Plan Review Details - Permit 01050883
Plan Review Stops For Permit 01050883
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-23 Cont ID  
Sent By dpalmer Date 2001-11-28 Time 22:14 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-23 00:00:00PROVISO: STORM SHUTTERS UNDER SEPERATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-06 Cont ID  
Sent By jwitmer Date 2001-06-06 Time 20:14 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-06 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050883
 1329 10TH STREET
 O/B TAYLOR, MARLA/
 GREEN, SCOTTY
 820-0145
 ARTHER PATERSON
 842- 1944
 1)- SBC SSTD 10-97 FOR RESIDENTIAL
 BUILDINGS THAT ARE NOT DESIGNED BY A
 DESIGN PROFESSIONAL (ARCHITECT OR ENGINE
 ER) THE EQUIREMENTS ARE DEEMED TO SATIS-
 FY THE WIND LOAD PROVISIONS OF 1606 IN
 THE 1997 SBC SUBJECT TO THE LIMITATIONS
 IN GENERIC BUILDING GEOMETRY, SITING
 LOCATIONS, MATERIALS AND WIND CLIMATE
 SET FORTH WITHIN.
  
 2)- SSTD 10-97 303.1 MONOLITHIC SLAB
 CONFIGURATION, 20" TALL X 12" WIDE.
  
 3)- SSTD 10-97 TABLE 205 C IS GIVEN FOR
 THE SPACING OFVERTICAL STEEL AND THE
 BOND BEAM REQUIREMENTS.
  
 4)- SSTD 10-97: 205.8 GIVES THE O/B
 3 OPTIONS FOR TYPE OF BEAM.THE THREE
 CHOICES ARE OUTLINED ON PAGES 36/41
 THE MOST COMMONLY USED IN THIS AREA IS
 THE BEAM / LINTAL ASSEMBLY. PAGE 41
 INDICATES A 16" BEAM ALL CELLS ARE GROUT
 ED ABOVE THE LINTEL & THE AMOUNT OF
 STEEL REQUIRED FOR THE PLACEMENT IN THE
 LINTEL.
  
 5)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THERE IS NO DETAIL FOR THE ATTACHMENT OF
 WINDOW BUCKS TO THE BLOCK.
  
 6)- DISCREPANCIES: THE TRUSS PLAN SHOWS
 A DIFFERENT TRUSSED ROOF THAN THE ELEVAT
 IONS, THERE IS ALSO A 3'-0" INDINTATION
 IN THE EXTERIOR WALL WHICH THE TRUSS
 PLAN DOESN'T SHOW CREATING A 5'-0" OVER-
 HANG + VERY HIGH UPLIFT VALUES WHICH
 WILL NEED TO BE ADDRESSED.
  
 7)- THE PLAN DOESN'T INDICATE IF THE
 GABLE END IS TO BE WOOD FRAME OR BLOCK,
 IF THERE IS TO BE A DROPPED GABLE TO
 ALLOW FOR THE 2'-0" OVERHANG?
  
 8)- SBC 1606.4.1/1707.4.1 GLAZED OPENING
 WILL REQUIRE STORM SHUTTERS THAT MEET
 THE LARGE MISSLE IMPACT RESISTANCE TEST-
 ING, SBCCI REPORT OR DADE COUNTY ARE
 ACCEPTABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-28 Cont ID  
Sent By dpalmer Date 2001-11-28 Time 22:14 Rev Time 0.00
Received By dpalmer Date 2001-11-28 Time 22:14 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-07-18 Cont ID  
Sent By dpalmer Date 2001-07-18 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2001-07-18 Time 18:41 Sent To  
Notes
2001-07-18 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ANY
 HANDWRITTENCHANGES ON PLANS ARE TO BE
 SIGNED,DATED BY ARCH OF RECORD. 481.221
  
 2)NOTE: PLEASE NOTE THAT LOAD
 CALCULATIONS DO NOT INCLUDE ALL LOADS
 REQ`D BY NEC ART 220. NO A/C, NO SM APPL
 PLEASE REVISE
  
 3)NOTE: PLEASE NOTE THAT UTILITY ROOM
 OUTLET TO BE GFI PER 210-8.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 11:34 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 11:34 Sent To  
Notes
2001-06-04 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT APPEARS THAT
 THE SERVICE IS BEING UPGRADED?
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS PANEL AT 21POLE/CIRCUIT? PLEASE
 VERIFY THIS AS IT IS NOT A COMMON SIZE.
  
 3)NOTE: PLEASE VERIFY LOAD CALCUALTION\\
 FOR MAIN HOUSE LIGHTING. CALCS SHOW
 4725 WATTS, AND SQ FT ON PAGE 1 OF 5
 SHOWS SQ FT AT 1844, WHICH WOULD MAKE
 IT 5532? PLEASE CLARIFY.
  
 4)NOTE: PLEASESHOW LOCATION OF NEW
 PANEL.
  
 5)NOTE: PLEASE NOTE THAT A SMOKE
 DETECT--OR IS REQ`D OUTSIDE OF MASTER
 BEDROOM
 ALSO/ PER NFPA-72 2-2.1.1.1
  
  
 JUST A NOTE, PLEASE NOTE THAT IF THERE
 IS GOING TO BE ANY CATV AND OR
 TELEPHONE`S IN NEW ADDITION THEN THESE
 NEED TO BE SHOWN ON PLANS.
 PLEASE SHOW LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-18 Cont ID  
Sent By pkrauss Date 2001-07-18 Time 16:40 Rev Time 0.45
Received By pkrauss Date 2001-07-18 Time 16:40 Sent To  
Notes
2001-07-18 00:00:00MECH PERMIT 01050888 - ADDING AIR TO
 MASTER BEDROOM & BATH 3 1/2 TON SYSTEM
 TOTAL SQ FOOTAGE 1844,ENERGY CALCS
 OKAY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-07-17 Cont ID  
Sent By pkrauss Date 2001-07-17 Time 16:37 Rev Time 0.30
Received By pkrauss Date 2001-07-17 Time 16:37 Sent To  
Notes
2001-07-17 00:00:00 
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1. IS SYSTEM AN UPGRADE OF AND OLD
 SYSTEM...IF SO WHAT SIZE WAS OLD
 SYSTEM, SIZE OF DUCT?
  
 2. RETURN AIR WILL BE REQUIRED FROM
 NEW MASTER BEDROOM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By pkrauss Date 2001-06-04 Time 15:03 Rev Time 0.45
Received By pkrauss Date 2001-06-04 Time 14:54 Sent To  
Notes
2001-06-04 00:00:00******************DENIED****************
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 MAKE, MODEL AND SEER/ERR RATING FOR A/C
 EQUIPMENT.
  
 LOCATION OF AIR HANDLER AND CONDENSER
 UNIT.
  
 MATERIAL AND SIZE OF ALL DUCTWORK AS
 WELL AS CFM DISTRIBUTION TO ROOMS.
  
 INDICATE LOCATION OF RETURN AIR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-25 Cont ID  
Sent By kstevens Date 2001-05-25 Time 15:52 Rev Time 0.33
Received By kstevens Date 2001-05-25 Time 15:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2001-06-06 Cont ID  
Sent By jwitmer Date 2001-06-06 Time 20:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-30 Cont ID  
Sent By sgraham Date 2001-05-21 Time 10:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-05-21 00:00:00NEED SITE PLAN WITH ADDITION