| Plan Review Stops For Permit 01050459 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-06-05 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-11 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-11 |
Time |
06:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-05 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-05 |
Time |
18:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-06 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-06 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-06-06 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-06 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-15 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-15 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | 1) INTERIOR FINISH TO BE AT LEAST CLASS | | | "C" ON WALLS AND CEILINGS. | | | 2) FIRE ALARM NOTES INDICATES THAT FIRE | | | ALARM CIRCUITS TO BE CLASS B, STYLE C. | | | ONLY CLASS A, STYLE D CIRCUITS WILL | | | BE PERMITTED. | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER REMODEL. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM EQUIPMENT INSTALLATION. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-30 |
Time |
11:54 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-07-30 |
Time |
11:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-29 |
Time |
07:39 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-06-29 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2001-06-29 00:00:00 | REVISION - ADDED 2 HEAT PUMPS THAT LOOK | | | TO BE SERVING AN AREA LABLED | | | "NO WORK IN THIS AREA". | | | CALL ARCHITECT DANNY BROWN. | | | | | | TALKED WITH DANNY BROWN, TWO NEW HEAT | | | PUMPS SERVE COMMON AREA.DUCT IS BEING | | | RUN UP TO FIRE DAMPERS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-06-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-04 |
Time |
11:24 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-06-04 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2001-06-04 00:00:00 | *******************PROVISO************** | | | | | | AHU(S) 2, 3 AND 4 HAVE MORE CFM'S BEING | | | DISTRIBUTED (DWG M2.1) THAN IS INDICATED | | | ON THE HEAT PUMP SCHEDULE (DWG M0.1). | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-07-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-07-29 |
Time |
14:32 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-29 00:00:00 | PLUMBING PLAN REVIEW,PROVISO | | | SHT P0-1PLACEMENT OF WATER HAMMER | | | ARRESTORS AS PER MFG, INSTRUCTIONS. | | | PDI-WH102,NOT AT HIGH POINT. | | | QUESTIONS PAUL SCHMITZ 561-659-8096 | | | X 8233. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-07-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-07-09 |
Time |
11:53 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
2001-07-09 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2001-07-09 00:00:00 | DENIED | | | | | | 1) PAGE A-1, STILL DO NOT HAVE CLEAR | | | FLOOR SPACE FOR LOUNGE SINK. 30" X 48" | | | REQUIRED. IF FRONT APPROACH, 30" X 19" | | | CLEAR UNDER COUNTER REQUIRED. SHOW | | | DETAIL. | | | | | | 2) PAGE A-1, MEN & WOMENS RESTROOMS, | | | 5' TURNING RADIUS REQUIRED OUTSIDE OF | | | STALL. DOORS CAN NOT OPEN INTO CLEAR | | | FLOOR SPACE. | | | | | | 3) PAGE PO-1 DOMESTIC WATER RISER DIA- | | | GRAM, WATER HAMMER ARRESTORS MUST BE IN- | | | STALLED PER MANUFACTURE INSTALLATION IN- | | | STRUCTIONS. PLEASE SEE ATTACHED SHEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-07-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-09 |
Time |
12:15 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-09 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) SHT A1 COMPLY W/FACBC 97,4.1.6(1)(B) | | | ACCESSIBLE BUILDING ALTERATIONS. | | | (2) SHT A4 REST RM 121 & 122,DETAIL#5,10 | | | H/C,W/C,DIMENSION OFF WALL 19",FACBC 97 | | | COMLPY WITH FIG 28, 18" OFF THE WALL. | | | (3) SHT A4,RM 121 LAVATORIES, MIRRORS, | | | COMPLY W/FACBC 97 SEC 4.19. | | | URINALS COMPLY W/FACBC SEC 4.18.2 & .3 | | | HGTH TO LIP OF URI 17" TO FF. CLEAR FLR | | | SPACE,30" X 48". | | | (4) SHT P0.1,DOMESTIC WATER ISOMETRIC & | | | NOTES 13,18, REFERENCE, AIR CHAMBERS. | | | SHOW A DETAIL OF AN APPROVED AIR CHAMBER | | | AND HOW IT WILL BE ACCESSIBLE,RECHARGE- | | | ABLE. SPC 94 SEC 607.8.3 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-06-06 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-06 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|