| Plan Review Stops For Permit 01050805 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-05-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-16 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-16 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2001-05-16 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE | | | TO BE A MINIMUM OF AT LEAST THREE FEET | | | FROM AIR CONDITIONER DIFFUSERS. | | | 2) FIRE ALARM EQUIPMENT TO BE CLASS A OR | | | FULLY ADDRESSABLE. | | | 3) FIRE ALARM SYSTEM IS TO BE MONITORED | | | BY A LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | 4) FIRE ALARM SYSTEM TO BE TESTED WITH | | | FIRE RESCUE PERSONNEL AFTER | | | INSTALLATION. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|