| 2001-05-15 00:00:00 | 1) FIRE HYDRANTS LOCATED ALONG THE WEST |
| | SIDE OF THE CONVENTION CENTER ALONG THE |
| | DELIVERY AREA MUST NOT BE BLOCKED BY |
| | THE CMU RETAINING WALL. THE FIRE |
| | HYDRANTS MUST BE LOCATED ON THE EAST |
| | SIDE OF THE RETAINING WALL. THE |
| | RETAINING WALL MUST NOT INTERFERE WITH |
| | THE OPERATION OF ANY FIRE HYDRANT |
| | LOCATED ALONG THE WEST SIDE OF THE |
| | CONVENTION CENTER. |
| | 2) UNDEGROUND FIRE MAINS TO BE LISTED |
| | FOR FIRE PROTECTION SERVICE AND COMPLY |
| | WITH NFPA 24, THE STANDARD FOR FIRE |
| | SERVICE MAINS AND THEIR APPURTENANCES. |
| | ALL UNDERGOUND FIRE MAINS ARE TO BE |
| | PRESSURE TESTED AT 200 LBS. FOR TWO |
| | HOURS PER NFPA 24. |
| | 3) WET FIRE HYDRANTS ARE TO BE PROVIDED |
| | PRIOR TO, DURING AND AFTER CONSTRUCTION |
| | OF THE CONVENTION CENTER. |
| | 4) THE CHAIN LINK GATES ARE TO PROVIDE |
| | AT LEAST TWENTY FEET IN CLEAR WIDTH FOR |
| | FIRE RESCUE ACCESS. |
| | 5) ADDITIONAL FIRE HYDRANTS ARE REQUIRED |
| | ALONG FLORIDA AVENUE. PRESENTLY THE |
| | PLANS ONLY SHOW ONE HYDRANT ON THE NORTH |
| | SIDE NEAR OKEECHOBEE BOULEVARD. THESE |
| | ADDITONAL FIRE HYDRANTS ARE TO BE |
| | STAGGERED ON THE EAST AND WEST SIDES OF |
| | THE PROPOSED FIVE LANE ROADWAY. |
| | 6) TAMPER SWITCHES,CHAINS AND LOCKS WILL |
| | BE REQUIRED FOR BACKFLOW DEVICES USED |
| | FOR FIRE MAINS. |
| | 7) ALL EXTERIOR STAIRS TO BE SLIP |
| | RESISTANT. |
| | 8) STAIRS TO COMPLY WITH NEW STAIR |
| | REQUIREMENTS FROM NFPA 101, THE LIFE |
| | SAFETY CODE. |
| | 9) PIPE BOLLARDS ARE TO NOT TO INTERFERE |
| | WITH THE SAFE USAGE OF ANY STAIRS. |
| | 10) HANDRAILS AND GUARDS TO COMPLY WITH |
| | NFPA 101, THE LIFE SAFETY CODE. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |