Plan Review Details - Permit 01051205
Plan Review Stops For Permit 01051205
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 15:08 Sent To  
Notes
2001-08-02 00:00:00SEPARATE PERMIT AND PLANS TO BE SUBMITTE
 D AT LATER DATE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-24 Cont ID  
Sent By dpalmer Date 2001-06-24 Time 13:08 Rev Time 0.00
Received By dpalmer Date 2001-06-24 Time 13:08 Sent To  
Notes
2001-06-24 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT ALL CHANGES
 THAT ARE MADE TO SIGNED AND SEALED
 PLANS ARE TO PRINTED AND DONE BY THE
 ARCH/ENGINEER OF RECORD. PLEASE SEE.F.S.
 AND F.A.C 471.025 AND 481.221.
  
 2)NOTE: PLEASE NOTE THAT OTHER PLANS
 WERE SUBMITTED FOR AN ELECTRICAL
 RE-WIREUNDER OTHER PERMIT #. IS THIS
 FOR NEW
 WORK? OR FOR A REVISION?
 PLEASE CLARIFY.
 IF WORK IS BEING DONE UNDER OTHER
 PERMITPLEASE REMOVE ELECTRICAL FROM
 THESE SETS
  
  
 PLEASE SUBMIT CLARIFICATION FOR THE
 ABOVE. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-07-07 Cont ID  
Sent By jleech Date 2001-07-07 Time 08:46 Rev Time 0.50
Received By jleech Date 2001-07-07 Time 08:46 Sent To  
Notes
2001-07-07 00:00:00NOT ENOUGH INFORMATION;
  
 1.EQUIPMENT SPECIFCATIONS FOR UNITS 2
 AND 3 ARE REQUIRED.
  
 2.ALL DROPS SHALL SHOW CFM'S.
  
 3.A/C CONTRACTOR TO SUBMIT PLAN WITH A/C
 APPLICATION.
  
 A/C PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-20 Cont ID  
Sent By kstevens Date 2001-06-20 Time 12:12 Rev Time 0.33
Received By kstevens Date 2001-06-20 Time 12:11 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-08-14 Cont ID  
Sent By rmcdouga Date 2001-08-14 Time 11:10 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-08-14 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR DOORS
  
 2) PROVIDE PRODUCT APPROVALS, KEY PLAN
 AND INSTALLATION SCHEDULE FOR STORM
 PANELS (2 COPIES) UNDER A SEPARATE
 PERMIT.
  
 3) SEPARATE PERMITS WILL BE REQUIRED FOR
 ROOFING, MECHANICAL AND ELECTRIC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-07-09 Cont ID  
Sent By rmcdouga Date 2001-07-09 Time 08:32 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-07-09 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 4) PROVIDE AT LEAST ONE BATHROOM WITH A
 DOOR THAT HAS A 29 INCH CLEAR OPENING,
 AS REQUIRED BY THE 1997 FLORIDA
 ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION.
  
 5) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 1997 SBC 1005.4
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR WINDOWS
 - EXTERIOR DOORS
  
 7) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 BEING USED FOR ALL NEW GLAZED OPENINGS.
 NOTE: PROVIDE BACKING AT EXTERIOR GLAZED
 OPENINGS FOR ATTACHMENT OF STORM PANELS.
 IF MORE THAN 50% OF THE GLAZED AREA OF
 THE STRUCTURE IS REPLACED, STORM PANELS
 WILL BE REQUIRED ON ALL EXISTING GLAZED
 OPENINGS.
  
 8) PROVIDE DETAIL OF EXISTING FOUNDATION
 INDICATING REINFORCEMENT OF FOOTING AND
 THICKNESS OF EXISTING SLAB AND OVERPOUR.
 THE BOTTOM OF THE FOOTING IS REQUIRED TO
 BE A MINIMUM OF 12" BELOW FINISHED GRADE
 PER 97 SBC 1804.1.3. THE BUILDING FINISH
 FLOOR ELEVATION MUST BE A MINIMUM OF 4"
 ABOVE FINISH GRADE PER 1804.1.9 OF THE
 CITY AMENDMENTS TO SBC.
  
 9) WHERE WIRE LATH AND STUCCO FINISH IS
 APPLIED OVER THE EXTERIOR OF WOOD FRAME
 CONSTRUCTION AN APPROVED STUCCO STOP
 PLACED NOT LESS THAN 6" ABOVE FINISHED
 GRADE SHALL BE USED TO TERMINATE THE
 STUCCO AT THE BASE OF THE WALL. 2304.2.5
 OF THE CITY AMENDMENTS TO 97 SBC.
  
 10) SAFETY GLASS IS REQUIRED IN WINDOW
 AT TUB IF LESS THAN 60" ABOVE THE DRAIN
 INLET.
  
 11) INDICATE ON PLANS THE CONNECTORS
 THAT WILL BE USED TO ANCHOR THE STUDS TO
 THE BOTTOM PLATES.
  
 12) INDICATE CONNECTORS USED TO ANCHOR
 2X8 LEDGER CARRYING ROOF JOISTS TO WALL
 STUDS.
  
 13) SPECIFY ANCHOR BOLT TYPE, LENGTH AND
 EMBEDMENT TO BE USED WITH SIMPSON MTT28B
 TO ANCHOR POSTS. SEE WALL SECTION 5 ON
 A201.
  
 14) SPECIFY CONNECTORS FOR 4X4 POST TO
 BEAM CONNECTION, BEAM TO FRAMING ABOVE,
 ETC. FOR THE INTERIOR BEARING WALLS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-29 Cont ID  
Sent By sgraham Date 2001-05-29 Time 15:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved