Plan Review Details - Permit 01050782
Plan Review Stops For Permit 01050782
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-24 Cont ID  
Sent By dpalmer Date 2001-05-24 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2001-05-24 Time 14:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-20 Cont ID  
Sent By pkrauss Date 2001-07-20 Time 15:36 Rev Time 0.30
Received By pkrauss Date 2001-07-20 Time 15:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-05-19 Cont ID  
Sent By hmoser Date 2001-05-19 Time 11:06 Rev Time 0.33
Received By hmoser Date 2001-05-19 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-12 Cont ID  
Sent By kstevens Date 2001-09-12 Time 18:10 Rev Time 0.50
Received By kstevens Date 2001-09-12 Time 18:10 Sent To  
Notes
2001-09-12 00:00:00DENIED
  
 REVISION DOES NOT MATCH FLOOR PLAN.
 PLEASE SUBMIT A REVISION THAT MATCHES
 INSTALLATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-18 Cont ID  
Sent By kstevens Date 2001-05-18 Time 11:01 Rev Time 0.33
Received By kstevens Date 2001-05-18 Time 11:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-07-09 Cont ID  
Sent By jgomez Date 2001-07-09 Time 18:10 Rev Time 0.50
Received By jgomez Date 2001-07-09 Time 18:09 Sent To  
Notes
2001-07-09 00:00:00TRUSS DRAWINGS SECOND CHECKLIST:
  
 1-ENGINEERED TRUSSES TO BE SIGNED,
 SEALED AND DATED AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
  
 2-UPDATE GENERAL DETAILS. USE ASCE 7-95
 FOR 145 MPH NOT ASCE 7-93 FOR 110 MPH.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-06-08 Cont ID  
Sent By jgomez Date 2001-06-08 Time 16:43 Rev Time 3.00
Received By jgomez Date 2001-06-08 Time 16:43 Sent To  
Notes
2001-06-08 00:00:00APPROVED WITH PROVISO:
  
 1-FLOOD ZONE "A". NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
  
 2-CLARIFY FOOTING SIZE. SEE FOUNDATION
 PLAN.
  
 3-STORM SHUTTERS INFORMATION IS NOT
 COMPLETE. PROVIDE COMPLETE INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT.
  
 4-SEE PLANS FOR ADDITIONAL COMMENTS.
  
 5-TRUSS DRAWINGS:
 A)TRUSS ENGINEER TO HAVE ALL HIS
 INFORMATION ON TRUSS LAYOUT AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES.
 B)TRUSS ENGINEER TO UPDATE ALL GENERAL
 DETAILS AND PROVIDE HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FL. STATUTES.
 C)TRUSS DRAWINGS WERE REVIEWED BY WHO?
 REVIEW STAMP DOESN'T IDENTIFY THE
 ENGINEER OR FIRM WHO DID THE REVIEW.
 D)CLARIFY WHY THERE ARE TWO DIFFERENT
 SIGNATURES ON ENGINEERED TRUSSES IF
 IT'S THE SAME ENGINEER SIGNING THEM.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-17 Cont ID  
Sent By sgraham Date 2001-05-17 Time 14:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***