| 2001-06-23 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | SBC 104.2.2 |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SHEET C1 INCORRECTLY SITES 1999 SBC |
| | AND 1999 FLORIDA ENERGY CODE. THE CITY |
| | OF WPB CURRENTLY USES THE 1997 SBC AND |
| | THE 1997 FLORIDA ENERGY CODE |
| | REQUIREMENTS. PLEASE CORRECT ON YOUR |
| | MASTER. |
| | |
| | 4)RIGHT ELEVATION EXCEEDS THE |
| | PERCENTAGEOF WALL OPENINGS PERMITTED BY |
| | TABLE 600 OF THE 97 SBC. TWENTY PERCENT |
| | OF WALL |
| | AREA IS ALLOWED AS WALL OPENINGS FOR A |
| | HORIZONTAL SEPARATION OF EIGHT FEET. |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | 5) PROVIDE ATTIC ACCESS PER 97SBC 2309.6 |
| | |
| | 6) SHEET A-2 IS NOT SIGNED BY DESIGN |
| | PROFESSIONAL IN ONE SET OF PLANS. |
| | |
| | 7) MEAN ROOF HEIGHT (DISTANCE FROM |
| | FINISH GRADE TO AVERAGE HEIGHT OF |
| | TALLEST ROOF) APPEARS TO BE 18 FT., NOT |
| | 15 FT. PLEASE REVIEW AND CORRECT. DESIGN |
| | CERTIFICATION FORM WILL HAVE TO BE |
| | CORRECTED,AS BASIC VELOCITY PRESSURE |
| | WILL CHANGE. |
| | |
| | 8) PLEASE REVIEW DETAIL 5/A5 CONNECTION |
| | FOR GIRDER TRUSS AT REAR COVERED PATIO. |
| | IT DOES NOT CORRESPOND TO PLAN. |
| | |
| | 9) PLEASE INDICATE CONNECTORS FOR TRUSS |
| | TO GIRDER ATTACHMENT AT LIVING ROOM. |
| | SEE SHEET A-6. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |