Plan Review Details - Permit 01050406
Plan Review Stops For Permit 01050406
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-06-21 Cont ID  
Sent By hpiskura Date 2001-06-21 Time 15:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-25 Cont ID  
Sent By hpiskura Date 2001-05-25 Time 10:22 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-05-25 00:00:00PLEASE PROVIDE A RECENT SURVEY SO THAT
 THE DISTANCE FROM THE BUILDING TO THE
 PROPERTY LINE MAY BE DETERMINED ON THE
 SOUTH SIDE.THIS IS NECESSARY TO
 INSURE COMPLIANCE WITH SBC TABLE 600
 FOR THE PERCENTAGE OF WALL OPENINGS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 11:34 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 11:34 Sent To  
Notes
2001-10-30 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT ORIGINAL PLANS
 ARE DONE BY A DIFFERENT ENGINEER OF
 RECORD. PLEASE NOTE THAT ORIG PLANS SHOW
 A DIFFERENT RISER SET UP.
 PLEASE NOTE THAT THESE PLANS MAY BE
 SUBMITTED BUT MUST BE UNDER A NEW
 PERMIT APPLICATION OR SUBMIT A REVISION
 BY THE ENGINEER OF RECORD FOR JOB OR
 RELEASE THE ENGINEER OF RECORD AND
 SUBMIT ALL NEW ELECTRICAL PLANS??
  
  
 PLEASE SUBMIT FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2001-05-15 Time 19:15 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-06-28 Cont ID  
Sent By lsmith Date 2001-06-28 Time 10:39 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-10 Cont ID  
Sent By mcarsill Date 2001-05-10 Time 09:47 Rev Time 0.00
Received By mcarsill Date 2001-05-10 Time 09:47 Sent To  
Notes
2001-05-10 00:00:001) INTERIOR FINISH ON WALLS AND CEILINGS
 TO BE CLASS A OR B IN EXITS. OTHER
 AREAS CAN BE A,B, OR C.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-11-08 Cont ID  
Sent By pkrauss Date 2001-11-08 Time 13:23 Rev Time 0.40
Received By pkrauss Date 2001-11-08 Time 13:13 Sent To  
Notes
2001-11-08 00:00:00 
 CHANGED SUPPLY DUCTS FROM SIDEWALL TO
 FLEX INTO A DROP.NOTE ON PLAN ROOMS
 WITH GREATER THAN 300 CFM REQUIRE A R/A.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-26 Cont ID  
Sent By pkrauss Date 2001-06-26 Time 08:01 Rev Time 0.35
Received By pkrauss Date 2001-06-26 Time 08:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By ndenmark Date 2001-06-04 Time 10:03 Rev Time 0.33
Received By ndenmark Date 2001-06-04 Time 10:03 Sent To  
Notes
2001-06-04 00:00:00DENIED
 PROVIDE INFORMATION ON ROOF ATTACHMENT
 FOR RTU'S
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR BOTH UNITS
 RTU 2 APPEARS TO SERVE PROCEDURE ROOM.
 PROVIDE RETURN AIR PATH TO UNIT FROM
 THIS SPACE ( ALL AREAS WITH 300 CFM OR
 MORE REQUIRE RETURN AIR TO UNIT.
 PROVIDE INFORMATION ON BATHROOM EXHAUST
 AS REQUIRED BY CODE
 PROVIDE OUTSIDE AIR SCHEDULE SHOWING
 COMPLIANCE WITH ASHRAE 62-89
 HOW DOES RTU 2 S/A DUCT ATTACH TO S/A
 DUCT IN SPACE?
 DUCT WITH 2 PIECE 90'S WILL REQUIRE
 TURNING VANES OR MAKE AS 3 PIECE 90'S.
  
 QUESTIONS CALL
 NANCY DENMARK @ 561 659-8096 EXT. 8221

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-28 Cont ID  
Sent By pschmitz Date 2001-06-28 Time 11:17 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-28 00:00:00PLUMBING PLAN REVIEW RE-SUB OK PES.
 SEE NOTE #17 RE: AIR CHAMBERS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-12 Cont ID  
Sent By jleech Date 2001-05-12 Time 10:06 Rev Time 1.75
Received By pschmitz Date 2001-05-12 Time 10:06 Sent To  
Notes
2001-05-12 00:00:00DENIED;
  
 1.DRINK FOUNTAIN SHALL BE INSTALLED, A
 WATER COOLER IS NOT A PLUMBING FIXTURE
  
 2.DRINKING FOUNTAIN TOO COMPLY WITH 97
 FACBC SEC. 4.13(10) AND 4.15 (D.F. TO
 ACCESSIBLE FOR PEOPLE IN WHEEL CHAIRS
 AND PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 3.HANDICAP BATH NOT TO FACBC SPECIFICA-
 TIONS. BATHROOM NOT LARGE ENOUGH.
 INLARGE AND SHOW TURNING RADIUS ON
 PLANS.
  
 4.LOUNG SINK TO COMPLY WITH FACBC 4.24.1
 THRU 4.24.7.
  
 5.AIR CHAMBERS TO COMPLY WITH 94 SPC
 607.8.2 AND 607.8.3. ENGINEERED WATER
 HAMMER ARRESTERS SHOULD BE SPECIFIED
 BY ENGINEER OF RECORD.
  
 6.PLUMBING FIXTURE SCHEDULE SHOWS
 HANDICAP FIXTURES IN STAFF BATHROOM.
 STAFF BATHROOM DOES NOT MEET FACBC
 SPECIFCATIONS.
  
 7.WATER RISER. ONLY 2 FIXTURES PERMITED
 ON 1/2" COLD WATER LINE. 97 COUNTY-
 WIDE AMENDMENTS 607.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-06-28 Cont ID  
Sent By lsmith Date 2001-06-28 Time 10:39 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***