Plan Review Details - Permit 01050294
Plan Review Stops For Permit 01050294
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By hpiskura Date 2001-05-22 Time 10:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-03 Cont ID  
Sent By dpalmer Date 2001-07-03 Time 18:09 Rev Time 0.00
Received By dpalmer Date 2001-07-03 Time 18:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 20:18 Rev Time 0.00
Received By dpalmer Date 2001-05-15 Time 20:18 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-05-23 Cont ID  
Sent By pkrauss Date 2001-05-23 Time 11:06 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-08 Cont ID  
Sent By mcarsill Date 2001-05-08 Time 09:11 Rev Time 0.00
Received By mcarsill Date 2001-05-08 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-05 Cont ID  
Sent By pkrauss Date 2001-07-05 Time 15:34 Rev Time 0.40
Received By pkrauss Date 2001-07-05 Time 15:27 Sent To  
Notes
2001-07-05 00:00:00********************PROVISO*************
  
  
 FIRE DAMPERS SHALL COMPLY WITH THE
 REQUIREMENTS OF UL 555 & SHALL BEAR THE
 LABLE OF AN APPROVED TESTING AGENCY.
 (1997 SMC 610.1.1)
  
 PLEASE PROVIDE INSTALLATION DETAILS OF
 FIRE DOOR AND FIRE DAMPER.(1997 SMC
 610.6)
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-05-23 Cont ID  
Sent By pkrauss Date 2001-05-23 Time 10:39 Rev Time 0.35
Received By pkrauss Date 2001-05-23 Time 10:28 Sent To  
Notes
2001-05-23 00:00:00******************PROVISO***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 1.OUTSIDE AIR CALCUTATIONS AS PER
 ASHRAE 62-89.
  
 2.SIZE OF SUPPLY DUCT IN BREAK/COPY/
 STORAGE ROOM, AND CFM TO THIS SPACE
 AS WELL AS THE DMG OFFICE.
  
  
 NOTE:NO COMBUSTIBLES ABOVE CEILING IN
 RETURN AIR PLENUM AS PER 1997
 SMC 609.1.1.
  
 FIRE DAMPERS SHALL COMPLY WITH
 REQUIREMENTS OF UL 555 AND SHALL
 BEAR THE LABLE OF AN APPROVED
 TESTING AGENCY. (1997 SMC
 610.1.1)
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8333.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-12 Cont ID  
Sent By jleech Date 2001-05-12 Time 13:34 Rev Time 0.75
Received By jleech Date 2001-05-12 Time 13:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-05-23 Cont ID  
Sent By pkrauss Date 2001-05-23 Time 11:06 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***