Plan Review Details - Permit 01051385
Plan Review Stops For Permit 01051385
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-07-07 Cont ID  
Sent By rmcdouga Date 2001-07-07 Time 10:29 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-30 Cont ID  
Sent By rmcdouga Date 2001-06-30 Time 10:05 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-30 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SHEET C1 SITES 1999 SBC AND 1999 FL
 ENERGY CODE, THE CITY OF WPB HAS ADOPTED
 THE 1997 SBC AND THE 1997 FLORIDA ENERGY
 CODE. PLEASE CORRECT.
  
 4) ONE SET OF THE ENERGY CALCULATION
 FORMS SUBMITTED WAS NOT SIGNED BY THE
 OWNER/AGENT. PLEASE HAVE FORM SIGNED.
  
 5) INDICATE SIZE AND LOCATION OF ATTIC
 ACCESS ON PLANS. 97 SBC 2309.6
  
 6) IN ONE SET OF PLANS, SHEET A-2 IS
 SEALED BUT NOT SIGNED AND DATED BY THE
 DESIGN PROFESSIONAL.
  
 7) THE MEAN ROOF HEIGHT OF THE STRUCTURE
 IS 18 FT. NOT 15 FT. PLEASE INDICATE
 MEAN ROOF HEIGHT (VERTICLE DISTANCE FROM
 GRADE TO A POINT AT THE AVERAGE HEIGHT
 OF THE HIGHEST ROOF HAVING A PITCH) ON
 THE PLANS AND CORRECT THE INFORMATION ON
 THE DESIGN COMPLIANCE FORM TO REFLECT AN
 18 FT. MEAN ROOF HEIGHT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-23 Cont ID  
Sent By rmcdouga Date 2001-06-23 Time 15:34 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-23 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
 SBC 104.2.2
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SHEET C1 INCORRECTLY SITES 1999 SBC
 AND 1999 FLORIDA ENERGY CODE. THE CITY
 OF WPB CURRENTLY USES THE 1997 SBC AND
 THE 1997 FLORIDA ENERGY CODE
 REQUIREMENTS. PLEASE CORRECT ON YOUR
 MASTER.
  
 4)RIGHT ELEVATION EXCEEDS THE
 PERCENTAGEOF WALL OPENINGS PERMITTED BY
 TABLE 600 OF THE 97 SBC. TWENTY PERCENT
 OF WALL
 AREA IS ALLOWED AS WALL OPENINGS FOR A
 HORIZONTAL SEPARATION OF EIGHT FEET.
 PLEASE REVIEW AND CORRECT.
  
 5) PROVIDE ATTIC ACCESS PER 97SBC 2309.6
  
 6) SHEET A-2 IS NOT SIGNED BY DESIGN
 PROFESSIONAL IN ONE SET OF PLANS.
  
 7) MEAN ROOF HEIGHT (DISTANCE FROM
 FINISH GRADE TO AVERAGE HEIGHT OF
 TALLEST ROOF) APPEARS TO BE 18 FT., NOT
 15 FT. PLEASE REVIEW AND CORRECT. DESIGN
 CERTIFICATION FORM WILL HAVE TO BE
 CORRECTED,AS BASIC VELOCITY PRESSURE
 WILL CHANGE.
  
 8) PLEASE REVIEW DETAIL 5/A5 CONNECTION
 FOR GIRDER TRUSS AT REAR COVERED PATIO.
 IT DOES NOT CORRESPOND TO PLAN.
  
 9) PLEASE INDICATE CONNECTORS FOR TRUSS
 TO GIRDER ATTACHMENT AT LIVING ROOM.
 SEE SHEET A-6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-02 Cont ID  
Sent By dpalmer Date 2001-07-02 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2001-07-02 Time 17:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-06 Cont ID  
Sent By dpalmer Date 2001-06-06 Time 22:43 Rev Time 0.00
Received By dpalmer Date 2001-06-06 Time 22:43 Sent To  
Notes
2001-06-06 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE MISSING GFI OUTLET
 FOR GARAGE. PER 210-52G
  
 2)NOTE: PLEASE NOTE MISSING OUTLET FOR
 MASTER HALL PER 210-52H
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
 IN GARAGE /ALSO MISSING REQ`D LIGHT.
  
 4) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 NUMEROUS LOCATIONS SHOW "J" FOR JUNCTION
 BOX WHERE LIGHT FIXTURES ARE REQ`D??
  
 5) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 FRONT RECEPT.
  
 6) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATING IS SHOWN FOR PANEL BUT NOT
 FOR MAIN DISCONNECT. PER 110-9/215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-06 Cont ID  
Sent By hmoser Date 2001-06-06 Time 17:49 Rev Time 0.33
Received By hmoser Date 2001-06-06 Time 17:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-30 Cont ID  
Sent By jleech Date 2001-08-30 Time 17:30 Rev Time 0.33
Received By jleech Date 2001-08-30 Time 17:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-02 Cont ID  
Sent By kstevens Date 2001-06-02 Time 09:18 Rev Time 0.33
Received By kstevens Date 2001-06-02 Time 09:18 Sent To  
Notes
2001-06-02 00:00:00REVIEW NOTES:PASSED
  
 ...PROVISO...
  
 SUBMIT SANITARY RISER DIAGRAM WITH
 CORRECTIONS SHOWN ON PLANS.
  
 REVIEW BY KEN STEVENS

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-01 Cont ID  
Sent By sgraham Date 2001-06-01 Time 13:12 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***