Plan Review Details - Permit 01051006
Plan Review Stops For Permit 01051006
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-06-08 Cont ID  
Sent By jwitmer Date 2001-06-08 Time 16:08 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-08 00:00:00PROVISO: STANDARD BUILDING CODE- 1204.2
 SURROUNDING MATERIALS:THE WALLS & FLOORS
 OF ALL PUBLIC RESTROOMS SHALL BE LINED
 WITH NONABSORBENT MATERIALS TO A HEIGTH
 OF4'-0" ABOVE THE FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659- 8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-18 Cont ID  
Sent By dpalmer Date 2001-06-18 Time 08:33 Rev Time 0.00
Received By dpalmer Date 2001-06-18 Time 08:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-06-07 Cont ID  
Sent By dpalmer Date 2001-06-07 Time 20:22 Rev Time 0.00
Received By dpalmer Date 2001-06-07 Time 20:22 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-06-09 Cont ID  
Sent By pkrauss Date 2001-06-09 Time 07:09 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-23 Cont ID  
Sent By mcarsill Date 2001-05-23 Time 12:41 Rev Time 0.00
Received By mcarsill Date 2001-05-23 Time 12:40 Sent To  
Notes
2001-05-23 00:00:001) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-06-09 Cont ID  
Sent By pkrauss Date 2001-06-09 Time 07:01 Rev Time 0.30
Received By pkrauss Date 2001-06-09 Time 06:57 Sent To  
Notes
2001-06-09 00:00:00*******************DENIED***************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE SUBMIT PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-24 Cont ID  
Sent By pschmitz Date 2001-06-24 Time 15:37 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-24 00:00:00PLUMBING PROVISO SEE SHT.P-1
 TWO WAY CO'S ON SANI,GREASE TANK.
 F/D REQ IN PUBLIC REST.RM,W/TRAP PRIMER
 SEC 409.4 SPC 94.
 3 COMP SINK NO RUNNING TRAPS.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-02 Cont ID  
Sent By pschmitz Date 2001-06-02 Time 08:25 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-02 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT A-1 MINIMUM FACILITIES REQ.
 SPC-94 SEC 407.2.2,TAB 407,MEN'S &
 WOMEN'S REST RM'S, ONE OF EACH DIRECTLY
 ACCESSIBLE TO THE PUBLIC,FROM THE AREA
 THEY ARE INTENDED TO SERVE, TO COMPLY
 W/FACBC 97 SEC 4.16
 LOCATION OF PLUMBING FIXTURES SEC 404.2.
 TOILET RM'S SHALL NOT OPEN DIRECTLY INTO
 RM'S USED FOR THE PREPRATION OF FOOD
 FOR SERVICE TO THE PUBLIC.
 (2) GREASE TRAP MIN SIZE 750 GALS, FAC
 10D-6.054(3)(D) & WPB RSTP ORD #2938-96
 GREASE INTERCEPTORS SHALL NOT BE LOCATED
 WITHIN FOOD STORAGE,PREPRATION, OR CLEAN
 EQUIPMENT STORAGE AREAS AND SHALL BE
 READLY ACCESSIBLE, FOR MAINTENANCE.
 (3) SHT P-1 PLBG NOTES #1 CURRENT CODE.
 STD PLBG.CODE 94,
 NOTE # 13 AIR CHAMBERS TO BE ACCESSIBLE
 & RECHARGEABLE SPC 94 SEC 607.8.3
 (4) SHT P-1 WATER SUPPLY, PROTECTED WITH
 A RPZV BACK FLOW PREVENTER SEC 606.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-06-09 Cont ID  
Sent By pkrauss Date 2001-06-09 Time 07:09 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***