2001-06-06 00:00:00BUILDING PLAN REVIEW
 O/B NUNEZ, CARMELA
 PERMIT # 01051100
 3000 STANFORD ROAD
  
 1)- OWNER / BUILDERS ARE TO FOLLOW THE
 STANDARD BUILDING CODE SSTD 10-97 WHEN
 PLANS AREN'T DRAWN BY A DESIGN PROFES-
 SIONAL. THIS IS A PRESCRIPTIVE CODE,
 WHERE SPECIFIC CONSTRUCTION REQUIREMENTS
 ARE NOT GIVEN, APPROPRIATE REQUIREMENTS
 OF THE STANDARD BUILDING CODE SHALL
 PREVAIL. WINDOWS AND DOORS SHALL BE
 DESIGNED FOR COMPONENTS & CLADDING LOADS
 OF THE SBC 1606.
  
 2)- SSTD- 303.1 MONOLITHIC SLAB CONFIGUR
 ATION 20" TALL X 12"WIDE.
  
 3)- SSTD- 203.3.2 MINIMUM EPOXY EMBED-
 MENT 6".
  
 4)- SSTD- 205.8 PLANS DO NOT INDICATE
 ASSEMBLIES & BEAMS SPANNING OPENINGS.
 THERE ARE 3 CHOICES, PAGE 36/41 GIVE THE
 STEEL REQUIREMENTS, PAGE 41 IS THE BEAM/
 LINTEL ASSEMBLY, USED COMMONLY IN THIS
 AREA. NOTE: PAGE 41 INDICATES A 16" BEAM
 ALL CELLS ARE GROUTED ABOVE THE LINTEL &
 THE AMOUNT OF STEEL REQUIRED FOR
 PLACEMENT IN THE LINTEL.
  
 5)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THERE IS NO WINDOW BUCK DETAIL GIVING
 THE ATTACHMENT SCHEDULE FOR WINDOWS AND
 DOORS.
  
 6)- TRUSS OR RAFTER ANCHOR: NO INFORMATI
 ON IS GIVEN FOR UPLIFT. THE MANUFACTURE
 MAKE ,MODEL, LATERAL LOADS ETC.
  
 7)- DICCREPANCY: NORTH SIDE ELEVATION
 SHOWS NO OVERHANG ON THE SIDES OF THE
 BUILDING, ON THE ROOF FRAMING PLAN IT
 APPEARS THERE MAY BE APPROXIMATELY A
 1"-0" OVERHANG?
  
 8)- SBC AMEND 2111.6 WHERE EXTERIOR HOLL
 OW MASONRY UNITS BEAR ON A CONCRETE
 SURFACE, A 1 1/2" RECESS, OR OTHER
 APPROVED WATER-STOP ACCEPTED BY THE
 BUILDING OFFICIAL, SHALL BE PROVIDED TO
 PREVENT WATER INTRSION.
  
 9)- SBC 1707.4 GLAZED OPENINGS ARE
 REQUIRED TO BE TESTED 10 SEC. LOAD TEST
 EQUAL TO 1.5 TIMES THE DESIGN PRESSURE.
  
 10)- SBC AMEND 1606.4.1/1707.4.1 GLAZED
 OPENINGS, WINDOWS & DOORS ARE REQUIRED
 TO SHOW PRODUCT TESTING FOR LARGE MISSLE
 IMPACT TESTING EITHER SBCCI OR DADE
 COUNTY PRODUCT TESTING REPORTS ARE
 ACCEPTABLE. IF WINDOWS & DOORS DO NOT HA
 VE PRODUCT TESTING STORM SHUTTERS WILL
 BE REQUIRED WITH THIS TESTING REPORT.
  
 11)- ROOFING: SBC 1503.3.2 ALL ROOFING
 SYSTEMS WILL BE TESTED FOR THE WIND ZONE
 THEY WILL BE USED IN, (110 MPH).
  
 12)- SHOW PRODUCT TESTING FOR A FINISHED
 ROOFING SYSTEM 90 LB? IS THIS TO BE A
 MODIFIED TORCH DOWN SYSTEM?
  
 13)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED:
 A)- PLANS INDICATE THE 2X10 ARE TO SIT
 ABOUT 6" ABOVE THE EXISTING BEAM,
 WHAT IS TO HOLD THEM AT THIS
 HEIGTH AND HOW ARE THEY STRAPPED
 TO THE EXISTING BEAM, GIVE ADDI-
 TIONAL INFORMATION.
 B)- WALL REMOVAL: WHAT IS GOING TO
 HOLD UPTHE EXISTING RAFTERS?
 C)- IS THE CLOSET & BATH PART OF THIS
 REMODEL?
 D)- DISCREPANCIES: IN DIMENSIONS,
 EXISTING FLOOR SLAB VS. FLOOR
 LAT OUT VS. EXISTING EAST WALL?
 E)- MISSING INFORMATION INSULATION ON
 EXTERIOR WALLS
 F)- NO ELECTRICAL INFORMATION.
  
 14)- MISSING: 1997 FL ENERGY CALCULATION
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-06 Cont ID  
Sent By jwitmer Date 2001-06-06 Time 19:19 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-06 00:00:00PER D.V. PALMER

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-23 Cont ID  
Sent By sgraham Date 2001-05-23 Time 09:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved