| Plan Review Stops For Permit 01050589 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-05-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-14 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-14 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2001-05-14 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE | | | TO BE A MINIMUM OF THREE FEET FROM | | | AIR CONDITONER DIFFUSERS. | | | 2) FIRE ALARM SYSTEM TO BE CLASS A OR | | | FULLY ADDRESSABLE. | | | 3) FIRE ALARM AND SPRINKLER SYSTEM ARE | | | TO BE MONITORED BY A UL LISTED CENTRAL | | | STATION APPROVED BY THE FIRE RESCUE | | | DEPARTMENT. | | | 4) FIRE ALARM SYSTEM WHEN INSTALLED IS | | | TO BE TESTED WITH FIRE RESCUE PERSONNEL. | | | 5) END OF LINE DEVICES SHOWN ON PLANS. | | | PLEASE REMOVE THESE DEVICES. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|