Plan Review Details - Permit 01050650
Plan Review Stops For Permit 01050650
Review Stop P PLUMBING
Rev No 3 Status P Date 2001-06-06 Cont ID  
Sent By pschmitz Date 2001-06-06 Time 10:08 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-06 00:00:00PLUMBING PLAN REVIEW"PROVISO"
 SHT P5 PIPE SIZES ADDED OFF HEADER.PES

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-02 Cont ID  
Sent By jleech Date 2001-06-02 Time 10:58 Rev Time 1.00
Received By jleech Date 2001-06-02 Time 10:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-22 Cont ID  
Sent By kstevens Date 2001-05-22 Time 11:49 Rev Time 1.25
Received By kstevens Date 2001-05-22 Time 11:48 Sent To  
Notes
2001-05-22 00:00:00REVEIW NOTES: FAILED
  
 1) SHOW DISTANCE TO MOST REMOTE OUTLET.
  
 2) CALCULATIONS FOR COMBUSTION AIR.
  
 3) TYPE, LOCATION, SIZE AND TERMINATION
 PT. OF GAS VENTS.
  
 4) SUBMIT MORE INFORMATION/ISOMETRIC
 DRAWING ON AIR INTAKE AND EXHAUST PIPING
 FOR WATER HEATERS. (SEE SHT. P-3)
  
 5) IS PIPE (3") GOING TO BE WELD PIPE
 OR SCREW PIPE?
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377