Plan Review Details - Permit 01051202
Plan Review Stops For Permit 01051202
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-08-06 Cont ID  
Sent By jwitmer Date 2001-08-06 Time 16:36 Rev Time 1.50
Received By jwitmer Date 2001-08-06 Time 16:36 Sent To  
Notes
2001-08-06 00:00:00PROVISO: CONTRACTOR TO APPEAL TO THE
 STATE BOARD FOR A VARIENCE ON THE
 ACCESSIBLE TOLIETS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-08-01 Cont ID  
Sent By jwitmer Date 2001-08-01 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2001-08-01 Time 10:42 Sent To  
Notes
2001-08-01 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01051202
 800 N OLIVE
 THE ROSARIAN ACADEMY
 MONTESSORI CLASSROOMS
 ARCH: SCHWAB, TWITTY & HANSER
 TEL: 832-5599
 FAX: 655-4828
 CONT: MJS CONSTRUCTION
 TEL: 722-1276
 FAX: 615-9496
  
 1)- FLORIDA ACCESSIBILITY CODE 1997,
 REQUIREMENTS FOR TOLIET ROOMS PER 4.22
 SEE ATTACHED DOCUMENTS AS TO RELIGIOUS
 EXEMPTIONS,(BUILDINGS INTENDED FOR
 CONGREGATIONS TO GATHER FOR THE PERFOR-
 MANCE OF RELIOUS CEREMONIES).
  
 BUILDING PLAN REVIEW
 JIM WITMR
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-13 Cont ID  
Sent By jwitmer Date 2001-06-13 Time 10:01 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-13 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01051202
 800 N OLIVE AV
 MJS CONSTRUCTION
 615- 9348
  
 STANDARD BUILDING CODE 1997
 1)- SBC 1503.3.2. ALL ROOFING SYSTEMS
 SHALL BE DESIGNED TO MEET THE WIND ZONE
 PRESCRIBED IN 1606 (110 MPH), ACCECTABLE
 PRODUCT APPROVAL REPORTS: SBCCI OR DADE
 COUNTY.
  
 2)- SBC AMEND. 1606.4/1707.4.1.THE CITY
 POLICY FOR STORM SHUTTERS REQUIRES A
 STORM SHUTTER SCHEDULE & KEY PLAN. THE
 SCHEDULE WILL INCLUDE WALL PRESSURES W/E
 OPENONG SIZE SHUTTER SIZE, SHUTTER SPAN
 HOR. OR VER., STORM BARS REQUIRED,
 ANCHOR SPACING, TYPE ANCHOR, IF STORM
 PANELS REQUIRE BOLTS.
  
 3)- DISCREPANCY SHEET A-3 RPPF PLAN
 DEPICTS A CONVENTIALLY FRAMED ROOF VS.
 STRUC. PLANS INDICATING A TRUSS PLAN.
  
 4)- FL ENERGY CODE 400. ENERGY CALS.
  
 5)-SBC 803.3 MINIMUM INTERIOR FINISH
 SCHEDULE.
  
 6)- FL ACC CODE 1997 REQUIREMENTS FOR
 TOLIET ROOMS PER 4.22.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-08-23 Cont ID  
Sent By dpalmer Date 2001-08-23 Time 11:43 Rev Time 0.00
Received By dpalmer Date 2001-08-23 Time 11:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-08-08 Cont ID  
Sent By dpalmer Date 2001-08-08 Time 07:39 Rev Time 0.00
Received By dpalmer Date 2001-08-08 Time 07:39 Sent To  
Notes
2001-08-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NONE OF THE
 NOTES FROM FIRST REVIEW WERE ADDRESSED.
  
 PLEASE SEE ATTACHED NOTES FORM FIRST
 REVIEW. PLEASE SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By dpalmer Date 2001-06-07 Time 21:02 Rev Time 0.00
Received By dpalmer Date 2001-06-07 Time 21:02 Sent To  
Notes
2001-06-07 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT SERVICE METER
 IS SHOWN AT 400A`S, TWO DISCONNECTS AT
 200A`S(FUSED AT 150A EACH) AND SERVICE
 ENTRANCE CONDUCTORS ONLY RATED FOR
 310A`S IN THE 75' COLUMN IN 310-16.
 PLEASE PLACE NOTE ON PLANS THAT FUSE
 RATINGS ARE NOT TO EXCEED SERVICE ENTRA-
 -NCE CONDUCTOR RATINGS.
 2)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS FOR PANELS
 WERE SUBMITTED BUT NOT FOR MAIN DISC`S
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC) PER 215-3 AND
 230-42.
 PLEASE SHOW LOAD CALCUALTIONS. PER 220
  
 4)NOTE: PLEASE SHOW CONDUCTORS SIZES
 FROM METER TO GUTTER AND GUTTER TO MAIN
 DISCONNECTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-21 Cont ID  
Sent By lsmith Date 2001-08-21 Time 10:48 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-08-17 Cont ID  
Sent By mcarsill Date 2001-08-17 Time 08:22 Rev Time 0.00
Received By mcarsill Date 2001-08-17 Time 08:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-07-31 Cont ID  
Sent By mcarsill Date 2001-07-31 Time 14:09 Rev Time 0.00
Received By mcarsill Date 2001-07-31 Time 14:09 Sent To  
Notes
2001-07-31 00:00:001) NO INFORMATION ON THE NUMBER OF
 HOURS OF OPERATION FOR THE DAY CARE
 CENTER.
 2) BATHROOM DOORS AS PER THE CODE
 REQUIRES THAT STAFF UNLOCKS THE DOORS.
 3) CLOSET DOOR LATCH SHALL BE
 OPERATIONAL FROM THE INSIDE BY CHILDREN.
 4) PROTECTIVE OUTET COVERS FOR
 ELECTRICAL OUTLETS ARE REQUIRED.
 5) CLASS C FLAME SPREAD MATERIALS NOT
 PERMITTED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-29 Cont ID  
Sent By mcarsill Date 2001-05-29 Time 09:06 Rev Time 0.00
Received By mcarsill Date 2001-05-29 Time 09:06 Sent To  
Notes
2001-05-29 00:00:001) PLEASE PROVIDE THE AGES OF CHILDREN
 WHO WILL OCCUPY THE BUILDING. PLEASE
 INDICATE THE HOURS OF OPERATION FOR
 THE BUILDING.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 3) PLEASE INDICATE WHAT TYPE OF
 LOCKING DEVICES WILL BE PRESENT ON EXIT
 DOORS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-09 Cont ID  
Sent By pkrauss Date 2001-08-09 Time 15:21 Rev Time 0.35
Received By pkrauss Date 2001-08-09 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-09 Cont ID  
Sent By pkrauss Date 2001-06-09 Time 07:59 Rev Time 0.35
Received By pkrauss Date 2001-06-09 Time 07:50 Sent To  
Notes
2001-06-09 00:00:00********************DENIED**************
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 AUXILIARY DRAIN PAN WITH OVER FLOW
 PROTECTION IS REQUIRED AS PER 304.8.6.1.
  
 NOTE:DUCT SMOKE DETECTOR TO PLACED IN
 RETURN AIR STREAM PERIOR TO ANY
 EXHAUSTING FROM BUILDING OR
 MIXING WITH FRESH AIR MAKE-UP.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2002-02-10 00:00:00REVISION: ADD SINK PER HEALTH DEPT. OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-10 Cont ID  
Sent By pschmitz Date 2001-08-10 Time 10:50 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-08-10 00:00:00PLUMBING PLAN REVIEW,PROVISO
 (1) AS PER HAMED,DELETE NOTE #16 AIR
 CHAMBERS.
 (2) SIZE AND PLACEMENT OF WATER ARRESTOR
 PER MFG INSTRUCTIONS.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-08 Cont ID  
Sent By pschmitz Date 2001-06-08 Time 08:36 Rev Time 1.20
Received By pschmitz Date 2001-06-08 Time 08:38 Sent To  
Notes
2001-06-07 00:00:00PLUMBING PLAN REVIEW"DENIED"
 ROSARIAN ACADEMY MONTESSORI CLASSROOMS
 (1) SHT A2 REST RM'S IN CLASS RM TO
 COMPLY W/FACBC-97 SEC 4.22.1 AND SPC 94
 TAB 407 MINIMUM FACILITIES, ONLY 1 W/C
 FOR 1-50 PERSONS, IS REQUIRED.
 (2) SHT A2 BREAK RM SINK IN STAFF LOUNGE
 TO COMPLY W/FACBC 97 SEC 4.24 HGTH 34",
 AND SEC 4.24.5 CLEAR FLR SPACE 30"X48".
 (3) SHT P1,P2 AIR CHAMBER,GENERAL NOTE
 #16 COMPLY WSPC 94 SEC 607.8.3 AIR CHAM-
 BERS TO BE ACCESSIBLE, RECHARGEABLE.
 (4) SHT P1 WATER PIPE ISOMETRIC,SHOW
 WHICH LINE IS HOT AND WHICH IS COLD,WITH
 DASHED LINES.SPC 94 SEC 104.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X 8233
 PREVIOUS PHONE CONVERSATION WITH
 MR. HAMED RODREGREQUEZ832-5599

Review Stop Z ZONING
Rev No 1 Status P Date 2001-08-23 Cont ID  
Sent By pschmitz Date 2001-06-08 Time 08:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***