Plan Review Details - Permit 01050326
Plan Review Stops For Permit 01050326
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-03 Cont ID  
Sent By lmartine Date 2001-06-03 Time 11:43 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-06-03 00:00:00NOT ENOUGH DETAILS FOR THE RETAINING
 WALLS, NO STRUCTURAL PAGES PROVIDED.
  
 L.MARTINEZ

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-23 Cont ID  
Sent By dpalmer Date 2001-05-23 Time 12:36 Rev Time 0.00
Received By dpalmer Date 2001-05-23 Time 12:36 Sent To  
Notes
2001-05-23 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NOT ENOUGH
 INFORMATION FOR COMPLETE ELECTRICAL
 REVIEW OF SITE WAS SUBMITTED. PLEASE
 NOTE THAT ONLY SHEET-E0.104 WAS SUBMITT-
 ED.
  
 PLEASE SUBMIT MORE INFORMATION FOR REVIE
 W OF ELECTRICAL SITE LIGHTING, FEEDS,
 ETC. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status A Date 2001-05-21 Cont ID  
Sent By dlauderm Date 2001-05-21 Time 08:06 Rev Time 5.00
Received By dlauderm Date 2001-05-21 Time 08:06 Sent To  
Notes
2001-05-21 00:00:00APPROVED WITH PROVISOS:
 SEE 6 PAGES OF NOTES ATTACHED TO THE
 PLAN.
 ADDITIONAL NOTES:
 1. RAMP AT N STREET AND LAKE (EAST SIDE)
 MUST BE DESIGNED TO TIE INTO CITY'S
 TOWNHOUSE WALL.CONTACT TIM HALL WITH
 CRAVEN AND THOMPSON AT 954-739-6400.
 THE CITY AND IT'S ENGINEERS NEED TO SEE
 SEE THE DEMINSIONAL DRAWINGS FOR THIS
 AREA.FOR THE CITY CONTACT DAVID
 CATES.
 2. THE CITY NEEDS TO REVIEW AND APPROVE
 THE MATERIALS OF COLORS AND TEXTURES OF
 THE RETAINING ALONG HOWARD PARK AS A
 DEMINSIONAL DRAWING FROM HOWARD PARK
 ELEVATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-15 Cont ID  
Sent By mcarsill Date 2001-05-15 Time 09:55 Rev Time 0.00
Received By mcarsill Date 2001-05-15 Time 09:55 Sent To  
Notes
2001-05-15 00:00:001) FIRE HYDRANTS LOCATED ALONG THE WEST
 SIDE OF THE CONVENTION CENTER ALONG THE
 DELIVERY AREA MUST NOT BE BLOCKED BY
 THE CMU RETAINING WALL. THE FIRE
 HYDRANTS MUST BE LOCATED ON THE EAST
 SIDE OF THE RETAINING WALL. THE
 RETAINING WALL MUST NOT INTERFERE WITH
 THE OPERATION OF ANY FIRE HYDRANT
 LOCATED ALONG THE WEST SIDE OF THE
 CONVENTION CENTER.
 2) UNDEGROUND FIRE MAINS TO BE LISTED
 FOR FIRE PROTECTION SERVICE AND COMPLY
 WITH NFPA 24, THE STANDARD FOR FIRE
 SERVICE MAINS AND THEIR APPURTENANCES.
 ALL UNDERGOUND FIRE MAINS ARE TO BE
 PRESSURE TESTED AT 200 LBS. FOR TWO
 HOURS PER NFPA 24.
 3) WET FIRE HYDRANTS ARE TO BE PROVIDED
 PRIOR TO, DURING AND AFTER CONSTRUCTION
 OF THE CONVENTION CENTER.
 4) THE CHAIN LINK GATES ARE TO PROVIDE
 AT LEAST TWENTY FEET IN CLEAR WIDTH FOR
 FIRE RESCUE ACCESS.
 5) ADDITIONAL FIRE HYDRANTS ARE REQUIRED
 ALONG FLORIDA AVENUE. PRESENTLY THE
 PLANS ONLY SHOW ONE HYDRANT ON THE NORTH
 SIDE NEAR OKEECHOBEE BOULEVARD. THESE
 ADDITONAL FIRE HYDRANTS ARE TO BE
 STAGGERED ON THE EAST AND WEST SIDES OF
 THE PROPOSED FIVE LANE ROADWAY.
 6) TAMPER SWITCHES,CHAINS AND LOCKS WILL
 BE REQUIRED FOR BACKFLOW DEVICES USED
 FOR FIRE MAINS.
 7) ALL EXTERIOR STAIRS TO BE SLIP
 RESISTANT.
 8) STAIRS TO COMPLY WITH NEW STAIR
 REQUIREMENTS FROM NFPA 101, THE LIFE
 SAFETY CODE.
 9) PIPE BOLLARDS ARE TO NOT TO INTERFERE
 WITH THE SAFE USAGE OF ANY STAIRS.
 10) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-06-03 Cont ID  
Sent By lmartine Date 2001-06-03 Time 11:46 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-24 Cont ID  
Sent By pschmitz Date 2001-05-24 Time 15:46 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-24 00:00:00PLUMBING PLAN REVIEWPROVISO
 SEE COMMENTS BY DEAN LAUDERMILK DATED
 5-15-01 FOR SITE WORK, EXCEPT IRRIGATION
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233
 PLUMBING PLAN REVIEW PROVISO
 SEE COMMENTS BY DEAN LAUDERMILK DATED
 5-15-01 FOR SITE WORK,EXCEPT IRRIGATION
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***