Plan Review Details - Permit 01050589
Plan Review Stops For Permit 01050589
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-14 Cont ID  
Sent By mcarsill Date 2001-05-14 Time 09:57 Rev Time 0.00
Received By mcarsill Date 2001-05-14 Time 09:57 Sent To  
Notes
2001-05-14 00:00:001) SMOKE DETECTORS WHEN INSTALLED ARE
 TO BE A MINIMUM OF THREE FEET FROM
 AIR CONDITONER DIFFUSERS.
 2) FIRE ALARM SYSTEM TO BE CLASS A OR
 FULLY ADDRESSABLE.
 3) FIRE ALARM AND SPRINKLER SYSTEM ARE
 TO BE MONITORED BY A UL LISTED CENTRAL
 STATION APPROVED BY THE FIRE RESCUE
 DEPARTMENT.
 4) FIRE ALARM SYSTEM WHEN INSTALLED IS
 TO BE TESTED WITH FIRE RESCUE PERSONNEL.
 5) END OF LINE DEVICES SHOWN ON PLANS.
 PLEASE REMOVE THESE DEVICES.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910