Plan Review Details - Permit 01050716
Plan Review Stops For Permit 01050716
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-06-15 Cont ID  
Sent By jwitmer Date 2001-06-15 Time 09:34 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By jwitmer Date 2001-06-04 Time 18:25 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050716
 2511 S DIXIE HWY
 MONARD CONST 758-0362
 ARCH ROBERT BELL 683-9133
  
 1)- FL. ACC. CODE 1997 SEC. 416.2.2
 DISPROPORTIONATE COST ALTERATIONS MADE
 TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL
 TO ALTERED AREAS SHALL BE DEEMED DISPRO-
 PORTIONAE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA.
 416.1 (C) IF ALTERATIONS OF SINGLE
 ELEMENTS, WHEN CONSIDERED TOGETHER,
 AMOUNT TO AN ALTERATIOIN OF A ROOM OR
 SPACE IN A BUILDING OR FACILITY, THE
 ENTIRE SPACE SHALL BE MADE ACCESIBLE.
  
 2)- SBC 1204.2 SURROUNDING WALLS &
 FLOORS OF ALL PUBLIC RESTROOMS SHALL BE
 LINED WITH NONABSORBANT MATERIALS TO A
 HEIGTH OF 4'-0" .
  
 3)- RAMP LOCATED IN FRONT OF THE WOMENS
 RESTROOM WHAT IS THE CHANGE INGRADE?
 WILL HANDRAILS BE REQUIRED?
  
 4)- SBC 104.2.2 ADD. INFORMATION. USEAGE
 OF ROOMS 9/10 FOR FUTURE FLOOR DRAINS?
  
 5)- SHEET #1 NOTE INDICATES NEW WINDOWS,
 DETAILS FOR WINDOW BUCK ATTACHMENT SBC
 1606.2.6.2 AND PRODUCT APPROVAL FOR SUCH
 GLAZED OPENINGS TEST PRESSURES AT 1 1/2
 THE DESIGN PRESSURE, ALSO LARGE MISSLE
 IMPACT TESTING OR STORM SHUTTERS WITH
 APPROVED LARGE MISSLE IMPACT TESTING.
 SBCCI REPORT OR DADE COUNTY PRODUCT
 APPROVAL TESTING REPORTS ARE ACCEPTABLE.
  
 6)- SSBC TABLE 803.3 REQUIRES A MINIMUM
 FINISH SCHEDULE BASED ON OCCUPANCY,
 FOR SPRINKLERED AND NONSPRINKLERED
 OCCUPANCIES.
  
 7)- SBC 104.2.2 ADD INFORMATION REQUIRED
 DETAILS 1/3, 2/3 INDICATE A RESTRAUNT IN
 ONE OF THE ADJACENT TENANT SPACES, WHAT
 IS THE SQ. FOOTAGE OF SPACE? 100 OCC.
 LOAD REQUIRES A 2 HR WALL WHICH IS INDIC
 ATED ON THE PLAN, WHERE AS YOU INDICATE
 1 HR SEPERATION REQUIRED? GIVE GYPSUM OR
 UL RATING OF WALLS.
  
 8)- FIRE CAUKING PENETRATIONS SBC 705.1
 (2) SHOW MAN SPEC FOR VERTICAL APPLICA-
 TION.
  
 BUILDING PLAN REVIEW.
 JIM WITMER
 (561) 659- 8096 EX 8412

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-11-06 Cont ID  
Sent By dpalmer Date 2001-11-06 Time 20:05 Rev Time 0.00
Received By dpalmer Date 2001-11-06 Time 20:04 Sent To  
Notes
2001-11-06 00:00:00************** UNSAT *******************
  
  
 1)NOTE: PLEASE NOTE THAT PER FS/FAC
 61G15-23.002. THE 8 1/2 X 11`S NEED TO
 HAVE ENGINEERS TITLE BLOCK ON SHEETS.
  
 2)NOTE: PLEASE NOTE MISSING AIC RATINGS
 FOR PANELS, P1,P2,AND P.
  
 3)NOTE: PLEASE NOTE MISSING PANEL
 INFORMATION FOR P2.
  
 4)NOTE: PLEASE NOTE MISSING CWP ON
 GROUNDING ELECTRODE SYSTEM. 250-50.
 PLEASE NOTE THAT THE ELECTRICAL
 INSPECTOR MENTIONED GAS LINE BEING
 ON SYSTEM? PLEASE CLARFIY.
  
 5)NOTE: PLEASE NOTE HANDWRITTEN CHANGES
 ON PLANS NEED TO BE PRINTED.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-06-22 Cont ID  
Sent By jleahy Date 2001-06-22 Time 07:49 Rev Time 1.30
Received By jleahy Date 2001-06-22 Time 07:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-14 Cont ID  
Sent By dpalmer Date 2001-06-14 Time 19:09 Rev Time 0.00
Received By dpalmer Date 2001-06-14 Time 19:09 Sent To  
Notes
2001-06-14 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NOTES FROM
 FIRST REVIEW WERE NOT ADDRESSED.
 PLEASE SUBMIT THE INFORMATION FOR REVIEW
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-06 Cont ID  
Sent By dpalmer Date 2001-06-06 Time 18:16 Rev Time 0.00
Received By dpalmer Date 2001-06-06 Time 18:16 Sent To  
Notes
2001-06-06 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT LOAD
 CALCULATIONS NEED TO BE COMPLETED.
 PLEASE SHOW
 ALL CONTINUOUS LOADS AT 125% 230-42 AND
 215-3.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE SUB-
 -MITTED FOR PANELS BUT NOT FOR MAIN
 DISCONNECTS. ARE MAIN DISC`S FUSED?
 WHICH NOTE 16 WOULD PERTAIN TO?
 PLEASE CLARIFY.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION
 ON CONDUIT TYPE BETWEEN MAIN AND PANELS.
 DOES NOTE 10 PERTIAN TO CONDUIT FROM
 MAIN TO PANEL? PLEASE CLARIFY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-25 Cont ID  
Sent By lsmith Date 2001-06-25 Time 10:50 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-06-25 00:00:00PER MEC 6/12/01

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-16 Cont ID  
Sent By mcarsill Date 2001-05-16 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2001-05-16 Time 13:48 Sent To  
Notes
2001-05-16 00:00:001) GAS INSTALLATIONS TO COMPLY WITH
 NFPA 54, THE NATIONAL FUEL GAS CODE.
 2) IT APPEARS THAT ADDITIONAL EMERGENCY
 LIGHTING FIXTURES ARE NEEDED THROUGHOUT
 THE SPACE.
 3) PLEASE PROVIDE OCCUPANT LOAD COUNT.
 4) DUCT SMOKE DETECTORS REQUIRED IN ALL
 AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN
 ACTIVATED, THE AIR HANDLING EQUIPMENT IS
 TO SHUT DOWN AND PROVIDE AN AUDIBLE AND
 VISUAL ALERT.
 5) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 6) NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS.
 7) PLEASE INDICATE HOW DRYER VENTS
 TERMINATE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-10-03 Cont ID  
Sent By pkrauss Date 2001-10-03 Time 13:02 Rev Time 0.35
Received By pkrauss Date 2001-10-03 Time 13:02 Sent To  
Notes
2001-10-03 00:00:00MECH REV 01070016

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-02 Cont ID  
Sent By pkrauss Date 2001-07-02 Time 10:10 Rev Time 0.45
Received By pkrauss Date 2001-07-02 Time 10:09 Sent To  
Notes
2001-07-02 00:00:00MECHANICAL PERMIT 01070016.
  
 NOTE ON PLAN MINIMUM 18" FROM ROOF
 SURFACE TO THE BOTTOM OF SUPPORT RAIL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-06-18 Cont ID  
Sent By pkrauss Date 2001-06-18 Time 16:32 Rev Time 0.30
Received By pkrauss Date 2001-06-18 Time 16:31 Sent To  
Notes
2001-06-18 00:00:00*******************DENIED***************
  
  
 AS PER LETTER FROM ROBERT L. BELL
 ARCHITECT, O.A. CALCULATIONS & AIR
 BALANCE SCHEDULE TO BE SUBMITTED WITH
 PERMIT MECHANICAL PERMIT APPLICATION.
 PLEASE PROVIDE ABOVE INFORMATION WITH
 PLANS AND APPLICATION.
  
 PLEASE PROVIDE INFORMATION/DETAIL ON THE
 6" X 6" PATE SUPPORTS FOR THE CONDENSER
 UNITS AS WELL AS DETAIL ON TIE DOWN
 FOR CONDENSER UNITS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By pkrauss Date 2001-06-07 Time 15:13 Rev Time 0.45
Received By pkrauss Date 2001-06-07 Time 14:18 Sent To  
Notes
2001-06-07 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.O.A. CALCULATIONS PER ASHRAE 62-89
 AND AIR BALANCE SCHEDULE AS PER 1997
 SMC 501.2.
  
 2.NO A/C DROP IN PRIVATE RESTROOM HOW
 IS AIR MAKE UP BEING SUPPLIED.
  
 3.PLAN SHEET 5 & 6 INDICATE A WALL
 BETWEEN LOBBY & WAITING ROOM, PLEASE
 CORRECT.
  
 4.A/C FOR ROOM 20 IS MISSING DUCT AND
 GRILL SIZE.
  
 5.PLEASE PROVIDE MANUFACTURER CUT
 SHEET FOR CONDENSER UNIT STANDS.
 (18" MIN. FROM ROOF SURFACE TO
 BOTTOM OF SUPPORT RAIL.)
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-06-25 Cont ID  
Sent By lsmith Date 2001-06-25 Time 10:52 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2001-06-25 00:00:00PLUMBING PLAN REVIEW RE-SUB OK PES.
 PER PS 6/25/01 LS

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-06-23 Cont ID  
Sent By pschmitz Date 2001-06-23 Time 09:06 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-23 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT R1 MEN,WOMENS REST RM'S,COMPLY
 WITH FACBC-97 SEC 4.24.5 URINAL 30"X 48"
 CLEAR FLR SPACE. MAX HGTH 17" SEC 4.18.2
 AN UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH 4.2.3 SHALL BE PROVIDED WITHIN AN
 ACCESSIBLE BATH RM. THE SPACE FOR A
 WHEEL CHAIR TO MAKE A 180-DEGREE TURN.
 (2) SHT 2 RM 25,PRIVATE OFFICE,COMPLY/W
 FACBC,SEC 4.1.3(11) SHALL BE ADAPTABLE.
 SHOWER STALL, SEC 4.21 SIZE, CLEARANCE,
 SEAT, SHOWER UNIT,CURB,CONTROLS.
 (3) SHT R1,DETAIL OF CURRENT ADA H/C
 STALL ENCLOSED.
 END OF COMMENTS, PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-29 Cont ID  
Sent By pschmitz Date 2001-05-29 Time 11:19 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-29 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) SHT-1 NUMBER ROOMS,AS PER FINISH
 SCHEDULE ON SHT-2.
 (2) SHT 1 EXISTING REST RM'S MEN'S
 WOMEN'S,COMPLY W/FACBC 97 SEC 4.16(2)
 ALTERATIONS TO AN AREA CONTAINING A PRIM
 ARY FUNCTION, THE PATH OF TRAVEL AND THE
 REST RM'S SERVING THE ALTERED AREA,
 ARE READLY ACCESSIBLE AND USEABLE BY
 INDIVIDUALS WITH DISABILITIES.
 SHOW CALCULATIONS FOR A BEAUTY SHOP.FOR
 MINIMUM FACILITIES,SPC 94 SEC 407.1.3
 (3) ALL REST RM FACILITIES IN COMMON
 AREA TO COMPLY W/FACBC 97 SEC 4.1.3.(11)
 (4) BREAK RM SINK TO COMPLY W/FACBC
 4.24.2,4.24.5 HEIGTH,KNEE CLEARANCE.
 (5) SHT 8 SEE GAS PERMIT APPLICATION
 REQUIRMENTS ATTACHED, ADDRESS EA ITEM.
 (6) SHT-8 FUTURE F/D TO HAVE A DEEP
 SEAL TRAP OR TRAP PRIMER SPC 97 409.1.1
 (7) SHT-8 2" CROSS NOT PERMITED ON A
 WASHING MAHINE WASTE,SEC 409.12.3
 (8) SHT-8 WATER SUPPLY, NO MORE 2 PLBG
 FIXTURES SHALL BE SUPPLIED W/ 1/2" COLD
 WATER SUPPLY, NO MORE THAN 4 PLBG.
 FIXTURES SHALL BE SUPPLIED W/ 1/2" HOT
 WATER SUPPLY. SEC 607.7 PBC AMEND SPC 94
 (9) SHT-8 DWV ISOMETRIC,SHOW ALL PIPE
 SIZES.SPC 94 SEC 104.3
 (10) WATER SUPPLY,EA TENANT SPACE TO
 HAVE A SEPERATE BACK FLOW PREVENTER.
 SPC 94 SEC 606.
 (11) SHT-8 PROVIDE CUT SHTS ON WASHING
 MACHINES,TO SHOW THAT A LINT SEPERATOR
 IS NOT REQUIRED.SPC 94 SEC 1004.10.1
 END OF COMMENTSPAUL SCHMITZ