| Plan Review Stops For Permit 01051202 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-06 |
Time |
16:36 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-08-06 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2001-08-06 00:00:00 | PROVISO: CONTRACTOR TO APPEAL TO THE | | | STATE BOARD FOR A VARIENCE ON THE | | | ACCESSIBLE TOLIETS. JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-01 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-08-01 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2001-08-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01051202 | | | 800 N OLIVE | | | THE ROSARIAN ACADEMY | | | MONTESSORI CLASSROOMS | | | ARCH: SCHWAB, TWITTY & HANSER | | | TEL: 832-5599 | | | FAX: 655-4828 | | | CONT: MJS CONSTRUCTION | | | TEL: 722-1276 | | | FAX: 615-9496 | | | | | | 1)- FLORIDA ACCESSIBILITY CODE 1997, | | | REQUIREMENTS FOR TOLIET ROOMS PER 4.22 | | | SEE ATTACHED DOCUMENTS AS TO RELIGIOUS | | | EXEMPTIONS,(BUILDINGS INTENDED FOR | | | CONGREGATIONS TO GATHER FOR THE PERFOR- | | | MANCE OF RELIOUS CEREMONIES). | | | | | | BUILDING PLAN REVIEW | | | JIM WITMR | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-06-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-06-13 |
Time |
10:01 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01051202 | | | 800 N OLIVE AV | | | MJS CONSTRUCTION | | | 615- 9348 | | | | | | STANDARD BUILDING CODE 1997 | | | 1)- SBC 1503.3.2. ALL ROOFING SYSTEMS | | | SHALL BE DESIGNED TO MEET THE WIND ZONE | | | PRESCRIBED IN 1606 (110 MPH), ACCECTABLE | | | PRODUCT APPROVAL REPORTS: SBCCI OR DADE | | | COUNTY. | | | | | | 2)- SBC AMEND. 1606.4/1707.4.1.THE CITY | | | POLICY FOR STORM SHUTTERS REQUIRES A | | | STORM SHUTTER SCHEDULE & KEY PLAN. THE | | | SCHEDULE WILL INCLUDE WALL PRESSURES W/E | | | OPENONG SIZE SHUTTER SIZE, SHUTTER SPAN | | | HOR. OR VER., STORM BARS REQUIRED, | | | ANCHOR SPACING, TYPE ANCHOR, IF STORM | | | PANELS REQUIRE BOLTS. | | | | | | 3)- DISCREPANCY SHEET A-3 RPPF PLAN | | | DEPICTS A CONVENTIALLY FRAMED ROOF VS. | | | STRUC. PLANS INDICATING A TRUSS PLAN. | | | | | | 4)- FL ENERGY CODE 400. ENERGY CALS. | | | | | | 5)-SBC 803.3 MINIMUM INTERIOR FINISH | | | SCHEDULE. | | | | | | 6)- FL ACC CODE 1997 REQUIREMENTS FOR | | | TOLIET ROOMS PER 4.22. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-23 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-23 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-08 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-08 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2001-08-08 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT NONE OF THE | | | NOTES FROM FIRST REVIEW WERE ADDRESSED. | | | | | | PLEASE SEE ATTACHED NOTES FORM FIRST | | | REVIEW. PLEASE SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-06-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-07 |
Time |
21:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-07 |
Time |
21:02 |
Sent To |
|
|
| Notes |
| 2001-06-07 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT SERVICE METER | | | IS SHOWN AT 400A`S, TWO DISCONNECTS AT | | | 200A`S(FUSED AT 150A EACH) AND SERVICE | | | ENTRANCE CONDUCTORS ONLY RATED FOR | | | 310A`S IN THE 75' COLUMN IN 310-16. | | | PLEASE PLACE NOTE ON PLANS THAT FUSE | | | RATINGS ARE NOT TO EXCEED SERVICE ENTRA- | | | -NCE CONDUCTOR RATINGS. | | | 2)NOTE:PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS FOR PANELS | | | WERE SUBMITTED BUT NOT FOR MAIN DISC`S | | | | | | 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) PER 215-3 AND | | | 230-42. | | | PLEASE SHOW LOAD CALCUALTIONS. PER 220 | | | | | | 4)NOTE: PLEASE SHOW CONDUCTORS SIZES | | | FROM METER TO GUTTER AND GUTTER TO MAIN | | | DISCONNECTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-08-21 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-17 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-17 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-07-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-31 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-31 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2001-07-31 00:00:00 | 1) NO INFORMATION ON THE NUMBER OF | | | HOURS OF OPERATION FOR THE DAY CARE | | | CENTER. | | | 2) BATHROOM DOORS AS PER THE CODE | | | REQUIRES THAT STAFF UNLOCKS THE DOORS. | | | 3) CLOSET DOOR LATCH SHALL BE | | | OPERATIONAL FROM THE INSIDE BY CHILDREN. | | | 4) PROTECTIVE OUTET COVERS FOR | | | ELECTRICAL OUTLETS ARE REQUIRED. | | | 5) CLASS C FLAME SPREAD MATERIALS NOT | | | PERMITTED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-05-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-29 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-29 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2001-05-29 00:00:00 | 1) PLEASE PROVIDE THE AGES OF CHILDREN | | | WHO WILL OCCUPY THE BUILDING. PLEASE | | | INDICATE THE HOURS OF OPERATION FOR | | | THE BUILDING. | | | 2) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION. | | | 3) PLEASE INDICATE WHAT TYPE OF | | | LOCKING DEVICES WILL BE PRESENT ON EXIT | | | DOORS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-08-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-09 |
Time |
15:21 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-08-09 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-06-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-09 |
Time |
07:59 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-06-09 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2001-06-09 00:00:00 | ********************DENIED************** | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89. | | | | | | AUXILIARY DRAIN PAN WITH OVER FLOW | | | PROTECTION IS REQUIRED AS PER 304.8.6.1. | | | | | | NOTE:DUCT SMOKE DETECTOR TO PLACED IN | | | RETURN AIR STREAM PERIOR TO ANY | | | EXHAUSTING FROM BUILDING OR | | | MIXING WITH FRESH AIR MAKE-UP. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-10 00:00:00 | REVISION: ADD SINK PER HEALTH DEPT. OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-08-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-08-10 |
Time |
10:50 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-10 00:00:00 | PLUMBING PLAN REVIEW,PROVISO | | | (1) AS PER HAMED,DELETE NOTE #16 AIR | | | CHAMBERS. | | | (2) SIZE AND PLACEMENT OF WATER ARRESTOR | | | PER MFG INSTRUCTIONS. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-06-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-08 |
Time |
08:36 |
Rev Time |
1.20 |
| Received By |
pschmitz |
Date |
2001-06-08 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2001-06-07 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | ROSARIAN ACADEMY MONTESSORI CLASSROOMS | | | (1) SHT A2 REST RM'S IN CLASS RM TO | | | COMPLY W/FACBC-97 SEC 4.22.1 AND SPC 94 | | | TAB 407 MINIMUM FACILITIES, ONLY 1 W/C | | | FOR 1-50 PERSONS, IS REQUIRED. | | | (2) SHT A2 BREAK RM SINK IN STAFF LOUNGE | | | TO COMPLY W/FACBC 97 SEC 4.24 HGTH 34", | | | AND SEC 4.24.5 CLEAR FLR SPACE 30"X48". | | | (3) SHT P1,P2 AIR CHAMBER,GENERAL NOTE | | | #16 COMPLY WSPC 94 SEC 607.8.3 AIR CHAM- | | | BERS TO BE ACCESSIBLE, RECHARGEABLE. | | | (4) SHT P1 WATER PIPE ISOMETRIC,SHOW | | | WHICH LINE IS HOT AND WHICH IS COLD,WITH | | | DASHED LINES.SPC 94 SEC 104.3 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X 8233 | | | PREVIOUS PHONE CONVERSATION WITH | | | MR. HAMED RODREGREQUEZ832-5599 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-08 |
Time |
08:38 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|