| 2001-05-14 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT PLANS THAT |
| | CONTAIN TITLE BL0CK, MUST BE BE SIGNED |
| | AND SEALED BY THAT ARCH/ENGINEER OF |
| | RECORD. PER F.A.C. 471.025 AND 481.221. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | NEW SERVICE SHOWN? |
| | |
| | 3) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | EXISTING? |
| | |
| | 4) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE NOTE THAT PLANS ARE SHOWING ALL |
| | EXISTING ROOMS WITH NEW ELECTRIC? IF |
| | EXISTING EGRESS LIGHTING IS PRESENT |
| | PLEASE CLARIFY. NOTE FRONT DOOR W/ TWO |
| | SWITCHES SHOWN CONTROLLING ?? |
| | PLEASE NOTE NEW FAMILY ROOM W/ SWITCH GO |
| | ING TO NEW FAN, DOES THIS HAVE A LIGHT |
| | KIT?? |
| | |
| | 5)NOTE: PLEASE NOTE THAT MECHANICAL |
| | PLANS AND ELECTRICAL PLANS DO NOT CORREL |
| | ATE. PLEASE NOTE THAT TWO A/C SYSTEMS |
| | ARE SHOWN ON A/C PLANS AND ONLY ONE |
| | ON ELECTRICAL LOAD CALCULATION AND PLANS |
| | PLEASE SHOW SECOND SYSTEM AHU AND CU. |
| | PLEASE SHOW DISCONNECTS PER 440-11. AND |
| | ANY REQ`D OUTLETS PER 210-63 AND 309.1. |
| | |
| | 6)NOTE: PLEASE NOTE THAT THE ELECTRICAL |
| | LEGEND SHOWS LOW VOLTAGE ITEMS. THIS IS |
| | JUST A NOTE, BUT IF THERE IS GOING TO BE |
| | TELEPHONE OR CATV IN HOUSE THEN IT NEEDS |
| | TO BE ON PLANS FOR NEW ADDITION. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLANREVIEW |
| | 561-659-8096 EXT 8372 |