Plan Review Details - Permit 01051432
| Plan Review Stops For Permit 01051432 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-06-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-13 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-13 |
Time |
18:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-06 |
Time |
22:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-06 |
Time |
22:28 |
Sent To |
|
|
| Notes |
| 2001-06-06 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | KITCHEN PENINSULAR PER 210-52-C-3 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | AIC RATING WAS SUBMITTED FOR PANLES, | | | BUT NOT FOR MAINS. PER 110-9 | | | | | | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | MISSING IN FAMILY ROOM. | | | | | | 4) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | FRONT RECEPT | | | | | | 5) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | MISSING OUTSIDE AND IN ATTIC IN GARAGE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-26 |
Time |
13:02 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-10-26 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2001-10-26 00:00:00 | AS BUILTS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-06-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2001-06-02 |
Time |
14:19 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2001-06-02 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-06-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-02 |
Time |
07:41 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-06-02 |
Time |
07:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2001-06-13 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2001-06-13 |
Time |
21:56 |
Rev Time |
4.00 |
| Received By |
lhatten |
Date |
2001-06-11 |
Time |
21:55 |
Sent To |
|
|
| Notes |
| 2001-06-13 00:00:00 | REVIEWED 06/11/2001 | | | STAMPED,CALC. FEES & PRINT CARDS | | | 06/13/2001 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-06-01 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-06-01 |
Time |
13:22 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|