Plan Review Details - Permit 01050966
Plan Review Stops For Permit 01050966
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-10-15 Cont ID  
Sent By jwitmer Date 2001-10-15 Time 10:39 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-10-15 00:00:00REVISION #4 09/20/01 OKJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-23 Cont ID  
Sent By jwitmer Date 2001-07-23 Time 14:46 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By jwitmer Date 2001-06-07 Time 16:29 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050966
 1 N. CLEMATIS SUITE 5TH FLOOR
  
 1)- A SUITE # WILL BE REQUIRED TO
 COMPLETE THE ADDRESS.
  
 2)- FL ACCESSIBILITY CODE: OFFICE #4
 SHEET A2-E REQUIRES 18" CLEARENCE PER
 FL ACC CODE 4.13.6.
  
 3)- SHEET A6-E DETAIL #7 PER U-465 UL
 LISTING, STUD SPACING NOT GIVEN.
  
 4)- SHEET A6-E DEAIL #7 CORRIDOR PARTI-
 TIONS & FIRE RATED WALLS REQUIRED TO
 HAVE PROTECTED OPENINGS SHALL PERMANETLY
 IDENTIFY WITH SIGNS OR STECLING "FIRE &
 SMOKE BARRIER PROTECT ALL OPENINGS".
  
 5)- SBC 704.2.1.2. DETAILS 6& 7 OF A6-E
 ALL PARTITIONS REQUIRED TO HAVE FIRE RES
 ISTANCE RATING SHALL EXTEND FROM THE TOP
 OF THE FLOOR BELOW TO THE CEILING ABOVE
 AND SHALL BE SECURELY ATTACHED & SEALED,
 HAVING A FIRE RESISTANCE RATING AT LEAST
 EQUAL FOR THE PARTITION.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 18:15 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 18:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 20:05 Sent To  
Notes
2001-09-10 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PER FS/FAC
 PLANS MUST CONTAIN ORIG WET SIGNATURE
 OF ARCHITECT.PLEASE NOTE THAT PLANS ARE
 HAVE A STAMPED SIG. NOT PERMITTED PER
 61G15-23.002, 481.221.
  
 2)NOTE: PLEASE ALSO NOTE THAT PLANS ARE
 NOTE SIGNED, DATED AND SEALED BY THE
 ORIGINAL ENGINEERS OF RECORD. "KAMM"
 FOR ALL "M,E,P" DRAWINGS BOTH SETS.
  
 3)NOTE: PLEASE NOTE THAT E5.1 DOES NOT
 INDICATE ANY CHANGES? CLOUDS? ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-06-07 Cont ID  
Sent By dpalmer Date 2001-06-07 Time 18:58 Rev Time 0.00
Received By dpalmer Date 2001-06-07 Time 18:58 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-06-08 Cont ID  
Sent By lsmith Date 2001-06-08 Time 10:57 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-10-16 Cont ID  
Sent By mcarsill Date 2001-10-16 Time 10:59 Rev Time 0.00
Received By mcarsill Date 2001-10-16 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-11 Cont ID  
Sent By mcarsill Date 2001-09-11 Time 13:59 Rev Time 0.00
Received By mcarsill Date 2001-09-11 Time 13:59 Sent To  
Notes
2001-09-11 00:00:00PLANS DO NOT HAVE ORIGINAL SIGNATURE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By mcarsill Date 2001-05-22 Time 10:08 Rev Time 0.00
Received By mcarsill Date 2001-05-22 Time 10:08 Sent To  
Notes
2001-05-22 00:00:001) INTERIOR FINISH TO BE A MINIMUM OF
 CLASS C ON THE WALLS AND CEILINGS.
 2) AN ADDITIONAL EMERGENCY LIGHT MAY
 BE NEEDED NEAR THE WAITING ROOM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-10-17 Cont ID  
Sent By pkrauss Date 2001-10-13 Time 07:16 Rev Time 0.40
Received By pkrauss Date 2001-10-13 Time 07:16 Sent To  
Notes
2001-10-13 00:00:00*******************DENIED***************
  
  
 ENGINEER TO REVISE DWGS AS PER CONVERSAT
 ION 10-17-01 WITH D. FRICK (KAMM) PHK
  
  
  
  
 PLANS INDICATE REMOVING FIRE DAMPER TO
 NEW LOCATION.LOCATION NOT SPECIFIED.
  
 ALL PENETRATIONS THROUGH A FIRE RATED
 WALL SHALL HAVE PROTECTION BY MEANS OF
 A FIRE DAMPER AS PER 1997 SMC 610.1.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-09-24 Cont ID  
Sent By pkrauss Date 2001-09-24 Time 12:19 Rev Time 0.40
Received By pkrauss Date 2001-09-24 Time 12:09 Sent To  
Notes
2001-09-24 00:00:00******************DENIED****************
  
  
 PLANS ARE NOT SEALED, SIGNED OR DATED
 BYTHE ENGINEER OF RECORD (KAMM).
  
 PLEASE ALSO NOTE SIGNATURE FOR THE
 ARCHITECT IS A STAMP AND NOT AN
 ORIGINAL SIGNATURE.PLANS ARE
 OTHERWISE ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-23 Cont ID  
Sent By pkrauss Date 2001-07-23 Time 10:36 Rev Time 0.35
Received By pkrauss Date 2001-07-23 Time 10:35 Sent To  
Notes
2001-07-23 00:00:00PROVISO FROM 6-8-01, ENGINEER RESPONSE
 -FIRE DAMPER INSTALLED PREVIOUSLY AND
 INSPECTED - APPROVED INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-08 Cont ID  
Sent By pkrauss Date 2001-06-08 Time 08:17 Rev Time 0.35
Received By pkrauss Date 2001-06-08 Time 07:59 Sent To  
Notes
2001-06-08 00:00:00*******************PROVISO**************
  
 DRAWING M2.1 INDICATES THE FIRE DAMPER
 IN THE EQUIPMENT ROOM (523) PENETRATING
 THE WALL ON A DIAGONAL, PLEASE
 REFERENCE MANUFACTURER INSTALLATION
 INSTRUCTIONS.
  
 RATED WALL MAY HAVE TO BE BUILT OUT AS
 TO ACCOMIDATE FIRE DAMPER TO PENETRATE
 WALL PERPENDICULAR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-10-11 Cont ID  
Sent By kstevens Date 2001-10-11 Time 14:22 Rev Time 0.33
Received By kstevens Date 2001-10-11 Time 14:22 Sent To  
Notes
2001-10-11 00:00:00DENIED
 REFERENCE: SPC-94- FLA STATE STATUES
  
 1) WATER HAMMER NOT INSTALLED IN PROPER
 LOCATION. PLEASE INSTALL CLOSE TO FIX-
 TURE PER MANUFACTURE INSTALLATION INSTRU
 CTIONS AND WH-PDI 201.
  
 2) SHEET PO.1 NOT SEALED AS REQUIRED PER
 61G15-23.002(1). PLEASE SEAL PLANS AS
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-09-11 Cont ID  
Sent By kstevens Date 2001-09-06 Time 17:13 Rev Time 0.50
Received By kstevens Date 2001-09-06 Time 17:13 Sent To  
Notes
2001-09-11 00:00:00DENIED
  
 PLANS DO NOT HAVE ORIGINAL SIGNATURE BY
 ARCHITECT, (STAMPED). ALSO PLANS ARE NOT
 SIGNED AND SEALED BY ENGINEER OF RECORD.
  
 ALSO PAGE PO.1 WATER RISER DIAGRAM,
 (MARKED FLOOR DRAIN DETAIL), WATER HAM-
 MER ARRESTOR NOT INSTALLED CORRECTLY.
 PLEASE SHOW INSTALLATION PER MANUFACTURE
 INSTALLATION INSTRUCTION AND PER WH-PDI
 201.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-22 Cont ID  
Sent By jleech Date 2001-07-22 Time 11:26 Rev Time 0.75
Received By jleech Date 2001-07-22 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-31 Cont ID  
Sent By pschmitz Date 2001-05-31 Time 14:18 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-31 00:00:00PLUMBING PLAN RVIEWDENIED
 (1) SHT A2-E,RM 591, BATH RM TO COMPLY
 W/ FACBC 97 SEC 4.1.3(11) COMMON USE
 BATH RM'S AT LEAST ONE LAV & ONE SHOWER
 TO COMLPY WITH CLEAR FLR SPACE AND
 GRAB BARS.
 (2) SHT A2-E RM 590, BREAK RM SINK
 COMPLY W FACBC 97 SEC 4.24.3 KNEE CLEAR-
 ANCE, SEC 4.24.5 CLEAR FLR SPACE.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-06-08 Cont ID  
Sent By lsmith Date 2001-06-08 Time 10:57 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***