| Plan Review Stops For Permit 01050154 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-30 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-20 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-07-20 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2001-07-20 00:00:00 | RE: SHEET A2 REV #2 DATED 7/5/01.SEE | | | SBC 202 DEFINITIONS FOR "PROPERTY LINE, | | | ASSUMED" TO ESTABLISH THAT THE | | | MEASUREMENT IS FROM THE CENTERLINE OF | | | THE STREET, WHICH PROVIDES IN THIS | | | SITUATION TO BE SIGNIFICANTLY LESS THAN | | | 15' (FIFTEEN FEET)SEE SBC 705.1.1.2 | | | AND PROVIDE A PROTECTED OPENING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-06-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-06-22 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-22 00:00:00 | SAME AS FIRST CHECKLIST. THE 15" WAS A | | | TYPO,HOWEVER NO DOUBT THE ARCHITECT | | | HAS ACCESS TO SBC 705.1.1 WHICH CLEARLY | | | STATES THAT "EVERY EXTERIOR WALL WITHIN | | | FIFTEEN FEET OF A PROPERTY LINE SHALL | | | BE EQUIPPED WITH APPROVED OPENING | | | PROTECTIVES"PLEASE REVISE AS NECESSARY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-05-15 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | SHEET A2 SHOWS AN EXHAUST FAN TO | | | PENERTATE THE WALL ON THE WEST SIDE. | | | THIS IS SIDE IS LESS THAT 15" FROM THE | | | ADJACENT PROPERTY AND REQUIRES AN | | | OPENING PROTECTIVE.SEE SBC 705.1.1.1. | | | | | | SHEET E2 SHOWS CONDUIT BEING PLACED IN | | | THE STAIRWAY WHICH IS PROHIBITTED BY | | | SBC 1006.1.3.1. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-18 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-18 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-06-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-14 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-14 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2001-06-14 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT AS PER OVERVIEW | | | AND CONVERSATION WITH WILLIAM STAPLES | | | ASS BUILDING OFFICAL. PLEASE CONTACT | | | DON NEELY IN REFERENCE TO LETTER ATTACHE | | | D FOR ALL INSPECTIONS INCLUDING FINAL TO | | | BE DONE BY MAURICE SHASHOUA P.E. | | | DON NEELY'S EXT IS 8333 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT NOTE ADDED TO PLANS ON | | | E-1. PLANS CALL FOR 10,000 RATED BRKRS | | | STILL MISSING RATINGS FOR ALL EQUIPMENT | | | PER FIRST REVIEW. | | | | | | 3)NOTE: PLEASE NOTE THAT AS OF THIS | | | REVIEW, LOAD CALCULAITONS WERE NOT | | | SUBMITTED FOR REVIEW. PLEASE DO NOT | | | RESUB NEXT TIME W/OUT LOAD CALCUALTIONS | | | ON PLANS FOR EXSITING LOADS AND ALL NEW | | | LOADS BEING ADDED. | | | | | | 4)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS NEED TO BE SHOWN AT 125%. INCLUD- | | | -ING LOAD CALCS SUBMITTED. PER215-5,215- | | | -3 AND 230-42 | | | | | | 5) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. | | | PLEASE NOTE THAT ALL OTHER ELECTRICAL | | | CODE VIOLATIONS DISCOVERED BY | | | CAPT MIKE CARSILLO DURING A FIELD | | | INSPECTION WILL NEED TO BE CORRECTED | | | BEFORE FINAL. SEPARATE PERMIT WILL BE | | | REQ`D AND THAT SHOULD BE WORKED OUT | | | WITH BLDG OWNER. | | | IF THERE ARE ANY QUESTIONS AND/OR A | | | REQUEST FOR FEILD MEETING IS NEEDED, | | | PLEASE CALL. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | JAKE LEAHY | | | CHIEF ELECTRICAL INSPECTOR | | | 561-659-8096 EXT 8451 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-05-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-11 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-11 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2001-05-11 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE PROVIDE LOAD | | | CALCULATIONSFOR EXISTING MAIN. 215-5 | | | | | | 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS THAT CORRELATE WITH | | | SUBMITTED PANEL SCHEDULES. | | | | | | 3)NOTE: PLEASE CLARIFY SIZE OF NEW | | | TRAN--SFER SWITCH,, IS IT THE SAME AS | | | EXISTING? | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-05-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-23 |
Time |
09:07 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-07-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-10 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-10 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-12 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-12 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2001-06-12 00:00:00 | 1) A RECENT SURVEY OF THE BASEMENT | | | STAIRWAY INDICATED SEVERAL CODE | | | VIOLATIONS. THEY INCLUDE NO HANDRAILS, | | | CONDUIT AND A FUSE PANEL, EXISTING | | | ELECTRICAL CONDUITS, NO EMERGENCY | | | LIGHTING, HOLES IN WALLS, OPEN | | | ELECTRICAL BOXES, AND OTHER VIOLATIONS. | | | HOW DOES PROTECTING THE EXISTING CONDUIT | | | WITH DRYWALL INTERFERE WITH INSTALLATION | | | OF HANDRAILS AND MEET THE MINIMUM | | | DIMENSIONS OF AT 36" WIDE STAIRS FOR | | | OCCUPANT LOADS OF LESS THAN 50 PERSONS. | | | 2) PLEASE PROVIDE DIMENSIONS OF NEW | | | SHAFT. | | | 3) IF THE NEW SHAFT IS APPROVED BY | | | THE BUILDINGS PLAN REVIEWER, IT SHALL | | | NOT INTERFERE WITH MINIMUM CODE | | | REQUIREMENTS FOR THE BASEMENT STAIRWAY. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-05-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-08 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-08 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2001-05-08 00:00:00 | 1) IT APPEARS THAT EQUIPMENT IS RUNNING | | | THROUGH THE EXIT STAIRWAY OR EXIT | | | CORRIDOR. NO PENETRATIONS ARE ALLOWED | | | TO ENTER THE EXIT STAIRWAY UNLESS IT | | | IS FOR FIRE PROTECTION OR EMERGENCY | | | LIGHTING. PLEASE CLARIFY AND NOTE THIS | | | ON THE DRAWINGS. | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE INSTALLATION OF THE FM 200 | | | SYSTEM. THIS SYSTEM SHALL NOT BE IN | | | LIEU OF ANY REQUIRED FIRE SPRINKLER | | | PROTECTION. | | | 3) PLEASE EXPLAIN EXISTING CONDUIT UP | | | STAIRWAY SHOWN ON ELECTRICAL RISER | | | DIAGRAM DRAWING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-07-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-23 |
Time |
11:11 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-07-23 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2001-07-23 00:00:00 | ******************PROVISO*************** | | | | | | | | | MINIMUM OF 24" BETWEEN EXHAUST AND FRESH | | | AIR INTAKE (1997 SMC 405) AND 10' FROM | | | ANY ADJACENT BUILDING, PARKING AREA, | | | PROPERTY LINE, WINDOW, DOOR AND ABOVE | | | THE AADJOINING GRADE LEVEL (1997 SMC | | | 506.1 | | | | | | MINIMUM OF 30" CLEAR SPACE ON SERVICE | | | SIDE OF CONDENSER FOR INPECTION AND | | | SERVICING. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-06-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-15 |
Time |
13:13 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-06-15 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2001-06-15 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89. | | | | | | PLEASE PROVIDE AIR BALANCE SCHEDULE AS | | | PER 1997 SMC 501.2. | | | | | | DUCTS PENETRATING RATED WALLS, REQUIRE | | | FIRE DAMPERS AS PER 1997 SMC 610.1.1 | | | PLEASE SHOW DUCT ON PLANS AS WELL AS | | | ANY FIRE DAMPERS. | | | | | | CONDENSATE SHALL COMPLY WITH 1997 SMC | | | 304.8.3, UNITS LARGER THAN 3 TON SHALL | | | DRAIN INTO STORM DRAIN OR AN APPROVED | | | DRY WELL. | | | | | | NOTE:SHOULD CONDENSERS BE MORE THAN | | | 20 FT ABOVE GRADE, THEY SHALL BE | | | ACCESSIBLE BY A PERMENANT MEANS. | | | | | | FM 200 FIRE SUPRESSION SYSTEM | | | REQUIRES SEPERATE PLANS & PERMIT | | | BY A LICENSED MECHANICAL | | | CONTRACTOR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-21 |
Time |
11:50 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-05-21 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2001-05-21 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | | | | 1.HOW ARE CONDENSER UNITS BEING | | | SECURED TO PLATFORM AND INDICATE | | | HOW UNITS WILL BE ACCESSED FOR | | | SERVICE.A MINIMUM OF 30" OF | | | CLEAR SPACE ON THE SERVICE SIDE | | | FOR INSPECTION AND SERVICE.(1997 | | | SMC 304.2.5.) | | | | | | 2.PROVIDE OUTSIDE CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 3.OVER FLOW PROTECTION AS PER 1997 | | | SMC 304.8.6, FOR THE FAN COIL. | | | | | | 4.PLEASE DESIGNATE WHERE CONDENSATE | | | TERMINATION WILL BE MADE. | | | NOTE, CONDENSATE SHALL NOT | | | TERMINATE INTO THE SANITARY.5 TON | | | SHALL DRAIN INTO STORM DRAIN OR | | | AN APPROVED FRENCH DRAIN. (1997 | | | SMC 304.8.3) | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096EXT.8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2001-05-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-23 |
Time |
09:08 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-23 00:00:00 | NO PLUMBING PLANS SUBMITTED FOR REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2001-07-26 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-07-26 |
Time |
09:25 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2001-06-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-15 |
Time |
14:59 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-06-15 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2001-06-15 00:00:00 | | | | | | | MUST SUPPLY A SURVEY OF PROPERTY TO SHOW | | | ALL PROPERTY LINE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-23 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-05-23 |
Time |
08:15 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-23 00:00:00 | EQUIPMENT MUST BE SCREENED IN DMP |
|
|