Plan Review Details - Permit 01050922
Plan Review Stops For Permit 01050922
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-07-02 Cont ID  
Sent By jwitmer Date 2001-07-02 Time 17:09 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-13 Cont ID  
Sent By dpalmer Date 2001-08-13 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2001-08-13 Time 15:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-11 Cont ID  
Sent By dpalmer Date 2001-06-11 Time 12:21 Rev Time 0.00
Received By dpalmer Date 2001-06-11 Time 12:21 Sent To  
Notes
2001-06-11 00:00:00****************** UNSAT **************
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 PLEASE CLARIFY THE LOADS SHOWN.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT THE AIC RATING WAS
 SUBMITTED FOR PANEL, BUT NOT FOR MAIN.
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 4) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By mcarsill Date 2001-05-22 Time 13:27 Rev Time 0.00
Received By mcarsill Date 2001-05-22 Time 13:27 Sent To  
Notes
2001-05-22 00:00:001) INTERIOR FINISH SHALL BE CLASS A OR
 B IN EXITS.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096 EXT. 8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-14 Cont ID  
Sent By ndenmark Date 2001-08-14 Time 13:35 Rev Time 0.33
Received By ndenmark Date 2001-08-14 Time 13:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-14 Cont ID  
Sent By pkrauss Date 2001-06-14 Time 08:35 Rev Time 0.25
Received By pkrauss Date 2001-06-14 Time 08:34 Sent To  
Notes
2001-06-14 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 PLEASE PROVIDE AIR BALANCE SCHEDULE FOR
 COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-09 Cont ID  
Sent By pschmitz Date 2001-08-09 Time 10:14 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-08-09 00:00:00PLUMBING PLAN REVIEW,PROVISO.
 SHT A3-2 MIN HGTH ON D/F 27"AFF.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-12 Cont ID  
Sent By pschmitz Date 2001-06-12 Time 08:48 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-27 00:00:00PLUMBING PLAN REVIEW "DENIED"
 SPC 94 TAB 407, 1 D/F REQ
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-14 Cont ID  
Sent By lsmith Date 2001-08-14 Time 14:06 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved