Plan Review Details - Permit 01051020
Plan Review Stops For Permit 01051020
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-06-05 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 21:50 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 21:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-05-30 Cont ID  
Sent By hmoser Date 2001-05-30 Time 18:13 Rev Time 0.33
Received By hmoser Date 2001-05-30 Time 18:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-27 Cont ID  
Sent By jleech Date 2001-11-27 Time 19:22 Rev Time 0.33
Received By jleech Date 2001-11-27 Time 19:21 Sent To  
Notes
2001-11-27 00:00:00REVISED RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-29 Cont ID  
Sent By kstevens Date 2001-05-29 Time 11:34 Rev Time 0.25
Received By kstevens Date 2001-05-29 Time 11:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-08-01 Cont ID  
Sent By rmcdouga Date 2001-08-01 Time 09:31 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-07-20 Cont ID  
Sent By rmcdouga Date 2001-07-20 Time 11:02 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-07-20 00:00:00*************BUILDING UNSAT*************
  
 1) THE SECOND STORY WINDOW ON THE RIGHT
 SIDE OF THE STRUCTURE AT THE STAIR
 LANDING IS LOCATED IN A WALL ON A ZERO
 LOT LINE. NO OPENINGS ARE ALLOWED IN THE
 WALL PER TABLE 600 OF THE 97 SBC. PLEASE
 CORRECT THE DRAWINGS.
  
 2) THE PRIVACY WALL FOOTING SHOWN IN
 DETAIL 1 ON SHEET S-1 (ZERO LOT LINE),
 ENCROACHES ON THE ADJACENT PROPERTY AND
 MAY INTERFERE WITH THE ADJOINING
 STRUCTURE.
  
 3) THE IMPORTANCE FACTOR LISTED IN THE
 DESIGN CERTIFICATION FORM ON SHEET S-1
 IS INCORRECT. THE CORRECT IMPORTANCE
 FACTOR FROM TABLE 6-2 IN ASCE 7-95 IS
 1.00.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-06-14 Cont ID  
Sent By rmcdouga Date 2001-06-14 Time 13:08 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-14 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) TABLE 600: NO OPENINGS ARE ALLOWED
 IN A ZERO LOT LINE WALL. A PORTION OF
 THE LIVING ROOM WINDOW SHOWN ON SHEET
 A-1.0 AS A DOUBLE WINDOW AND ON A-2.0 AS
 A SINGLE WINDOW IS LOCATED IN THE ZERO
 LOT LINE WALL AND IS NOT ALLOWED. THE
 WINDOW LOCATED ON THE SECOND FLOOR AT
 THE STAIR LANDING IS ALSO LOCATED IN THE
 ZERO LOT LINE WALL. PLEASE MAKE THE
 REQUIRED CORRECTIONS.
  
 3) THE A/C COMPRESSOR UNIT SHOWN ON THE
 FIRST FLOOR PLAN (A-1.0) IS LOCATED ON
 THE ADJACENT LOT. PLEASE CORRECT.
  
 4) FIRST FLOOR PLAN (A-1.0) APPEARS TO
 INDICATE A PRIVACY WALL AT THE COVERED
 PORCH,HOWEVER NOTHING IS INDICATED ON
 THE FOUNDATION PLAN (S-1).PLEASE CLARIFY
  
 5) PAGE 5 OF THE SOIL REPORT STATES THAT
 EXTERIOR FOUNDATIONS SHOULD BEAR AT
 LEAST 18" BELOW ADJACENT OUTSIDE FINAL
 GRADE. THE CITY AMENDMENTS TO THE 97 SBC
 REQUIRE THE BUILDING FLOOR ELEVATION TO
 BE A MINIMUM OF 4" ABOVE FINAL GRADE.
 THIS EQUATES TO A 22" DEEP EXTERIOR
 FOOTING. THE PLANS INDICATE 18" DEEP
 FOOTINGS. PLEASE REVIEW AND CORRECT OR
 PROVIDE APPROVAL LETTER FROM SOIL
 ENGINEER.
  
 6) THE PRODUCT APPROVAL FOR THE 16'X7'
 OVERHEAD GARAGE DOOR DOES NOT LIST A
 DOOR OF THIS SIZE WHICH HAS A DESIGN
 LOAD CAPABLE OF WITH STANDING THE DESIGN
 PRESSURES (+42,-45) GIVEN ON SHEET S1
 FOR THE GARAGE DOOR OPENING.
  
 7)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIALS FOR FLAT ROOF AREAS
  
 8) PRODUCT APPROVAL FOR "SKANDIA" ROOF
 TILES EXPIRED ON 12-16-00.
  
 9) TRUSSES: PROVIDE DETAIL OF ATTACHMENT
 OF GIRDER FG1 AT COLUMN MC4(SHEET S1).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-23 Cont ID  
Sent By sgraham Date 2001-05-23 Time 13:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***