| Plan Review Stops For Permit 01050716 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-06-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-06-15 |
Time |
09:34 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-06-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-06-04 |
Time |
18:25 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01050716 | | | 2511 S DIXIE HWY | | | MONARD CONST 758-0362 | | | ARCH ROBERT BELL 683-9133 | | | | | | 1)- FL. ACC. CODE 1997 SEC. 416.2.2 | | | DISPROPORTIONATE COST ALTERATIONS MADE | | | TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL | | | TO ALTERED AREAS SHALL BE DEEMED DISPRO- | | | PORTIONAE TO THE OVERALL ALTERATION WHEN | | | THE COST EXCEEDS 20% OF THE COST OF THE | | | ALTERATION TO THE PRIMARY FUNCTION AREA. | | | 416.1 (C) IF ALTERATIONS OF SINGLE | | | ELEMENTS, WHEN CONSIDERED TOGETHER, | | | AMOUNT TO AN ALTERATIOIN OF A ROOM OR | | | SPACE IN A BUILDING OR FACILITY, THE | | | ENTIRE SPACE SHALL BE MADE ACCESIBLE. | | | | | | 2)- SBC 1204.2 SURROUNDING WALLS & | | | FLOORS OF ALL PUBLIC RESTROOMS SHALL BE | | | LINED WITH NONABSORBANT MATERIALS TO A | | | HEIGTH OF 4'-0" . | | | | | | 3)- RAMP LOCATED IN FRONT OF THE WOMENS | | | RESTROOM WHAT IS THE CHANGE INGRADE? | | | WILL HANDRAILS BE REQUIRED? | | | | | | 4)- SBC 104.2.2 ADD. INFORMATION. USEAGE | | | OF ROOMS 9/10 FOR FUTURE FLOOR DRAINS? | | | | | | 5)- SHEET #1 NOTE INDICATES NEW WINDOWS, | | | DETAILS FOR WINDOW BUCK ATTACHMENT SBC | | | 1606.2.6.2 AND PRODUCT APPROVAL FOR SUCH | | | GLAZED OPENINGS TEST PRESSURES AT 1 1/2 | | | THE DESIGN PRESSURE, ALSO LARGE MISSLE | | | IMPACT TESTING OR STORM SHUTTERS WITH | | | APPROVED LARGE MISSLE IMPACT TESTING. | | | SBCCI REPORT OR DADE COUNTY PRODUCT | | | APPROVAL TESTING REPORTS ARE ACCEPTABLE. | | | | | | 6)- SSBC TABLE 803.3 REQUIRES A MINIMUM | | | FINISH SCHEDULE BASED ON OCCUPANCY, | | | FOR SPRINKLERED AND NONSPRINKLERED | | | OCCUPANCIES. | | | | | | 7)- SBC 104.2.2 ADD INFORMATION REQUIRED | | | DETAILS 1/3, 2/3 INDICATE A RESTRAUNT IN | | | ONE OF THE ADJACENT TENANT SPACES, WHAT | | | IS THE SQ. FOOTAGE OF SPACE? 100 OCC. | | | LOAD REQUIRES A 2 HR WALL WHICH IS INDIC | | | ATED ON THE PLAN, WHERE AS YOU INDICATE | | | 1 HR SEPERATION REQUIRED? GIVE GYPSUM OR | | | UL RATING OF WALLS. | | | | | | 8)- FIRE CAUKING PENETRATIONS SBC 705.1 | | | (2) SHOW MAN SPEC FOR VERTICAL APPLICA- | | | TION. | | | | | | BUILDING PLAN REVIEW. | | | JIM WITMER | | | (561) 659- 8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2001-11-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-06 |
Time |
20:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-06 |
Time |
20:04 |
Sent To |
|
|
| Notes |
| 2001-11-06 00:00:00 | ************** UNSAT ******************* | | | | | | | | | 1)NOTE: PLEASE NOTE THAT PER FS/FAC | | | 61G15-23.002. THE 8 1/2 X 11`S NEED TO | | | HAVE ENGINEERS TITLE BLOCK ON SHEETS. | | | | | | 2)NOTE: PLEASE NOTE MISSING AIC RATINGS | | | FOR PANELS, P1,P2,AND P. | | | | | | 3)NOTE: PLEASE NOTE MISSING PANEL | | | INFORMATION FOR P2. | | | | | | 4)NOTE: PLEASE NOTE MISSING CWP ON | | | GROUNDING ELECTRODE SYSTEM. 250-50. | | | PLEASE NOTE THAT THE ELECTRICAL | | | INSPECTOR MENTIONED GAS LINE BEING | | | ON SYSTEM? PLEASE CLARFIY. | | | | | | 5)NOTE: PLEASE NOTE HANDWRITTEN CHANGES | | | ON PLANS NEED TO BE PRINTED. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-07 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-07 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-06-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-06-22 |
Time |
07:49 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
2001-06-22 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-06-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-14 |
Time |
19:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-14 |
Time |
19:09 |
Sent To |
|
|
| Notes |
| 2001-06-14 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT NOTES FROM | | | FIRST REVIEW WERE NOT ADDRESSED. | | | PLEASE SUBMIT THE INFORMATION FOR REVIEW | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-06 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-06 |
Time |
18:16 |
Sent To |
|
|
| Notes |
| 2001-06-06 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT LOAD | | | CALCULATIONS NEED TO BE COMPLETED. | | | PLEASE SHOW | | | ALL CONTINUOUS LOADS AT 125% 230-42 AND | | | 215-3. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS WERE SUB- | | | -MITTED FOR PANELS BUT NOT FOR MAIN | | | DISCONNECTS. ARE MAIN DISC`S FUSED? | | | WHICH NOTE 16 WOULD PERTAIN TO? | | | PLEASE CLARIFY. | | | | | | 3)NOTE: PLEASE PROVIDE CLARIFICATION | | | ON CONDUIT TYPE BETWEEN MAIN AND PANELS. | | | DOES NOTE 10 PERTIAN TO CONDUIT FROM | | | MAIN TO PANEL? PLEASE CLARIFY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-06-25 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-25 |
Time |
10:50 |
Rev Time |
0.25 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-25 00:00:00 | PER MEC 6/12/01 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-05-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-16 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-16 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2001-05-16 00:00:00 | 1) GAS INSTALLATIONS TO COMPLY WITH | | | NFPA 54, THE NATIONAL FUEL GAS CODE. | | | 2) IT APPEARS THAT ADDITIONAL EMERGENCY | | | LIGHTING FIXTURES ARE NEEDED THROUGHOUT | | | THE SPACE. | | | 3) PLEASE PROVIDE OCCUPANT LOAD COUNT. | | | 4) DUCT SMOKE DETECTORS REQUIRED IN ALL | | | AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN | | | ACTIVATED, THE AIR HANDLING EQUIPMENT IS | | | TO SHUT DOWN AND PROVIDE AN AUDIBLE AND | | | VISUAL ALERT. | | | 5) BUILDING ADDRESS REQUIRED PER CITY | | | CODE REQUIREMENTS. | | | 6) NO INTERIOR FINISH INFORMATION | | | PROVIDED WITH PLANS. | | | 7) PLEASE INDICATE HOW DRYER VENTS | | | TERMINATE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-03 |
Time |
13:02 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-03 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2001-10-03 00:00:00 | MECH REV 01070016 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-07-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-02 |
Time |
10:10 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-07-02 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2001-07-02 00:00:00 | MECHANICAL PERMIT 01070016. | | | | | | NOTE ON PLAN MINIMUM 18" FROM ROOF | | | SURFACE TO THE BOTTOM OF SUPPORT RAIL. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-06-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-18 |
Time |
16:32 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-06-18 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2001-06-18 00:00:00 | *******************DENIED*************** | | | | | | | | | AS PER LETTER FROM ROBERT L. BELL | | | ARCHITECT, O.A. CALCULATIONS & AIR | | | BALANCE SCHEDULE TO BE SUBMITTED WITH | | | PERMIT MECHANICAL PERMIT APPLICATION. | | | PLEASE PROVIDE ABOVE INFORMATION WITH | | | PLANS AND APPLICATION. | | | | | | PLEASE PROVIDE INFORMATION/DETAIL ON THE | | | 6" X 6" PATE SUPPORTS FOR THE CONDENSER | | | UNITS AS WELL AS DETAIL ON TIE DOWN | | | FOR CONDENSER UNITS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-06-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-07 |
Time |
15:13 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-06-07 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2001-06-07 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.O.A. CALCULATIONS PER ASHRAE 62-89 | | | AND AIR BALANCE SCHEDULE AS PER 1997 | | | SMC 501.2. | | | | | | 2.NO A/C DROP IN PRIVATE RESTROOM HOW | | | IS AIR MAKE UP BEING SUPPLIED. | | | | | | 3.PLAN SHEET 5 & 6 INDICATE A WALL | | | BETWEEN LOBBY & WAITING ROOM, PLEASE | | | CORRECT. | | | | | | 4.A/C FOR ROOM 20 IS MISSING DUCT AND | | | GRILL SIZE. | | | | | | 5.PLEASE PROVIDE MANUFACTURER CUT | | | SHEET FOR CONDENSER UNIT STANDS. | | | (18" MIN. FROM ROOF SURFACE TO | | | BOTTOM OF SUPPORT RAIL.) | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-06-25 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-25 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-25 00:00:00 | PLUMBING PLAN REVIEW RE-SUB OK PES. | | | PER PS 6/25/01 LS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-06-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-23 |
Time |
09:06 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-23 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1) SHT R1 MEN,WOMENS REST RM'S,COMPLY | | | WITH FACBC-97 SEC 4.24.5 URINAL 30"X 48" | | | CLEAR FLR SPACE. MAX HGTH 17" SEC 4.18.2 | | | AN UNOBSTRUCTED TURNING SPACE COMPLYING | | | WITH 4.2.3 SHALL BE PROVIDED WITHIN AN | | | ACCESSIBLE BATH RM. THE SPACE FOR A | | | WHEEL CHAIR TO MAKE A 180-DEGREE TURN. | | | (2) SHT 2 RM 25,PRIVATE OFFICE,COMPLY/W | | | FACBC,SEC 4.1.3(11) SHALL BE ADAPTABLE. | | | SHOWER STALL, SEC 4.21 SIZE, CLEARANCE, | | | SEAT, SHOWER UNIT,CURB,CONTROLS. | | | (3) SHT R1,DETAIL OF CURRENT ADA H/C | | | STALL ENCLOSED. | | | END OF COMMENTS, PAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-29 |
Time |
11:19 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-29 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) SHT-1 NUMBER ROOMS,AS PER FINISH | | | SCHEDULE ON SHT-2. | | | (2) SHT 1 EXISTING REST RM'S MEN'S | | | WOMEN'S,COMPLY W/FACBC 97 SEC 4.16(2) | | | ALTERATIONS TO AN AREA CONTAINING A PRIM | | | ARY FUNCTION, THE PATH OF TRAVEL AND THE | | | REST RM'S SERVING THE ALTERED AREA, | | | ARE READLY ACCESSIBLE AND USEABLE BY | | | INDIVIDUALS WITH DISABILITIES. | | | SHOW CALCULATIONS FOR A BEAUTY SHOP.FOR | | | MINIMUM FACILITIES,SPC 94 SEC 407.1.3 | | | (3) ALL REST RM FACILITIES IN COMMON | | | AREA TO COMPLY W/FACBC 97 SEC 4.1.3.(11) | | | (4) BREAK RM SINK TO COMPLY W/FACBC | | | 4.24.2,4.24.5 HEIGTH,KNEE CLEARANCE. | | | (5) SHT 8 SEE GAS PERMIT APPLICATION | | | REQUIRMENTS ATTACHED, ADDRESS EA ITEM. | | | (6) SHT-8 FUTURE F/D TO HAVE A DEEP | | | SEAL TRAP OR TRAP PRIMER SPC 97 409.1.1 | | | (7) SHT-8 2" CROSS NOT PERMITED ON A | | | WASHING MAHINE WASTE,SEC 409.12.3 | | | (8) SHT-8 WATER SUPPLY, NO MORE 2 PLBG | | | FIXTURES SHALL BE SUPPLIED W/ 1/2" COLD | | | WATER SUPPLY, NO MORE THAN 4 PLBG. | | | FIXTURES SHALL BE SUPPLIED W/ 1/2" HOT | | | WATER SUPPLY. SEC 607.7 PBC AMEND SPC 94 | | | (9) SHT-8 DWV ISOMETRIC,SHOW ALL PIPE | | | SIZES.SPC 94 SEC 104.3 | | | (10) WATER SUPPLY,EA TENANT SPACE TO | | | HAVE A SEPERATE BACK FLOW PREVENTER. | | | SPC 94 SEC 606. | | | (11) SHT-8 PROVIDE CUT SHTS ON WASHING | | | MACHINES,TO SHOW THAT A LINT SEPERATOR | | | IS NOT REQUIRED.SPC 94 SEC 1004.10.1 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|