Plan Review Details - Permit 01050299
Plan Review Stops For Permit 01050299
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-08-21 Cont ID  
Sent By jwitmer Date 2001-08-21 Time 18:39 Rev Time 0.50
Received By jwitmer Date 2001-08-21 Time 18:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-13 Cont ID  
Sent By hpiskura Date 2001-07-13 Time 12:39 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By hpiskura Date 2001-05-22 Time 14:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-19 Cont ID  
Sent By dpalmer Date 2001-06-19 Time 07:40 Rev Time 0.00
Received By dpalmer Date 2001-06-19 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-16 Cont ID  
Sent By dpalmer Date 2001-05-16 Time 16:26 Rev Time 0.00
Received By dpalmer Date 2001-05-16 Time 16:26 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-06-27 Cont ID  
Sent By lsmith Date 2001-06-27 Time 15:44 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-08-14 Cont ID  
Sent By mcarsill Date 2001-08-14 Time 13:38 Rev Time 0.00
Received By mcarsill Date 2001-08-14 Time 13:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2001-06-27 Cont ID  
Sent By lsmith Date 2001-06-27 Time 15:45 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-09 Cont ID  
Sent By mcarsill Date 2001-05-09 Time 14:12 Rev Time 0.00
Received By mcarsill Date 2001-05-09 Time 14:12 Sent To  
Notes
2001-05-09 00:00:001) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER SYSTEM.
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM SYSTEM EQUIPMENT
 INSTALLATION.
 3) INTERIOR FINISH ON WALLS AND CEILINGS
 MUST BE AT LEAST A CLASS C FLAME
 SPREAD.
 4) PORTABLE FIRE EXTINGUISHERS TYPE 2A
 10BC, WITH CURRENT SERVICE TAGS ARE
 TO BE PROVIDED.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-10-12 Cont ID  
Sent By pkrauss Date 2001-10-12 Time 12:45 Rev Time 0.35
Received By pkrauss Date 2001-10-12 Time 12:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-08-13 Cont ID  
Sent By pkrauss Date 2001-08-09 Time 12:10 Rev Time 0.40
Received By pkrauss Date 2001-08-09 Time 12:08 Sent To  
Notes
2001-08-09 00:00:00*****************PROVISO****************
  
  
  
 ACCESS DOOR IN LASER ROOM SHOULD HAVE A
 FIRE RATING THAT OF THE CEILING IN THAT
 SPACE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-08-08 Cont ID  
Sent By pkrauss Date 2001-08-08 Time 07:27 Rev Time 0.40
Received By pkrauss Date 2001-08-08 Time 06:55 Sent To  
Notes
2001-08-08 00:00:00*******************PROVISO**************
  
  
 SHOULD CEILING HAVE A 1 HR OR GREATER
 RATING, ACCESS DOOR SHALL CARRY THE
 SAME RATING.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-20 Cont ID  
Sent By pkrauss Date 2001-06-13 Time 13:49 Rev Time 0.45
Received By pkrauss Date 2001-06-13 Time 12:53 Sent To  
Notes
2001-06-13 00:00:00******************PROVISO***************
  
  
  
 NOTE:AC-6 SHALL COMPLY WITH 1997 SMC
 304.4.1, ACCESS FOR SERVICE &
 REPLACEMENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-29 Cont ID  
Sent By ndenmark Date 2001-05-29 Time 09:24 Rev Time 0.50
Received By ndenmark Date 2001-05-29 Time 09:24 Sent To  
Notes
2001-05-29 00:00:00**************DENIED*******************
  
 1. VERIFY EXISTANCE OF BASE BLDG.
 EXHAUST RISER
 2. A/C 4 AND 5 CFM ON PLAN DO NOT
 MATCH SCHEDULE FOR CFM
 3. SCHEDULE DOES NOT SHOW A/C 6 SHOWN ON
 PLAN
 4. LEIBERT (A/C 6?) SHOWS DUCTS TO
 CONDENSER OF A/C . FL. ENERGY CODE
 407.1.ABC D.3.3 DOES NOT PERMIT THE
 CONDENSING COILS OF ONE UNIT TO BE IN
 THE COOL AIR STREAM OF ANOTHER A/C UNIT.
 5. PROVIDE OUTSIDE AIR PER ASHRAE 62-89
 6. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 7. NO COMBUSTIBLES ALLOWED IN R/A PLENUM
 AREA INCLUDING PVC.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-08-20 Cont ID  
Sent By kstevens Date 2001-08-20 Time 15:15 Rev Time 1.00
Received By kstevens Date 2001-08-20 Time 15:15 Sent To  
Notes
2001-08-20 00:00:00PROVISO
  
 BACKFLOW SHALL BE READILY ACCESSABLE,
 FINAL APPROVAL BY FIELD INSPECTOR.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-08-01 Cont ID  
Sent By kstevens Date 2001-08-01 Time 13:04 Rev Time 0.50
Received By kstevens Date 2001-08-01 Time 13:03 Sent To  
Notes
2001-08-01 00:00:00PROVISO...
  
 1) REVISION REQUIRED FOR DETAIL ON
 LOCATION OF BACKFLOW. BACKFLOW MUST BE
 READLY ACCESSABLE.
  
 2) APPROVAL SHALL BE BY FIELD INSPECTORS
 APPROVAL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-07-22 Cont ID  
Sent By jleech Date 2001-07-22 Time 07:39 Rev Time 1.00
Received By jleech Date 2001-07-22 Time 07:39 Sent To  
Notes
2001-07-22 00:00:00REVISION DENIED;
  
 BACKFLOW PREVENTER MUST BE READILY
 ACCESSIBLE FOR TESTING AND REPAIR NO
 HIGHER THAN 4'.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-20 Cont ID  
Sent By kstevens Date 2001-06-18 Time 16:29 Rev Time 0.50
Received By kstevens Date 2001-06-18 Time 16:29 Sent To  
Notes
2001-06-18 00:00:00REVIEW NOTES:PASSED
  
 PROVISO:
  
 1)BACKFLOW REQUIRED TO BE MAXIMUM OF
 4' ABOVE FINISHED FLOOR FOR MAINTENANCE.
  
 2) BACKFLOW ALSO REQUIRES A FLOOR SINK
 TO DRAIN INTO, WITH A TRAP-PRIMER TO
 KEEP TRAP SEAL.
  
 3) PROVIDE DETAIL FOR ABOVE INSTALLATION
 THAT IS SIGNED AND SEALED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-27 Cont ID  
Sent By pschmitz Date 2001-05-27 Time 21:48 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-27 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) SHT A9.1 DOOR SWING IN RM'S #523 &
 #535,TO COMPLY W/FACBC 4.23.2 SWING DOOR
 OUT OF TURNING RADIUS OF WHEEL CHAIR.
 (2) SHT A9.2 DR'S OFFICE REST RM # 518
 TO BE ADAPTABLE, SHOW BACKING FOR GRAB
 BARS,DIMENSIONS OF FIXTURES OFF WALL.
 FACBC 97 SEC 4.1.3(11).
 (3) SHT A9.1 BREAK RM SINK RM #522,SHOW
 CLEAR FLOOR SPACE, COUNTER HGTH 34"FF.
 FACBC 97 SEC 4.24.2,4.24.5
 (4) SHT M-1 RM#525,NOTE 7,HUMIDIFIER
 WTER SUPPLY,TO BE PROTECTED WITH A BACK
 FLOW PREVENTER."RPZV".
 SPC 94 SEC 601.6
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096 X8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-06-27 Cont ID  
Sent By lsmith Date 2001-06-27 Time 15:44 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***