Plan Review Details - Permit 01051389
Plan Review Stops For Permit 01051389
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-20 Cont ID  
Sent By dpalmer Date 2001-07-20 Time 07:38 Rev Time 0.00
Received By dpalmer Date 2001-07-20 Time 07:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 19:13 Sent To  
Notes
2001-06-04 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS THAT WERE SUBMITTED NEED TO
 CORRELATE W/ NEC 220.
 PLEASE NOTE THAT A/C LOADS ARE NOT DED-
 -UCTED WITH LIGHTING LOADS.
 PLEASE GO OVER LOAD CALCUALTIONS AND
 RE-DO. 215-5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3)NOTE: PLEASE NOTE THAT 1- 1/0 WIRE IS
 GOING TO THE 200A PANEL? PLEASE NOTE THA
 T 1/0 IS NOT RATED FOR 200A. PLEASE
 VERIFY
  
 4)NOTE: PLEASE NOTE MISSING OUTLET PER
 210-52
  
  
 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. NEW ADDITION BLDG STEEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-14 Cont ID  
Sent By hmoser Date 2001-07-14 Time 12:43 Rev Time 0.50
Received By hmoser Date 2001-07-14 Time 12:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By pkrauss Date 2001-06-07 Time 10:39 Rev Time 0.40
Received By pkrauss Date 2001-06-07 Time 10:26 Sent To  
Notes
2001-06-07 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 SIZE OF ALL DUCT AND SIZE OF GRILLS.
  
 PROVIDE INFORMATION ON EXISTING AIR
 DISTRIBUTION FOR AHU-1.PLAN INDICATES
 AN ADDITIONAL 580 CFM, WILL THE
 EXISTING UNIT BE ABLE TO PROVIDE THIS?
  
 PLEASE PROVIDE SIZE OF BOTH EXHAUST
 VENTS (KITCHEN & BATHROOMS).
  
 LOCATION OF CONDENSER UNITS NEED TO BE
 REFLECTED ON PLAN.
  
 PLEASE INDICATE SIZE AND LOCATION OF
 CONDENSATE.
  
  
 NOTE:PRIOR TO CONNECTING TO ANY
 EXISTING DUCTWORK, CALL FOR AN
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-18 Cont ID  
Sent By jleech Date 2001-07-18 Time 17:31 Rev Time 0.33
Received By jleech Date 2001-07-18 Time 17:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-06 Cont ID  
Sent By kstevens Date 2001-06-06 Time 15:02 Rev Time 0.33
Received By kstevens Date 2001-06-06 Time 15:02 Sent To  
Notes
2001-06-06 00:00:00REVIEW NOTES:FAILED
  
 ...PAGE P-1...
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. PLEASE SUBMIT A
 RISER DIAGRAM THAT MEETS SPC-94 CODE
 REQUIREMENTS.
  
 2) AIR CHAMBERS TO COMPLY WITH SPC-94
 607.8.2 AND 607.8.3
  
 3) 3" PIPE NOT ALLOWED IN 8" BLOCK WALL
 PER SBC-97 1907.3.5 (1).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-07-24 Cont ID  
Sent By jgomez Date 2001-07-24 Time 13:22 Rev Time 3.00
Received By jgomez Date 2001-07-24 Time 13:22 Sent To  
Notes
2001-07-24 00:00:00APPROVED WITH PROVISO:
 1-WIDTH OF STAIRS SHALL NOT DECREASE IN
 THE DIRECTION OF EXIT TRAVEL. REVISE
 AS REQUIRED. SEC 1007.6.2 SBC 1997.
 2-PROVIDE ROOF VENTILATION FOR FLAT
 ROOF. SEC 2309.7 SBC 1997.
 3-SOIL TEST REPORT SHOWS ROOTS AND
 ORGANIC MATERIALS. REMOVE PRIOR TO
 CONSTRUCTION. SEC 1804

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-06-29 Cont ID  
Sent By jgomez Date 2001-06-29 Time 17:06 Rev Time 4.50
Received By jgomez Date 2001-06-29 Time 17:06 Sent To  
Notes
2001-06-29 00:00:00CHECKLIST:
 1-NEED TO FILE NOTICE OF COMMENCEMENT.
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 3-UPDATE GENERAL NOTES. SEE COMMENTS.
 4-ROOF DRAINAGE:
 A)FLAT ROOF TO HAVE 1/4" PER FT SLOPE,
 NOT 1/8". SEC. 1503.1.2.3 SBC 1997.
 B)SPECIFY SIZES OF GUTTERS, SCUPPERS&
 RAIN LEADERS. SEC 1517.6. SBC 1997.
 C)SPECIFY OVERFLOW SCUPPERS. SECTION
 1517.6.4.3 SBC 1997.
 5-REVISE CALCULATED AREAS ON SHEET A-1.
 SEE DEFINITION FOR BUILDING AREA.
 -SPECIFY HOW MUCH A/C AREA AND NON A/C
 AREAS LIKE PORCHES.
 6-SPECIFY SAFETY GLASS WHERE REQUIRED BY
 SEC 2405.2 SBC 1997. SEE PLANS.
 7-BEDROOM EGRESS WINDOWS DON'T COMPLY W/
 SEC 1005.4 SBC 1997. WINDOWS SPECIFIED
 HAVE A MULLION IN THE MIDDLE.
 8-SPECIFY DESIGN PRESSURES CALCULATED AT
 ALL EXTERIOR OPENINGS AS REQUIRED BY
 SECTION 1606 SBC 1997.
 9-"WIDTH OF STAIRS SHALL NOT DECREASE IN
 THE DIRECTION OF EXIT TRAVEL". SECTION
 1007.6.2 SBC 1997. REVISE AS REQUIRED.
 10-PROVIDE ATTIC ACCESS AT NEW ROOF IF
 CLEAR ATTIC SPACE IS MORE THAN 24".
 PROVIDE CROSS SECTION SHOWING PROFILE
 OF ROOF TRUSSES TO DETERMINE HEIGHT.
 SECTION 2309.6 SBC 1997.
 11-ROOF VENTILATION:
 A)SPECIFY VENTILATION FOR FLAT ROOF.
 B)CLARIFY HOW VENTILATION IS ACHIEVED
 THRU THE DRIP EDGE. PROVIDE DETAIL &
 SPECS. SECTION 2309.7 SBC 1997.
 12-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. THE
 MEAN ROOF HEIGHT & VELOCITY PRESSURE
 DON'T MATCH. SEE TABLE 1606.2A SBC/97
 -ARCHITECT TO WRITE LICENSE # ON FORM
 AS REQUIRED BY CHAPTER 481 FL. ST.
 13-SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION AT SECOND FLOOR FRAMING PLAN.
 SEC 2305.2 SBC 1997.
 14-OWNER TO SIGN & DATE ENERGY CALCS.
 15-REVISE WALL SECTIONS AS REQUIRED. SEE
 RECOMMENDATIONS ON SOIL TEST REPORT
 FOR SLAB ON GRADE CONSTRUCTION. ALSO
 SEE SHEET A-4 FOR ADDITIONAL COMMENTS
 16-SOIL TEST REPORT SHOWS ROOTS AND
 ORGANIC MATERIALS. REMOVE THEM BEFORE
 CONSTRUCTION. SEC 1804.1.8 SBC 1997.
 17-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS (MISSING COPIES OF THE
 APPROVED DRAWINGS).
 NOTE: VERIFY IF APPROVED DRAWINGS
 COVER THE DOOR SHOWN ON ARCHITECT'S
 EXTERIOR ELEVATION.
 B)ROOF HATCH.
 18-SPECIFY THE UPLIFT LOADS CALCULATED
 FOR THE NEW STRUCTURE. SEC 1606 SBC/97
 19-SEE PLANS FOR ADDITIONAL COMMENTS.
 AND, PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS/UPDATES ARE DONE TO THE
 ORIGINAL DRAWINGS IN ORDER TO EXPEDITE
 THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-31 Cont ID  
Sent By sgraham Date 2001-05-31 Time 11:03 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***