Plan Review Details - Permit 01050173
Plan Review Stops For Permit 01050173
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-05-16 Cont ID  
Sent By rmcdouga Date 2001-05-16 Time 16:43 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-05-16 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE SAFETY GLASS PER 1997 SBC SEC
 2405.2.1
  
 2) BEDROOM EMERGENCY EGRESS TO BE
 MAINTAINED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-08 Cont ID  
Sent By dpalmer Date 2001-05-08 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2001-05-08 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-09 Cont ID  
Sent By kstevens Date 2001-05-09 Time 16:05 Rev Time 0.45
Received By kstevens Date 2001-05-09 Time 16:05 Sent To  
Notes
2001-05-09 00:00:00REVIEW NOTES:PASSED
  
 *** PLUMBING NOTES ***
  
 PAGE A-1 PLUMBING NOTES #16 AIR CHAMBERS
 MUST COMPLY WITH SPC-94 607.8.2 AND
 607.8.3, MUST BE ACCESSABLE AND RECHARG-
 ABLE.
  
 PAGE A-1 PLUMBING NOTES #19 SPC-94 PIPE
 2" AND SMALLER SHALL BE INSTALLED WITH
 FALL OF 1/4" PER FOOT. 705.2
  
 SPC-94 TABLE 714.1, 3" PIPE (FOOTNOTE-3)
 NOT MORE THAN 2 W/C'S ALLOWED ON 3"
 SANITARY.
  
 SPC-94 MODEL COUNTYWIDE AMMENDMENTS TO
 CODE 607.7 "NO MORE THAN 2 FIXTURES
 SHALL BE SUPPLIED WITH A 1/2" COLD WATER
 SUPPLY. NO MORE THAN 4 FIXTURES SHALL BE
 SUPPLIED WITH A 1/2" HOT WATER SUPPLY.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377