Plan Review Details - Permit 01051077
Plan Review Stops For Permit 01051077
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-12 Cont ID  
Sent By mcarsill Date 2001-06-12 Time 13:32 Rev Time 0.00
Received By mcarsill Date 2001-06-12 Time 13:32 Sent To  
Notes
2001-06-12 00:00:00ON JULY 12, 2001, WRITER CALLED LADONNA
 HENDERSON OF RUBY BELL CORPORATION. IT
 WAS INDICATED TO BOTH WRITER AND PATTY
 KRAUSS THAT THE CEILING IS NOT RATED.
  
 1) A CLEANOUT IS TO BE PROVIDED AT 12
 FEET.
 2) THE TECHNICAL DATA PROVIDED FOR THE
 FLAMESHIELD BLANKET INDICATES THAT
 PINNING IS REQUIRED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-01 Cont ID  
Sent By mcarsill Date 2001-06-01 Time 14:11 Rev Time 0.00
Received By mcarsill Date 2001-06-01 Time 14:11 Sent To  
Notes
2001-06-01 00:00:001) NO DRAWINGS OF THE EXHAUST DUCT WHEN
 IT LEAVES THE TOP OF THE HOOD. PLEASE
 PROVIDE DUCT DRAWING.
 2) A FIRE DAMPER IS REQUIRED AT SUPPLY
 AIR OPENING IF IT IS PRESENT UNDER THE
 WELDED PORTION OF THE HOOD.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SUPPRESSION SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-12 Cont ID  
Sent By pkrauss Date 2001-06-12 Time 13:52 Rev Time 0.40
Received By pkrauss Date 2001-06-12 Time 13:51 Sent To  
Notes
2001-06-12 00:00:00*******************PROVISO**************
  
 CALL FOR AN INSPECTION PRIOR TO CONCEALI
 NG DUCTS OR WELDS WITH PAINT OR ANY OTHE
 R MATERIAL.IF DUCT IS TO BE WRAPPED WI
 TH A TWO LAYERED FIRE WRAP, CALL FOR AN
 INSPECTION ON THE FIRST LAYER BEFORE THE
 SECOND LAYER IS APPLIED.
  
 NOTE:MINIMUM SLOPE FOR GREASE HOOD
 DUCT SYSTEMS IS 1 INCH PER FOOT
 (1997 SMC 505.4), NOT 1/4 PER
 FOOT AS DICTATED IN NFPA 96.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-01 Cont ID  
Sent By ndenmark Date 2001-06-01 Time 15:00 Rev Time 0.33
Received By ndenmark Date 2001-06-01 Time 15:00 Sent To  
Notes
2001-06-01 00:00:00DENIED
 PROVIDE INFORMATION ON DUCTS BOTH
 EXHAUST AND MAKE UP AIR
 IF MAKE UP AIR ENTERS HOOD UNDER MAIN
 BODY OF HOOD A FIRE DAMPER WILL BE
 REQUIRED PER NFPA 96. PROVIDE CLEAR
 ENOUGH DRAWING TO INDICATE ANY
 MATERIAL/PHYSICAL SEPARATION BETWEEN
 HOOD AND MAKE UP AIR PLENUM TO INDICATE
 FIRE DAMPER REQUIREMENT