Plan Review Details - Permit 01050336
Plan Review Stops For Permit 01050336
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-05-21 Cont ID  
Sent By hpiskura Date 2001-05-21 Time 15:24 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-06 Cont ID  
Sent By dpalmer Date 2001-07-06 Time 16:05 Rev Time 0.00
Received By dpalmer Date 2001-07-06 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 20:30 Rev Time 0.00
Received By dpalmer Date 2001-05-15 Time 20:29 Sent To  
Notes
2001-05-15 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PER LOCAL
 AMENDMENTS, COUNTY-WIDE AND CITY-WIDE
 ART: 210-50. OUTLETS IN STORAGE TO BE
 INSTALLED EVERY 20' OFUNENCUMBERED
 WALL SPACE AND EVERY 12' FOR OFFICE
 AREAS.
  
 2)NOTE: PLEASE CLARIFY LIGHTING ON
 STAORAGE ROOM #108. EXSITING? NEW?
 BATTERY ROOM?
  
 3)NOTE: PLEASE SHOW ALL BRANCH CIRCUITS
 ON PLANS AND CORRELATE WITH PANEL
 SCHEDULES.(MDP)
  
 4)NOTE: PLEASE NOTE THAT PANEL SCHEDULES
 HAVE AREA AT THE BOTTOM OF PANEL SHOWING
 ADDITIONAL 25% FOR CONTINUOUS LOADS,
 BUT NO ADDITIONAL LOAD IS SHOWN FOR
 CONTINUOUS LOADS. ALSO LARGEST MOTOR
 LOAD. 215-3 AND 230-42
  
  
 PLEASE NOTE:GOING OVER NOTE FROM THE
 ADVISORYSHOWN AT THE BOTTOM OF
 PANELS B1 AND B2.GOING OVER LOAD
 CALCULATIONS SHOWN NOW, SOME SERIOUS
 THOUGHT SHOULD BE NOTED TO OWNER(S)
 ABOUT A SERVICE CHANGE BEFORE NEW LOADS
 ARE ADDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-18 Cont ID  
Sent By pkrauss Date 2001-07-18 Time 12:16 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-18 Cont ID  
Sent By rturnque Date 2001-07-18 Time 10:29 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-07-09 Cont ID  
Sent By mcarsill Date 2001-07-09 Time 13:18 Rev Time 0.00
Received By mcarsill Date 2001-07-09 Time 13:18 Sent To  
Notes
2001-07-09 00:00:001) PREVIOUS PLAN REVIEW COMMENTS NOT
 ADDRESSED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-10 Cont ID  
Sent By mcarsill Date 2001-05-10 Time 10:05 Rev Time 0.00
Received By mcarsill Date 2001-05-10 Time 10:05 Sent To  
Notes
2001-05-10 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF THE NEW FUEL
 TANK. PLEASE BE ADVISED THAT THE SITE
 APPEARS TO BE LOCATED IN THE CITY FIRE
 LIMITS. CERTAIN RESTRICTIONS APPLY
 TO FUEL AND FLAMMABLE GAS STORAGE IN
 THE FIRE LIMITS.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM REMODEL.
 3) PLEASE CLEARLY INDICATE LOCATIONS
 OF ALL EMERGENCY LIGHTS AND ILLUMINATED
 EXIT SIGNS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-18 Cont ID  
Sent By pkrauss Date 2001-07-18 Time 12:12 Rev Time 0.45
Received By pkrauss Date 2001-07-18 Time 12:11 Sent To  
Notes
2001-07-18 00:00:00PROVISO ON PLAN ADDITIONAL PERMIT
 REQUIRED FOR FUEL...PLEASE SUBMIT
 MANUFACTURER DETAILS / ENGINEER DRAWING
 FOR FUEL TANK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-23 Cont ID  
Sent By pkrauss Date 2001-05-23 Time 12:19 Rev Time 0.45
Received By pkrauss Date 2001-05-23 Time 11:42 Sent To  
Notes
2001-05-23 00:00:00*******************DENIED***************
  
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 (ASHRAE 62-89) AND AIR BALANCE
 SCHEDULE AS PER 1997 SMC 501.2.
  
 2.DRAWING M2.1 INDICATES EXISTING R/A
 GRILLES TO REMAIN, ARE THEY BEING
 USED FOR SUPPLY AS INDICATED ON
 M2.2?ALSO, IS THIS WALL FIRE
 RATED?
  
 3.PLEASE PROVIDE INFORMATION ON THE
 EXISTING EXHAUST FAN IN THE BATTERY
 ROOM.HOW MANY CFM'S WILL IT BE
 REMOVING AND DOES IT RUN CON-
 TINUOUSLY?
  
 4.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 5.PLEASE ADDRESS HOW THE REMAINING
 "STORAGE" AREA IS BEING VENTILATED.
  
 NOTE:ADDITIONAL PLANS AND PERMIT
 REQUIRED FOR FUEL OIL TANK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-27 Cont ID  
Sent By pschmitz Date 2001-05-27 Time 19:54 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-27 00:00:00PLUMBING PLAN REVIEW
 ADD OFFICES TO EX SPACE W/ EX REST RM'S.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-18 Cont ID  
Sent By pkrauss Date 2001-07-18 Time 12:16 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***