| 2001-07-09 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 4) PROVIDE AT LEAST ONE BATHROOM WITH A |
| | DOOR THAT HAS A 29 INCH CLEAR OPENING, |
| | AS REQUIRED BY THE 1997 FLORIDA |
| | ACCESSIBILITY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 5) PROVIDE EMERGENCY EGRESS WINDOW IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGHT OF 24INCHES,NET CLEAR |
| | OPENING WIDTH OF 20 INCHES AND NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT |
| | SHALL NOT BE MORE THAN 44 INCHES ABOVE |
| | THE FLOOR. 1997 SBC 1005.4 |
| | |
| | 6)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - EXTERIOR WINDOWS |
| | - EXTERIOR DOORS |
| | |
| | 7) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | BEING USED FOR ALL NEW GLAZED OPENINGS. |
| | NOTE: PROVIDE BACKING AT EXTERIOR GLAZED |
| | OPENINGS FOR ATTACHMENT OF STORM PANELS. |
| | IF MORE THAN 50% OF THE GLAZED AREA OF |
| | THE STRUCTURE IS REPLACED, STORM PANELS |
| | WILL BE REQUIRED ON ALL EXISTING GLAZED |
| | OPENINGS. |
| | |
| | 8) PROVIDE DETAIL OF EXISTING FOUNDATION |
| | INDICATING REINFORCEMENT OF FOOTING AND |
| | THICKNESS OF EXISTING SLAB AND OVERPOUR. |
| | THE BOTTOM OF THE FOOTING IS REQUIRED TO |
| | BE A MINIMUM OF 12" BELOW FINISHED GRADE |
| | PER 97 SBC 1804.1.3. THE BUILDING FINISH |
| | FLOOR ELEVATION MUST BE A MINIMUM OF 4" |
| | ABOVE FINISH GRADE PER 1804.1.9 OF THE |
| | CITY AMENDMENTS TO SBC. |
| | |
| | 9) WHERE WIRE LATH AND STUCCO FINISH IS |
| | APPLIED OVER THE EXTERIOR OF WOOD FRAME |
| | CONSTRUCTION AN APPROVED STUCCO STOP |
| | PLACED NOT LESS THAN 6" ABOVE FINISHED |
| | GRADE SHALL BE USED TO TERMINATE THE |
| | STUCCO AT THE BASE OF THE WALL. 2304.2.5 |
| | OF THE CITY AMENDMENTS TO 97 SBC. |
| | |
| | 10) SAFETY GLASS IS REQUIRED IN WINDOW |
| | AT TUB IF LESS THAN 60" ABOVE THE DRAIN |
| | INLET. |
| | |
| | 11) INDICATE ON PLANS THE CONNECTORS |
| | THAT WILL BE USED TO ANCHOR THE STUDS TO |
| | THE BOTTOM PLATES. |
| | |
| | 12) INDICATE CONNECTORS USED TO ANCHOR |
| | 2X8 LEDGER CARRYING ROOF JOISTS TO WALL |
| | STUDS. |
| | |
| | 13) SPECIFY ANCHOR BOLT TYPE, LENGTH AND |
| | EMBEDMENT TO BE USED WITH SIMPSON MTT28B |
| | TO ANCHOR POSTS. SEE WALL SECTION 5 ON |
| | A201. |
| | |
| | 14) SPECIFY CONNECTORS FOR 4X4 POST TO |
| | BEAM CONNECTION, BEAM TO FRAMING ABOVE, |
| | ETC. FOR THE INTERIOR BEARING WALLS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |