06-12 Time 21:22 Rev Time 0.00
Received By dpalmer Date 2001-06-12 Time 21:21 Sent To  
Notes
2001-06-12 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT ALL PLANS THAT
 ARE SIGNED AND SEALED ARE TO HAVE A
 TITLE BLOCK 61G15-23.002 .ALSO PLANS
 ARE TO BE DATED PER 481.221 AND 471.025
 WHEN SIGNED AND SEALED.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
  
 5)NOTE: PLEASE NOTE THAT GARAGE OUTLETS
 NEED TO BE SHOWN AS GFI/GFI PROTECTED
 PER 210-8
 ALSO OUTSIDE OUTLETS.
  
 6) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 MISSING OUTLET IN FRONT
  
 7)NOTE: PLEASE NOTE ALL A/C EQUIPMENT
 NOT SHOWN ON PLANS.
 MISSING DISCONNECTS PER 440-11
 PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 8) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 10)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW LOCATIONS PF PANELS? PLEASE NOTE
 GROUPING OF MAINS PER 230-72
  
 11)NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.
  
 12)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 FOR BOTH PANELS. THIS MAY CHANGE IN THE
 COARSE OF BLDG BUT IS REQ`D FOR
 PRELIMINARY CIRCUITING. 215-5
  
 13)NOTE: PLEASE NOTE THAT LOAD
 CALCULATIONS SHOW ALL AHU HEAT LOADS
 BEING DERATED AT 40%. PLEASE CLARIFY.
 ALL LOAD CALCSARE TO BE DONE IN ACCORD
 TO NEC AND ART 220. PLEASE NOTE THAT
 THE MAX DEDUCTION FOR DERATING AHU`S
 AND HEAT STRIP LOADS IS 65%. PLEASE SEE
 ART 220.
  
 14)NOTE: PLEASE NOTE THAT SUB PANEL FOR
 DOCK WAS NOT SHOWN ON RISER DIAGRAM??
 PLEASE SHOW ON LINE DIAGRAM. BEING SUB-
 -PANEL FROM PANEL ?? SHOW ON PANEL
 SCHEDULE.
 CONDUIT SIZES/WIRE SIZES ETC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 15:04 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 15:04 Sent To B
Notes
2004-11-12 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 10:38 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 10:38 Sent To B
Notes
2004-11-01 00:00:00TO JG DESK/SUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-10 Cont ID  
Sent By pkrauss Date 2002-03-07 Time 11:21 Rev Time 0.35
Received By pkrauss Date 2002-03-07 Time 11:06 Sent To  
Notes
2003-01-10 00:00:00MECHANICAL PERMIT 02080612

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-06 Cont ID  
Sent By hmoser Date 2001-06-06 Time 19:02 Rev Time 0.75
Received By hmoser Date 2001-06-06 Time 18:51 Sent To  
Notes
2001-06-06 00:00:00NO BATH EXHAUST ON MECHANICAL PLAN
 BATH EXHAUST ON LIGHTING PLAN

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-03-05 Cont ID  
Sent By kstevens Date 2002-03-05 Time 18:19 Rev Time 1.00
Received By kstevens Date 2002-03-05 Time 18:19 Sent To  
Notes
2002-03-05 00:00:00PASSED/PROVISO: SUBMIT SANT RISER DIAG.
 THAT REFLECTS FLOOR PLAN AND MEET SPC-94
 CODE REQUIREMENTS PRIOR TO FINAL INSP.
 REVISION.......

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2002-02-25 Time 10:29 Rev Time 0.50
Received By kstevens Date 2001-11-07 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-25 Cont ID  
Sent By jleech Date 2001-08-25 Time 07:28 Rev Time 0.50
Received By jleech Date 2001-08-25 Time 07:27 Sent To  
Notes
2001-08-25 00:00:00PROVISO;
 REVISED RISER DIAGRAM REQUIRED BEFORE
 PLUMBING FINAL. RISER DIAGRAM NOT TO
 CODE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-02 Cont ID  
Sent By kstevens Date 2001-06-02 Time 10:59 Rev Time 0.33
Received By kstevens Date 2001-06-02 Time 10:59 Sent To  
Notes
2001-06-02 00:00:00REVIEW NOTES:FAILED
  
 1) PAGE A-10 SEC. 15400 PLUMBING NOTES.
 PROVIDE MANUFACTURE SPECIFICATIONS FOR
 LEAD WRAP PIPE SOUND INFORMATION.
  
 2) SANITARY RISER DIAGRAM DOES NOT
 COMPLY WITH SPC-94. SUBMIT RISER DIAGRAM
 THAT MEETS CODE REQUIREMENTS AND
 REFLECTS FLOOR LAYOUT AS IT WILL BE IN-
 STALLED.
  
 REVIEW BY KEN STEVENS. ANY QUESTIONS
 CALL (561) 659-8096 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 8 Status F Date 2004-09-20 Cont ID  
Sent By jgomez Date 2004-09-20 Time 15:11 Rev Time 0.50
Received By jgomez Date 2004-09-20 Time 15:11 Sent To PC
Notes
2004-09-20 00:00:00CHECKLIST:
 1-NEED PRODUCT APPROVAL FOR SINGLE ENTRY
 DOOR WITH SIDELITES. PRODUCT APPROVAL
 SUBMITTED DOESN'T INCLUDE THIS ASSEMBLY
  
 2-PROVIDE INFORMATION AS REQUESTED ON
 PROVISO DATED 2-25-02. SEE ATTACHED
 COPY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop R ROOF PLAN REVIEW
Rev No 7 Status P Date 2002-05-24 Cont ID  
Sent By jgomez Date 2002-05-24 Time 14:27 Rev Time 0.25
Received By jgomez Date 2002-05-24 Time 14:24 Sent To  
Notes
2002-05-24 00:00:001-TRUSS ENGINEER NEEDS TO FOLLOW FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS RULES
 AND PROVIDE ORIGINAL SIGNATURE, DATE
 AND USE EMBOSSED SEAL ON ALL THE
 DOCUMENTS SUBMITTED FOR PUBLIC RECORDS
 AS REQUIRED BY CHAPTER 471 FL STATUTES

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status F Date 2002-05-20 Cont ID  
Sent By jgomez Date 2002-05-20 Time 15:06 Rev Time 0.50
Received By jgomez Date 2002-05-20 Time 15:06 Sent To  
Notes
2002-05-20 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-TRUSS ENGINEER TO SIGN, SEAL AND DATE
 TRUSS PLAN AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
 2-TRUSS ENGINEER TO PROVIDE ORIGINAL
 SIGNATURE, SEAL AND DATE ON ALL
 ENGINEERED DRAWINGS & MICROLLAM BEAMS
 AS REQUIRED BY CHAPTER 471 FL STATUTES
 3-MICROLLAM BEAMS ENGINEERED BEAMS ARE
 NOT LEGIBLE. ALSO, WHAT'S THE DESIGN
 CRITERIA USED. ASCE 7-98 140MPH AS THE
 ENGINEERED TRUSSES?
 4-ENGINEER OF RECORD TO REVISE TRUSS
 ANCHOR SCHEDULE TO RESIST THE UPLIFT
 LOADS AS CALCULATED ON THE ENGINEERED
 TRUSSES. SEE ENGINEERED TRUSSES.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2002-02-25 Cont ID  
Sent By jgomez Date 2002-02-25 Time 17:08 Rev Time 2.00
Received By jgomez Date 2002-02-25 Time 17:08 Sent To  
Notes
2002-02-25 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A5. PROVIDE INSPECTOR WITH
 ELEVATION CERTIFICATE.
 2-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS ASSEMBLY.
 B)GARAGE DOORS.
  
 3-REMOVE KITCHEN BY THE PLAY ROOM AREA
 AS REQUESTED BY ZONING.
 4-MASONRY FENCES TO BE DONE UNDER A
 SEPARATE PERMIT.
 5-STORM PANEL SHUTTERS FOR ENTRY DOOR.
 A)CLEARLY INDICATE ON DRAWINGS ALL THE
 COMPONENTS THAT ARE GOING TO BE USED
 FOR THIS APPLICATION. SEE PAGE -2-.
 B)PROVIDE COMPLETE INSTALLATION
 SCHEDULE AND KEY PLAN.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2001-11-09 Cont ID  
Sent By jgomez Date 2001-11-09 Time 16:42 Rev Time 1.00
Received By jgomez Date 2001-11-09 Time 16:42 Sent To  
Notes
2001-11-09 00:00:00PRODUCT APPROVAL REVIEW:
  
 1-PRODUCT APPROVALS SUBMITTED ARE OK
 EXCEPT FOR MAIN ENTRY DOOR ASSEMBLY.
 NEED TO PROVIDE PRODUCT APPROVAL FOR
 COMPLETE ASSEMBLY AS SHOWN ON THE
 ARCHITECTURAL PLANS AND ELEVATIONS.
 PRODUCT APPROVALS SUBMITTED FOR WOOD
 FIXED WINDOW AND WOOD FRENCH DOORS ARE
 FOR SINGLE UNITS ONLY AS SHOWN ON
 APPROVED PLANS. SEE LIMITATIONS ON
 SHEET #2 OF PRODUCT APPROVALS.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-09-15 Cont ID  
Sent By jgomez Date 2001-09-15 Time 16:30 Rev Time 3.00
Received By jgomez Date 2001-09-15 Time 16:30 Sent To  
Notes
2001-09-15 00:00:00APPROVED WITH PROVISO:
  
 1-ENTRY DOORS WITH SIDELITES, FRENCH
 DOORS WITH SIDELITES AND BAY WINDOWS
 CALL FOR 2X STRUCTURAL MULLIONS.
 PROVIDE COMPLETE SPECIFICATIONS AND
 CONNECTION DETAILS SHOWING THE SUPPORT
 TO STRUCTURE AND TO WINDOWS/DOORS.
 -ALSO, CLARIFY WHAT ASSEMBLIES ARE
 GOING TO USE THE STRUCTURAL MULLIONS
 SUBMITTED IN THE PRODUCT APPROVAL.
 2-ENGINEER OF RECORD TO REVIEW ALL
 WINDOW, DOORS, MULLIONS PRODUCT
 APPROVALS TO ASSURE THAT THEY MEET THE
 DESIGN PRESSURES HE CALCULATED. (USE
 SHOP DRAWINGS REVIEW STAMP).
 3-PROVIDE PRODUCT APPROVAL FOR:
 -ENTRY DOORS WITH SIDELITES ASSEMBLY.
 -INSWING FRENCH DOORS. SEE PLANS.
 -EXTERIOR SWING DOORS. SEE PLANS.
 -UL LISTING FOR BBQ.
 -PROVIDE UL LISTING FOR FIREPLACE AND
 SUBMITT TWO COPIES.
 4-BORING TEST REPORT SHALL BE DONE
 USING SECTION 1804.2.7 OF CITY
 AMENDMENTS TO SBC 1997, NOT SOUTH
 FLORIDA BUILDING CODE.
 -PROVIDE TWO COPIES.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-09-10 Cont ID  
Sent By jgomez Date 2001-09-10 Time 19:46 Rev Time 4.00
Received By jgomez Date 2001-09-11 Time 14:01 Sent To  
Notes
2001-09-10 00:00:00CHECKLIST:
 1-ENTRY DOOR SIZE DOESN'T PROVIDE THE
 MINIMUM CLEAR OPENING (AT LEAST ONE
 LEAF) OF 32" AS REQUIRED BY TABLE
 1004 SBC 1997.
 2-COMPLETE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM.
 3-PROVIDE SMOKE DETECTORS AT EACH STORY
 AS REQUIRED BY SEC. 905.2 SBC 1997.
 4-ENTRY DOOR ASSEMBLY, FRENCH DOORS WITH
 SIDELITES AND BAY WINDOWS CALL FOR
 2XSTRUCTURAL MULLIONS, BUT THERE IS
 NOT SPECIFICATIONS FOR FASTENERS.
 REMEMBER THAT THIS ASSEMBLIES WILL
 HAVE MISSILE IMPACT GLAZING.
 5-ENGINEER OF RECORD TO REVIEW ALL
 MISSILE IMPACT PRODUCT APPROVALS TO
 VERIFY THAT THEY WILL MEET THE DESIGN
 PRESSURES CALCULATED ON PLANS.
 6-PROVIDE PRODUCT APPROVALS FOR:
 -INSWING FRENCH DOORS AS SHOWN ON PLANS
 -EXTERIOR SWING DOORS. EG @ LAUNDRY,ETC
 -UL LISTING FOR BBQ.
 7-OWES ADDITIONAL FEES OF $1234.68 FOR
 LOW VALUATION AND RADON FEES. SEE
 ATTACHED RECEIPT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-07-17 Cont ID  
Sent By jgomez Date 2001-07-17 Time 10:33 Rev Time 6.00
Received By jgomez Date 2001-07-17 Time 10:32 Sent To  
Notes
2001-07-17 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-NEED TO FILE NOTICE OF COMMENCEMENT.
 3-PROVIDE SIGNED, SEALED AND DATED
 SURVEY WITH NEW BUILDING LAYOUT AND
 PROPOSED FINISH FLOOR ELEVATIONS.
 4-COMPLETE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM ATTACHED
 5-SPECIFY DESIGN PRESSURES CALCULATED AT
 ALL EXTERIOR OPENINGS. SEC 1606 SBC/97
 6-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR
 OPENING (AT LEAST ON ONE LEAF) AS
 REQUIRED BY TABLE 1004 SBC 1997.
 7-PROVIDE COMPLETE AREA TABULATIONS. EG:
 A/C AREAS, PORCHES, GARAGE, BALCONIES.
 8-WINDOWS SPECIFIED DON'T PROVIDE THE
 MIN CLEAR OPENINGS REQUIRED FOR EGRESS
 SEC. 1005.4 SBC 1997. REVISE SIZE OF
 WINDOWS AT GUEST BEDRM AND 2ND FLOOR
 BEDRMS. ALSO, OFFICE AT 2ND FLOOR MAY
 BE CONSIDERED AS A BEDRM, THEREFORE,
 WINDOWS SHALL COMPLY W/ THIS SEC. TOO.
 9-PROVIDE ATTIC ACCESS AT GARAGE, LOGGIA
 & MASTER BEDRM BALCONY. SEC 2309.6 SBC
 10-PROVIDE SMOKE DETECTORS AT EACH STORY
 AS REQUIRED BY SEC. 905.2 SBC 1997.
 11-FLAT ROOF AND PARAPETS:
 A)MIN SLOPE 1/4"/FT. SEC 1503.1.2.3 SBC
 B)PROVIDE DRAINAGE FOR MASTER BEDROOM
 BALCONIES AND EMERGENCY SCUPPERS AS
 REQUIRED BY SEC. 1517.6.4 SBC 1997.
 12-SPECIFY ATTIC VENTILATION AS REQUIRED
 BY SEC 2309.7 SBC 1997.
 13-ARCHITECT TO DATE DRAWINGS AT TIME OF
 SEALING. CHAPTER 481 FLORIDA STATUTES
 14-REVISE DESIGN ASSUMPTION NOTES ON
 SHEET S-1.1. ASCE 7-95 FOR 145MPH OR
 SBC FOR 110 MPH.
 15-OWNER TO SIGN & DATE ENERGY CALCS.
 16-SOIL TEST REPORT TO HAVE ORIGINAL
 SIGNATURE, DATE AND EMBOSSED SEAL AS
 REQUIRED BY CHAPTER 471 FL. STATUTES.
 17-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOOR WITH SIDELITES AND TRANSOM
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 B)FIXED WINDOWS(NEED APPROVED DWGS)
 C)FRENCH DOORS WITH SIDELITES SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 D)SWING DOORS. EG: @ LAUNDRY AND BATH.
 E)UL LISTING AND SPECS FOR FIREPLACE.
 F)UL LISTING AND SPECS FOR BBQ.
 G)ROOF TILE.
 H)FLAT ROOF SYSTEM.
 I)WINDOW MULLIONS.
  
 18-SEE PLANS FOR ADDITIONAL MINOR
 COMMENTS AND PLEASE RETURN REVIEWED
 SET IN ORDER TO EXPEDITE THE REVIEW
 PROCESS.

Review Stop Z ZONING
Rev No 3 Status P Date 2002-03-25 Cont ID  
Sent By sgraham Date 2002-03-25 Time 11:33 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2002-02-25 Cont ID  
Sent By sgraham Date 2002-02-25 Time 16:01 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-02-25 00:00:00NO KITCHEN ALLOWED IN THE PLAYROOM
 PROPERTY ZONED SF7

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-01 Cont ID  
Sent By sgraham Date 2001-06-01 Time 13:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***