Plan Review Details - Permit 01051022
Plan Review Stops For Permit 01051022
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-21 Cont ID  
Sent By mcarsill Date 2001-06-21 Time 13:27 Rev Time 0.00
Received By mcarsill Date 2001-06-21 Time 13:27 Sent To  
Notes
2001-06-21 00:00:001) GENERATOR ROOM IS TO BE AT LEAST
 TWO HOUR FIRE RATED AND BE EQUIPPED
 WITH B LABELED (1 1/2 ) RATED FIRE
 DOORS.
 2) FIRE DAMPERS REQUIRED FOR ANY
 VENTILATION LOUVERS.
 3) VENTING OF FUEL TANK TO COMPLY WITH
 APPLICABLE STANDARDS AND BE VISIBLE.
 4) PLEASE PROVIDE WELDING CERTIFICATIONS
 TO MECHANICAL DIVISION.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-29 Cont ID  
Sent By mcarsill Date 2001-05-29 Time 09:27 Rev Time 0.00
Received By mcarsill Date 2001-05-29 Time 09:27 Sent To  
Notes
2001-05-29 00:00:001) NO CUT SHEETS PROVIDED FOR FUEL TANK
 OR OTHER APPURTENANT EQUIPMENT. PLEASE
 PROVIDE CUT SHEETS ON FUEL TANK AND
 OTHER EQUIPMENT SHOWN WITH DRAWINGS.
  
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-21 Cont ID  
Sent By pkrauss Date 2001-06-21 Time 13:33 Rev Time 0.45
Received By pkrauss Date 2001-06-21 Time 13:32 Sent To  
Notes
2001-06-21 00:00:00******************PROVISO***************
  
  
 SEE FIRE RESCUE REVIEW COMMENTS.
  
 NOTE:ALL COMMENTS TO BE COMPLIED WITH
 PRIOR TO FINAL INSPECTION.
  
 NO C.O. TO BE ISSUED PRIOR TO COMPLIANCE
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-01 Cont ID  
Sent By ndenmark Date 2001-06-01 Time 09:04 Rev Time 0.33
Received By ndenmark Date 2001-06-01 Time 09:04 Sent To  
Notes
2001-06-01 00:00:00PROVIDE INFO REQUIRED BY FIRE DEPT.