Plan Review Details - Permit 01050850
Plan Review Stops For Permit 01050850
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-17 Cont ID  
Sent By jwitmer Date 2001-10-17 Time 10:47 Rev Time 1.00
Received By jwitmer Date 2001-10-17 Time 10:47 Sent To  
Notes
2001-10-17 00:00:00PROVISO: WINDOWS WILL REQUIRE A SEPERATE
 PERMIT.LOW PRESSURES! JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-08 Cont ID  
Sent By jwitmer Date 2001-08-08 Time 09:17 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-08-08 00:00:00BUILDING PLAN REVIW
 PERMIT # 01050850
 4650 GEORGIA AVE
 CLARK CONSTRUCTION SERVICES
 TEL: 848-6061
  
 1)- SBC 104.2.2: ADDITIOAL INFORMATION
 REQUIRED, (2) COPIES OF A CURRENT SURVEY
 2)- SHEET A-1 DISCREPANCY, EAST ELEVA-
 TION VS. FLOOR PLAN, ELEVATION IS BACK-
 WARDS.
 3)- SHEET A-2 SEC.1 & 2 FOUNDATION, SBC
 1804.1.3 THE BOTTOM OF THE FOOTING SHALL
 BE A MINIMUM OF 12" BELOW GRADE.
 4)- 2X12 LEDGER SBC 2304.5.2: REQUIRES
 ALL WOOD AGAINST CONCRETE OR CEMENT TO
 BE PRESSURE TREATED.
 5)- FIRESTOPPING: SHEET A-2/B:
 SBC2305.1.4(1) FIREBLOCKING REQUIRED
 AT THE CEILING LINE
 6)- SBC 1606. DESIGN CRITERIA SEE CERTI-
 FICATION SHEET
 7)- SBC 1606.4.1/ 1707.4.1 ALL GLAZED
 OPENINGS WILL REQUIRE EITHER PRODUCT TES
 TING FOR LARGE MISSLE RESISTANCE OR
 PROVIDE STORM SHUTTER APPROVAL, EITHER
 SBCCI OR DADE COUNTY REPORTS ARE ACCEPT-
 TED.
 8)- SBC 1606.2.6.2:COMPONENTS & CLADDING
 PROVIDE WIND ZONES FOR ALL OPENINGS
 INTERIOR & END ZONES,TABLE 1606.2B &
 TABLE 1606.2C.
 9)- ROOFING : SBC1503.3.2 ROOFING ASSEM-
 BLIES ARE TO COMPLY FOR TESTING IN A
 110MPH WIND ZONE, PROVIDE (2) COPIES
 OF THE PRODUCT APPROVAL REPORT.
 ROOFING: LOCTED IN A FIRE DISTRICT, ONLY
 CLASS A & B MATERIALS ARE TO BE USED.
 10)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, THE PLANS DO NOT SPECIFY WHAT
 USAGE THE MEZANINE IS TO BE USED FOR?
 ASSUMED STORAGE WITH THE LIVE LOAD.
 THE PLANS WILL NEED TO HAVE THE USAGE
 ON THE PLANS TO TAKE THE EXEMPTION TO
 VERTICAL ACCESSIBLITY REQUIRED THROUGH
 THE FL ACCESSIBILTY CODE.
 THE OTHER ISSUE WILL BE IF THE ENTEND-
 ED USEAGE IS TO BE STORAGE:
 AN EXISTING OR NEW BUILDINGS SHALL NOT
 BE OCCUPIED FOR ANY PURPOSE WHICH WILL
 CAUSE THE FLOORS THEREOF TO BE LOADED
 BEYOND THEIR SAFE CAPACITY. THE BUILDING
 OFFICIAL MAY PERMIT OCCUPANCY OF A BUILD
 ING FOR MERCANTILE, COMMERCIAL, OR IN-
 DUSTRIAL PURPOSES, BY A SPECIFIC BUSSIN-
 ESS WHEN HE/SHE IS SATISFIED THAT SUCH
 CAPACITY WILL NOT THEREBY BE EXCEEDED.
 IN EVERY BUILDING OR PART OF A BUILDING
 USED FOR STORAGE, INDUSTRIAL OR
 HAZARDOUS PURPOSES, THE SAFE FLOOR LOADS
 AS REVIEWED BY THE BUILDING OFFICIAL ON
 THE PLAN, SHALL BE MARKED ON THE PLATES
 OF APPROVED DESIGN WHICH SHALL BE
 SUPPLIED & SECURED BY THE OWNER OF THE
 BUILDING IN A CONSPICUOUS PLACE IN EACH
 STORY TO WHICH THEY RELATE. SUCH PLATES
 SHALL NOT BE REMOVED OR DEFACED, IF LOST
 REMOVED OR DEFACED, SHALL BE REPLACED BY
 THE OWNER OF THE BUILDING.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 22:05 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 22:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 21:14 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 21:14 Sent To  
Notes
2001-08-07 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT NO PANEL SCHED-
 -ULES WERE SUBMITTED.
 NO LOAD CALCUALTIONS WERE SUBMITTED FOR
 REVIEW.
  
 2)NOTE: PLEASE NOTE, PLANS NEED TO SHOW
 ALL BRANCH CIRCUIT #`S ON PLANS AND
 CORRELATE WITH SUBMITTED PANEL SCHEDULES
  
 3)NOTE: PLEASE CLARIFY ANY A/C THAT MAY
 BE INSTALLED FOR OFFICE/WAREHOUSE.
 PLEASE NOTE ANY A/C UNITS WILL NEED TO
 BE SHOWN ON PLANS WITH ALL DISCONNECTS
 PER 440-11.
  
 4)NOTE: PLEASE CLARIFY RISER SHOWING
 4-4/0`S GOING TO LIGHTING CONTACTOR???
  
 5)NOTE: PLEASE NOTE RISER DIAGRAM NEEDS
 TO SHOW ALL WIRE/CONDUIT SIZES FROM
 METER-MAIN-PANEL.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-10-02 Cont ID  
Sent By mamini Date 2001-10-02 Time 09:59 Rev Time 3.00
Received By mamini Date 2001-10-02 Time 09:59 Sent To  
Notes
2001-10-02 00:00:00PASSED WITH PROVISOS:
 1. CROSS-CONNECTION AND SANITARY LATERAL
 MUST BE APPROVED BY PUBLIC UTILITIES
 ENGINEERING SERVICES DEP.,659-8040.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-07-19 Cont ID  
Sent By mamini Date 2001-07-19 Time 11:00 Rev Time 4.00
Received By mamini Date 2001-07-19 Time 11:00 Sent To  
Notes
2001-07-19 00:00:00FAILED:
 1. SHEET C-1 DRIVEWAY ENTRANCE
 A. DRIVEWAY SHOULD BE PER CITY STANDARD,
 SEE ATTACHED.
 B. PLEASE FURNISH CONTACT PERSON'S NAME,
 LETTER TO INDICATE THAT DRIVEWAY WILL BE
 CONSTRUCTED BY THE CITY.
 2. SHEET C-3 WATER & SEWER LATERALS
 A. PLEASE FURNISH CONTACT PERSONS'S
 NAME, LETTTER TO INDICATETHAT WATER &
 SEWER WILL BE CONSTRUCTED BY THE CITY.
 3. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT THROUGH OFFICE
 OF CITY ENGINNER. 659-8040
 4. ANY NEW CONNECTIONS TO CITY SERVICES
 WILL REQUIRE A SEPARATE PERMIT THROUGH
 PUBLIC UTILITIES ENGINEERING SERVICES
 DEPARTMENT. 659-8040
  
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-10 Cont ID  
Sent By mcarsill Date 2001-10-10 Time 13:58 Rev Time 0.00
Received By mcarsill Date 2001-10-10 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-08-09 Cont ID  
Sent By pkrauss Date 2001-08-09 Time 13:14 Rev Time 0.25
Received By pkrauss Date 2001-08-09 Time 13:12 Sent To  
Notes
2001-08-09 00:00:00 
  
  
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE SUBMIT PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-01 Cont ID  
Sent By kstevens Date 2001-11-01 Time 18:43 Rev Time 1.00
Received By kstevens Date 2001-11-01 Time 18:43 Sent To  
Notes
2001-11-01 00:00:00PASSED/PROVISO
 REFERENCE: SPC-94 - FACBC-97
  
 EACH BLDG DRAIN SHALL HAVE A 2-WAY C/O
 3' OUTSIDE BLDG.
  
 PLUMBING CONTR. TO LEAVE VALVE AND ADAPT
 FOR IRRIGATION CONTRACTOR.

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-15 Cont ID  
Sent By kstevens Date 2001-10-15 Time 18:35 Rev Time 0.50
Received By kstevens Date 2001-10-15 Time 18:35 Sent To  
Notes
2001-10-15 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SPC-94 TABLE 407 REQUIRED 2 BATHROOMS
 1 MALE AND 1 FEMALE.
  
 2) DOOR TO RESTROOM SHALL NOT OPEN INTO
 CLEAR FLOOR SPACE OF DRINKING FOUNTAIN,
 OR LAV.
  
 3) IRRIGATION ON SEPARATE PERMIT.
 PLUMBING CONTRACTOR TO INSTALL A SEPAR-
 ATE TEE WITH A VALVE AND AN N-36 WATTS
 VACUUM BREAKER TO TIE INTO.
  
 4) TWO WAY CLEAN OUTS ARE REQUIRED FOR
 EACH BLDG DRAIN WHERE IT TIES INTO THE
 BLDG SEWER.
  
 5) SHEET E-1, WATER RISER. AIR CHAMBERS
 ARE "QUICK FIX" WATER HAMMER ARRESTORS
 SHALL BE INSTALLED PER MANUFACTURE'S
 INSTALLATION AND WH-PDI 201. PLACE CLOSE
 TO SOURCE OF SHUTOFF, NOT ON TOP OF DROP
 AS SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 569 8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-29 Cont ID  
Sent By jleech Date 2001-07-29 Time 10:41 Rev Time 1.00
Received By jleech Date 2001-07-29 Time 10:41 Sent To  
Notes
2001-07-29 00:00:00DENIED;
  
 1.SHOW CALCULATIONS FOR EMPLOYEES TO
 COMPLY WITH 94 SPC TABLE 407.SHOW
 LOCATION OF DRINKING FOUNTAIN REQUIRED
 SEE TABLE 407 MISCELLANEOUS FIXTURES.
 2.FLOOR DRAIN IN BATHROOM SHALL HAVE A
 TRAP PRIMER 409.4.1.1.
 3.3" FLOOR DRAIN IN S.E. CORNER OF
 BUILDING.
 A.WILL THERE BE ANY CEMICALS OR
 ANYTHING THAT WILL DAMAGE THE
 DRAINAGE SYSTEM?
 B. FLOOR DRAIN MUST BE VENTED PER.
 TABLE 908.1.
 C.FLOOR DRAIN SHALL BE A DEEP SEAL
 TYPE.
 4.PAGE F-1. PLUMBING LINE DRAWING. FLOOR
 DRAIN NOT VENTED PROPERLY (TOILET
 FLUSHES PAST FLOOR DRAIN). FLOOR DRAIN
 SHOULD COME OFF LAVITORY DRAIN LINE.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 2 Status P Date 2001-09-28 Cont ID  
Sent By sgraham Date 2001-09-28 Time 13:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-10-15 Cont ID  
Sent By jwitmer Date 2001-10-15 Time 15:34 Rev Time 0.00
Received By jwitmer Date 2001-08-13 Time 08:19 Sent To  
Notes
***NONE***