Plan Review Details - Permit 01050533
Plan Review Stops For Permit 01050533
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-02 Cont ID  
Sent By jwitmer Date 2001-07-02 Time 14:57 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-02 00:00:00PROVISO:PROVIDE THE INTRRIOR FINISH
 REQUIRED BASED ON THE OCCUPANCY, SEE
 STANDARD BUILDING CODE TABLE 803.3
 MINIMUM INTERIOR FINISH CLASSIFICATION.
 TO THIS OFFICE BEFORE THE FIRST INSPEC-
 TION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By jwitmer Date 2001-06-07 Time 11:48 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050533
 1572 PALM BEACH LAKES
 BAYS 1& 2
 842-5137
  
 1)- NOTE EXTERIOR AWNINGS REQUIRE A
 SEPERATE PERMIT & FEES.
  
 2)- PUBLIC RESTROOMS, SBC 1204.2.
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBENT
 MATERIALS TO A HEIGHT OF 4'-0".
  
 3)- SBC 104.2.2: ADDITIONAL INFORMATION
 SHEET A-4 DETAILS 1, 2 & 5 THE DESIGN
 PROFESSIONAL TO GIVE INFORMATION AS TO
 ATTACH THE SOFFIT TO THE STRUCTURE ABOVE
 THE SPACING OF STUDSALSO?
  
 4)- SEC. X/A2 STEEL JOIST PENETRATION /
 1 HOUR RATED WALL, THE GIVEN UL LISTING
 W-L-1074 ISN'T LISTED IN THE 2001
 UL LISTINGS, PLEASE PROVIDE CUT SHEET.
  
 5)- SBC 803.3.1 INTERIOR FINISH REQUIRE-
 MENTS BASED ON OCCUPANCY.
 TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATIONS.
  
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-08 Cont ID  
Sent By dpalmer Date 2001-08-08 Time 07:32 Rev Time 0.00
Received By dpalmer Date 2001-08-08 Time 07:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 19:37 Rev Time 0.00
Received By dpalmer Date 2001-05-15 Time 19:37 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-06-04 Cont ID  
Sent By lsmith Date 2001-06-04 Time 11:17 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-31 Cont ID  
Sent By mcarsill Date 2001-07-31 Time 13:43 Rev Time 0.00
Received By mcarsill Date 2001-07-31 Time 13:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-26 Cont ID  
Sent By mcarsill Date 2001-06-26 Time 13:23 Rev Time 0.00
Received By mcarsill Date 2001-06-26 Time 13:23 Sent To  
Notes
2001-06-26 00:00:00ON JUNE 26, 2001, THIS WRITER CALLED
 DANNY DISOA. HE ADVISED THAT BETWEEN
 4 TO 5 PERSONS WOULD TAKE TO OPERATE
 THE BUSINESS. IT WAS AGREED THAT A
 SINGLE MEANS OF EGRESS WAS OKAY SINCE
 THE FIRE CODE ALLOWS IT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-16 Cont ID  
Sent By mcarsill Date 2001-05-14 Time 15:04 Rev Time 0.00
Received By mcarsill Date 2001-05-14 Time 15:04 Sent To  
Notes
2001-05-14 00:00:001) PLEASE PROVIDE THIS OFFICE A LETTER
 INDICATING THAT NO COOKING THAT
 PRODUCES SMOKE OR GREASE LADEN VAPORS
 WILL BE CONDUCTED AT THE SITE. ANY
 COOKING THAT PRODUCES SMOKE OR GREASE
 LADEN VAPORS MUST BE PROTECTED BY A
 HOOD,DUCT AND EXTINGUISHING SYSTEM.
 SEPARATE PLANS AND PERMITS ARE REQUIRED.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 3) PLEASE EXPLAIN EXITING ARRANGEMENT
 TO THIS OFFICE.
 4) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 5) DUCT SMOKE DETECTOR WHEN ACTIVATED
 IS TO SHUT DOWN AIR HANDLING EQUIPMENT
 AND PROVIDE VISUAL NOTIFICATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-08-09 Cont ID  
Sent By pkrauss Date 2001-08-09 Time 16:01 Rev Time 0.35
Received By pkrauss Date 2001-08-09 Time 15:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-29 Cont ID  
Sent By pkrauss Date 2001-06-29 Time 07:25 Rev Time 0.30
Received By pkrauss Date 2001-06-29 Time 06:58 Sent To  
Notes
2001-06-29 00:00:00 
  
 MECHANICAL PERMIT # 01050572.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-06 Cont ID  
Sent By pkrauss Date 2001-06-06 Time 15:30 Rev Time 0.45
Received By pkrauss Date 2001-06-06 Time 12:39 Sent To  
Notes
2001-06-06 00:00:00********************DENIED**************
  
 AIR BALANCE SCHEDULE ON DRAWING M-1
 REFLECTS TWO AC#3.
  
 AIR DISTRIBUTION ON PLAN - 6 DROPS AT
 465 CFM IS 2790 CFM, BOTH AIR BALANCE
 SCHEDULE AND ROOF TOP A.C. UNIT
 SCHEDULE REFLECT 2400 CFM. PLEASE
 CORRELATE.
  
 NOTE:18" MINIMUM FROM ROOF SURFACE TO
 BOTTOM OF SUPPORT RAIL.
  
 ADDITIONAL MECHANICAL PERMITS AND PLANS
 REQUIRED FOR WALK-IN COOLERS, KITCHEN
 HOODS/EXHAUST AND FIRE SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-08-18 Cont ID  
Sent By jleech Date 2001-08-18 Time 06:10 Rev Time 0.75
Received By jleech Date 2001-08-18 Time 06:10 Sent To  
Notes
2001-08-18 00:00:00REVISION OK

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-08-06 Cont ID  
Sent By jleech Date 2001-08-06 Time 18:47 Rev Time 1.50
Received By jleech Date 2001-08-06 Time 18:47 Sent To  
Notes
2001-08-06 00:00:00REVISION DENIED;
  
 1.ADD NOTES THAT WERE DELETED FROM
 REVISION 1 DATED 6/12/01.
 A.NOTE 1 LOCAL CODE IS STANDARD
 PLUMBING CODE NOT SOUTH FLORIDA.
 B.ADD NOTE 13 DRAINAGE PIPE TO BE
 USED.
 C.ALSO ADD NOTE ABOUT THE HANDICAP
 LAVS.
 2.REVISED WATER RISER DIAGRAM IS ALSO
 REQUIRED BEFORE FINAL PLUMBING
 INSPECTION. (WATER PIPING WAS NOT
 INSTALLED PER APPROVED PLAN.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-01 Cont ID  
Sent By pschmitz Date 2001-06-01 Time 13:29 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-01 00:00:00PLUMBING PLAN REVIEW PROVISO:
 (1) NOTES ON SHT'S A-2 P-1,P-2 AS PER
 ARCHETICT MR EDWARD GHEEZI,305-596-3800
 (2) SHT P-1 SPC 94 CURRENT CODE.
 (3) SHT P-2 3 COMP SINK WASTE NO RUNNING
 TRAPS, INDIVIDUAL TRAPS FOR EA COMPART-
 MENT.SPC 94 SEC 1003.
 (4) SHT P-1 MATERIAL FOR DWV SYSTEM
 SCH 40 PVC PIPE.ABOVE,BELOW GRADE.
 (5) SHT P-2 AIR CHAMBERS DELETED,SCHOCK
 ARRESTOR LOCATION BY ENG. OF RECORD.
 (6) NO GAS APPLIANCES SHOWN ON SHT K-1.
 END OF CIMMENTSPAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-18 Cont ID  
Sent By jleech Date 2001-05-18 Time 14:44 Rev Time 1.50
Received By jleech Date 2001-05-18 Time 14:44 Sent To  
Notes
2001-05-18 00:00:00DENIED;
  
 HANDICAP LAVATORIES CLEARANCES SHALL
 COMPLY WITH 97 FACBC FIG. 32. CLEAR
 FLOOR SPACE IS 15" FROM WALL TO CENTER
 OF LAV.
  
 PAGE P-1 PLUMBING NOTES. PLUMBING CODE
 USED IS THE 94 STANDARD PLUMBING CODE.
  
 SPECIFY MATERIAL TO BE USED FOR DRAINAGE
 PIPE.
  
 3 COMPARTMENT SINK D192 SHALL BE
 INDIRECTLY WASTED PER.804.1.
  
 WATER HEATER TO BE READILY ACCESSIBLE.
 LOCATE ON FLOOR OR INSTALL A PERMINATE
 FIXED SHIPS LADDER.
  
 SPECIFY TYPE AND SIZE OF SHOCK ARRESTERS
 TO BE USED AND SHOW LOCATION ON WATER
 RISER DIAGRAM.
  
 GAS DRAWINGS REQUIRED FOR GAS EQUIPMENT
 TO BE USED. FOLLOW ATTACHED, GAS PERMIT
 APPLICATION REQUIREMENTS SHEET.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-06-04 Cont ID  
Sent By lsmith Date 2001-06-04 Time 11:17 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***