| Plan Review Stops For Permit 01050299 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-21 |
Time |
18:39 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2001-08-21 |
Time |
18:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-13 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-13 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-05-22 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-06-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-19 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-19 |
Time |
07:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-05-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-16 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-16 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-06-27 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-27 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-08-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-14 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-14 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
N |
Date |
2001-06-27 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-27 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-09 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-09 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2001-05-09 00:00:00 | 1) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE SPRINKLER SYSTEM. | | | 2) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE ALARM SYSTEM EQUIPMENT | | | INSTALLATION. | | | 3) INTERIOR FINISH ON WALLS AND CEILINGS | | | MUST BE AT LEAST A CLASS C FLAME | | | SPREAD. | | | 4) PORTABLE FIRE EXTINGUISHERS TYPE 2A | | | 10BC, WITH CURRENT SERVICE TAGS ARE | | | TO BE PROVIDED. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2001-10-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-12 |
Time |
12:45 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-12 |
Time |
12:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-08-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-09 |
Time |
12:10 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-08-09 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2001-08-09 00:00:00 | *****************PROVISO**************** | | | | | | | | | | | | ACCESS DOOR IN LASER ROOM SHOULD HAVE A | | | FIRE RATING THAT OF THE CEILING IN THAT | | | SPACE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-08 |
Time |
07:27 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-08-08 |
Time |
06:55 |
Sent To |
|
|
| Notes |
| 2001-08-08 00:00:00 | *******************PROVISO************** | | | | | | | | | SHOULD CEILING HAVE A 1 HR OR GREATER | | | RATING, ACCESS DOOR SHALL CARRY THE | | | SAME RATING. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-06-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-13 |
Time |
13:49 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-06-13 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2001-06-13 00:00:00 | ******************PROVISO*************** | | | | | | | | | | | | NOTE:AC-6 SHALL COMPLY WITH 1997 SMC | | | 304.4.1, ACCESS FOR SERVICE & | | | REPLACEMENT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-29 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-05-29 |
Time |
09:24 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-05-29 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2001-05-29 00:00:00 | **************DENIED******************* | | | | | | 1. VERIFY EXISTANCE OF BASE BLDG. | | | EXHAUST RISER | | | 2. A/C 4 AND 5 CFM ON PLAN DO NOT | | | MATCH SCHEDULE FOR CFM | | | 3. SCHEDULE DOES NOT SHOW A/C 6 SHOWN ON | | | PLAN | | | 4. LEIBERT (A/C 6?) SHOWS DUCTS TO | | | CONDENSER OF A/C . FL. ENERGY CODE | | | 407.1.ABC D.3.3 DOES NOT PERMIT THE | | | CONDENSING COILS OF ONE UNIT TO BE IN | | | THE COOL AIR STREAM OF ANOTHER A/C UNIT. | | | 5. PROVIDE OUTSIDE AIR PER ASHRAE 62-89 | | | 6. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 7. NO COMBUSTIBLES ALLOWED IN R/A PLENUM | | | AREA INCLUDING PVC. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-20 |
Time |
15:15 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-08-20 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2001-08-20 00:00:00 | PROVISO | | | | | | BACKFLOW SHALL BE READILY ACCESSABLE, | | | FINAL APPROVAL BY FIELD INSPECTOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-01 |
Time |
13:04 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-08-01 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2001-08-01 00:00:00 | PROVISO... | | | | | | 1) REVISION REQUIRED FOR DETAIL ON | | | LOCATION OF BACKFLOW. BACKFLOW MUST BE | | | READLY ACCESSABLE. | | | | | | 2) APPROVAL SHALL BE BY FIELD INSPECTORS | | | APPROVAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-07-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-22 |
Time |
07:39 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-07-22 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2001-07-22 00:00:00 | REVISION DENIED; | | | | | | BACKFLOW PREVENTER MUST BE READILY | | | ACCESSIBLE FOR TESTING AND REPAIR NO | | | HIGHER THAN 4'. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-06-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-18 |
Time |
16:29 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-06-18 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2001-06-18 00:00:00 | REVIEW NOTES:PASSED | | | | | | PROVISO: | | | | | | 1)BACKFLOW REQUIRED TO BE MAXIMUM OF | | | 4' ABOVE FINISHED FLOOR FOR MAINTENANCE. | | | | | | 2) BACKFLOW ALSO REQUIRES A FLOOR SINK | | | TO DRAIN INTO, WITH A TRAP-PRIMER TO | | | KEEP TRAP SEAL. | | | | | | 3) PROVIDE DETAIL FOR ABOVE INSTALLATION | | | THAT IS SIGNED AND SEALED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-27 |
Time |
21:48 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-27 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) SHT A9.1 DOOR SWING IN RM'S #523 & | | | #535,TO COMPLY W/FACBC 4.23.2 SWING DOOR | | | OUT OF TURNING RADIUS OF WHEEL CHAIR. | | | (2) SHT A9.2 DR'S OFFICE REST RM # 518 | | | TO BE ADAPTABLE, SHOW BACKING FOR GRAB | | | BARS,DIMENSIONS OF FIXTURES OFF WALL. | | | FACBC 97 SEC 4.1.3(11). | | | (3) SHT A9.1 BREAK RM SINK RM #522,SHOW | | | CLEAR FLOOR SPACE, COUNTER HGTH 34"FF. | | | FACBC 97 SEC 4.24.2,4.24.5 | | | (4) SHT M-1 RM#525,NOTE 7,HUMIDIFIER | | | WTER SUPPLY,TO BE PROTECTED WITH A BACK | | | FLOW PREVENTER."RPZV". | | | SPC 94 SEC 601.6 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096 X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-06-27 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-27 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|