Plan Review Details - Permit 01050918
Plan Review Stops For Permit 01050918
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-07-02 Cont ID  
Sent By jwitmer Date 2001-07-02 Time 17:31 Rev Time 0.60
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-13 Cont ID  
Sent By dpalmer Date 2001-08-13 Time 18:37 Rev Time 0.00
Received By dpalmer Date 2001-08-13 Time 18:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-08 Cont ID  
Sent By drunnels Date 2001-06-08 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2001-06-08 Time 16:16 Sent To  
Notes
2001-06-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%.
 PER 215-3/230-42
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING IS SHOWN FOR
 PANEL BUT NOT FOR MAIN DISCONNECT.
  
 3) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By mcarsill Date 2001-05-22 Time 11:23 Rev Time 0.00
Received By mcarsill Date 2001-05-22 Time 11:22 Sent To  
Notes
2001-05-22 00:00:001) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-10 Cont ID  
Sent By pkrauss Date 2001-12-10 Time 15:28 Rev Time 0.35
Received By pkrauss Date 2001-12-10 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-14 Cont ID  
Sent By ndenmark Date 2001-08-14 Time 13:30 Rev Time 0.33
Received By ndenmark Date 2001-08-14 Time 13:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-14 Cont ID  
Sent By pkrauss Date 2001-06-14 Time 07:50 Rev Time 0.25
Received By pkrauss Date 2001-06-14 Time 07:49 Sent To  
Notes
2001-06-14 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 PLEASE PROVIDE AIR BALANCE SCHEDULE FOR
 COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-01 Cont ID  
Sent By lsmith Date 2001-08-14 Time 14:47 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-08-14 00:00:00PROVISO PER PS SEE PLANS FOR PROVISO
 8/14/01 LS
2001-08-09 00:00:00PLUMBING PLAN REVIEW,POVISO.
 SHT B2-2,MIN HGTH OF D/F 27" AFF.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-12 Cont ID  
Sent By pschmitz Date 2001-06-12 Time 08:15 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-27 00:00:00PLUMBING PLAN REVIEW"DENIED'
 SPC 94 TAB 407,1 D/F REQ.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-14 Cont ID  
Sent By lsmith Date 2001-08-14 Time 14:46 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2001-06-08 00:00:00THIS IS A TEST