Plan Review Details - Permit 01051150
Plan Review Stops For Permit 01051150
Review Stop P PLUMBING
Rev No 3 Status P Date 2001-06-28 Cont ID  
Sent By kstevens Date 2001-06-28 Time 11:59 Rev Time 1.25
Received By kstevens Date 2001-06-28 Time 11:59 Sent To  
Notes
2001-06-28 00:00:00PROVISO
  
 SPACE UNDER STAIRS SHALL BE 1 HOUR FIRE
 RATED AND WILL NOT BE USED FOR STORAGE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-08 Cont ID  
Sent By kstevens Date 2001-06-08 Time 15:15 Rev Time 0.75
Received By kstevens Date 2001-06-08 Time 15:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-01 Cont ID  
Sent By kstevens Date 2001-06-01 Time 15:22 Rev Time 1.25
Received By kstevens Date 2001-06-01 Time 15:22 Sent To  
Notes
2001-06-01 00:00:00REVIEW NOTES: FAILED
  
 REFERENCE SGC-97 - TABLE 305.4A -
 TABLE 305.4E - TRACPIPE - TABLE N-4
  
 DISTANCE TO MOST REMOTE OUTLET PER
 NUMBERS SUPPLIED 91' SO 100' ON TABLES
 WAS DISTANCE USED.
  
 TOTAL FIXTURE UNITS USED WAS 632K
  
 USING THIS INFORMATION THE SIZING OF
 PIPE SUBMITTED IS NOT LARGE ENOUGH.
 2" TO FIRST TEE, 1-1/2"X1'X2".
 P.E. PIPE TO BE 1-1/2" TO POOL HEATER
 1'X1/2"X3/4" GALV. TEE
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377