Plan Review Details - Permit 01050154
Plan Review Stops For Permit 01050154
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-07-30 Cont ID  
Sent By hpiskura Date 2001-07-30 Time 11:37 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-07-20 Cont ID  
Sent By hpiskura Date 2001-07-20 Time 11:55 Rev Time 0.00
Received By hpiskura Date 2001-07-20 Time 11:43 Sent To  
Notes
2001-07-20 00:00:00RE: SHEET A2 REV #2 DATED 7/5/01.SEE
 SBC 202 DEFINITIONS FOR "PROPERTY LINE,
 ASSUMED" TO ESTABLISH THAT THE
 MEASUREMENT IS FROM THE CENTERLINE OF
 THE STREET, WHICH PROVIDES IN THIS
 SITUATION TO BE SIGNIFICANTLY LESS THAN
 15' (FIFTEEN FEET)SEE SBC 705.1.1.2
 AND PROVIDE A PROTECTED OPENING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-22 Cont ID  
Sent By hpiskura Date 2001-06-22 Time 10:35 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-06-22 00:00:00SAME AS FIRST CHECKLIST. THE 15" WAS A
 TYPO,HOWEVER NO DOUBT THE ARCHITECT
 HAS ACCESS TO SBC 705.1.1 WHICH CLEARLY
 STATES THAT "EVERY EXTERIOR WALL WITHIN
 FIFTEEN FEET OF A PROPERTY LINE SHALL
 BE EQUIPPED WITH APPROVED OPENING
 PROTECTIVES"PLEASE REVISE AS NECESSARY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-15 Cont ID  
Sent By hpiskura Date 2001-05-15 Time 16:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-05-15 00:00:00SHEET A2 SHOWS AN EXHAUST FAN TO
 PENERTATE THE WALL ON THE WEST SIDE.
 THIS IS SIDE IS LESS THAT 15" FROM THE
 ADJACENT PROPERTY AND REQUIRES AN
 OPENING PROTECTIVE.SEE SBC 705.1.1.1.
  
 SHEET E2 SHOWS CONDUIT BEING PLACED IN
 THE STAIRWAY WHICH IS PROHIBITTED BY
 SBC 1006.1.3.1.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-07-18 Cont ID  
Sent By dpalmer Date 2001-07-18 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2001-07-18 Time 16:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-14 Cont ID  
Sent By dpalmer Date 2001-06-14 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2001-06-14 Time 17:34 Sent To  
Notes
2001-06-14 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT AS PER OVERVIEW
 AND CONVERSATION WITH WILLIAM STAPLES
 ASS BUILDING OFFICAL. PLEASE CONTACT
 DON NEELY IN REFERENCE TO LETTER ATTACHE
 D FOR ALL INSPECTIONS INCLUDING FINAL TO
 BE DONE BY MAURICE SHASHOUA P.E.
 DON NEELY'S EXT IS 8333
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT NOTE ADDED TO PLANS ON
 E-1. PLANS CALL FOR 10,000 RATED BRKRS
 STILL MISSING RATINGS FOR ALL EQUIPMENT
 PER FIRST REVIEW.
  
 3)NOTE: PLEASE NOTE THAT AS OF THIS
 REVIEW, LOAD CALCULAITONS WERE NOT
 SUBMITTED FOR REVIEW. PLEASE DO NOT
 RESUB NEXT TIME W/OUT LOAD CALCUALTIONS
 ON PLANS FOR EXSITING LOADS AND ALL NEW
 LOADS BEING ADDED.
  
 4)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%. INCLUD-
 -ING LOAD CALCS SUBMITTED. PER215-5,215-
 -3 AND 230-42
  
 5) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
 PLEASE NOTE THAT ALL OTHER ELECTRICAL
 CODE VIOLATIONS DISCOVERED BY
 CAPT MIKE CARSILLO DURING A FIELD
 INSPECTION WILL NEED TO BE CORRECTED
 BEFORE FINAL. SEPARATE PERMIT WILL BE
 REQ`D AND THAT SHOULD BE WORKED OUT
 WITH BLDG OWNER.
 IF THERE ARE ANY QUESTIONS AND/OR A
 REQUEST FOR FEILD MEETING IS NEEDED,
 PLEASE CALL.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 JAKE LEAHY
 CHIEF ELECTRICAL INSPECTOR
 561-659-8096 EXT 8451

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-11 Cont ID  
Sent By dpalmer Date 2001-05-11 Time 15:48 Rev Time 0.00
Received By dpalmer Date 2001-05-11 Time 15:48 Sent To  
Notes
2001-05-11 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE PROVIDE LOAD
 CALCULATIONSFOR EXISTING MAIN. 215-5
  
 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS THAT CORRELATE WITH
 SUBMITTED PANEL SCHEDULES.
  
 3)NOTE: PLEASE CLARIFY SIZE OF NEW
 TRAN--SFER SWITCH,, IS IT THE SAME AS
 EXISTING?
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-05-23 Cont ID  
Sent By pkrauss Date 2001-05-23 Time 09:07 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-10 Cont ID  
Sent By mcarsill Date 2001-07-10 Time 13:49 Rev Time 0.00
Received By mcarsill Date 2001-07-10 Time 13:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-06-12 Cont ID  
Sent By mcarsill Date 2001-06-12 Time 10:03 Rev Time 0.00
Received By mcarsill Date 2001-06-12 Time 10:03 Sent To  
Notes
2001-06-12 00:00:001) A RECENT SURVEY OF THE BASEMENT
 STAIRWAY INDICATED SEVERAL CODE
 VIOLATIONS. THEY INCLUDE NO HANDRAILS,
 CONDUIT AND A FUSE PANEL, EXISTING
 ELECTRICAL CONDUITS, NO EMERGENCY
 LIGHTING, HOLES IN WALLS, OPEN
 ELECTRICAL BOXES, AND OTHER VIOLATIONS.
 HOW DOES PROTECTING THE EXISTING CONDUIT
 WITH DRYWALL INTERFERE WITH INSTALLATION
 OF HANDRAILS AND MEET THE MINIMUM
 DIMENSIONS OF AT 36" WIDE STAIRS FOR
 OCCUPANT LOADS OF LESS THAN 50 PERSONS.
 2) PLEASE PROVIDE DIMENSIONS OF NEW
 SHAFT.
 3) IF THE NEW SHAFT IS APPROVED BY
 THE BUILDINGS PLAN REVIEWER, IT SHALL
 NOT INTERFERE WITH MINIMUM CODE
 REQUIREMENTS FOR THE BASEMENT STAIRWAY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-08 Cont ID  
Sent By mcarsill Date 2001-05-08 Time 08:19 Rev Time 0.00
Received By mcarsill Date 2001-05-08 Time 08:18 Sent To  
Notes
2001-05-08 00:00:001) IT APPEARS THAT EQUIPMENT IS RUNNING
 THROUGH THE EXIT STAIRWAY OR EXIT
 CORRIDOR. NO PENETRATIONS ARE ALLOWED
 TO ENTER THE EXIT STAIRWAY UNLESS IT
 IS FOR FIRE PROTECTION OR EMERGENCY
 LIGHTING. PLEASE CLARIFY AND NOTE THIS
 ON THE DRAWINGS.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF THE FM 200
 SYSTEM. THIS SYSTEM SHALL NOT BE IN
 LIEU OF ANY REQUIRED FIRE SPRINKLER
 PROTECTION.
 3) PLEASE EXPLAIN EXISTING CONDUIT UP
 STAIRWAY SHOWN ON ELECTRICAL RISER
 DIAGRAM DRAWING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-23 Cont ID  
Sent By pkrauss Date 2001-07-23 Time 11:11 Rev Time 0.40
Received By pkrauss Date 2001-07-23 Time 11:11 Sent To  
Notes
2001-07-23 00:00:00******************PROVISO***************
  
  
 MINIMUM OF 24" BETWEEN EXHAUST AND FRESH
 AIR INTAKE (1997 SMC 405) AND 10' FROM
 ANY ADJACENT BUILDING, PARKING AREA,
 PROPERTY LINE, WINDOW, DOOR AND ABOVE
 THE AADJOINING GRADE LEVEL (1997 SMC
 506.1
  
 MINIMUM OF 30" CLEAR SPACE ON SERVICE
 SIDE OF CONDENSER FOR INPECTION AND
 SERVICING.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-06-15 Cont ID  
Sent By pkrauss Date 2001-06-15 Time 13:13 Rev Time 0.50
Received By pkrauss Date 2001-06-15 Time 13:13 Sent To  
Notes
2001-06-15 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 PLEASE PROVIDE AIR BALANCE SCHEDULE AS
 PER 1997 SMC 501.2.
  
 DUCTS PENETRATING RATED WALLS, REQUIRE
 FIRE DAMPERS AS PER 1997 SMC 610.1.1
 PLEASE SHOW DUCT ON PLANS AS WELL AS
 ANY FIRE DAMPERS.
  
 CONDENSATE SHALL COMPLY WITH 1997 SMC
 304.8.3, UNITS LARGER THAN 3 TON SHALL
 DRAIN INTO STORM DRAIN OR AN APPROVED
 DRY WELL.
  
 NOTE:SHOULD CONDENSERS BE MORE THAN
 20 FT ABOVE GRADE, THEY SHALL BE
 ACCESSIBLE BY A PERMENANT MEANS.
  
 FM 200 FIRE SUPRESSION SYSTEM
 REQUIRES SEPERATE PLANS & PERMIT
 BY A LICENSED MECHANICAL
 CONTRACTOR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-21 Cont ID  
Sent By pkrauss Date 2001-05-21 Time 11:50 Rev Time 0.40
Received By pkrauss Date 2001-05-21 Time 11:50 Sent To  
Notes
2001-05-21 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
  
 1.HOW ARE CONDENSER UNITS BEING
 SECURED TO PLATFORM AND INDICATE
 HOW UNITS WILL BE ACCESSED FOR
 SERVICE.A MINIMUM OF 30" OF
 CLEAR SPACE ON THE SERVICE SIDE
 FOR INSPECTION AND SERVICE.(1997
 SMC 304.2.5.)
  
 2.PROVIDE OUTSIDE CALCULATIONS AS PER
 ASHRAE 62-89.
  
 3.OVER FLOW PROTECTION AS PER 1997
 SMC 304.8.6, FOR THE FAN COIL.
  
 4.PLEASE DESIGNATE WHERE CONDENSATE
 TERMINATION WILL BE MADE.
 NOTE, CONDENSATE SHALL NOT
 TERMINATE INTO THE SANITARY.5 TON
 SHALL DRAIN INTO STORM DRAIN OR
 AN APPROVED FRENCH DRAIN. (1997
 SMC 304.8.3)
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096EXT.8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-05-23 Cont ID  
Sent By pkrauss Date 2001-05-23 Time 09:08 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2001-05-23 00:00:00NO PLUMBING PLANS SUBMITTED FOR REVIEW.

Review Stop Z ZONING
Rev No 3 Status P Date 2001-07-26 Cont ID  
Sent By sgraham Date 2001-07-26 Time 09:25 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2001-06-15 Cont ID  
Sent By pkrauss Date 2001-06-15 Time 14:59 Rev Time 0.25
Received By pkrauss Date 2001-06-15 Time 14:58 Sent To  
Notes
2001-06-15 00:00:00 
  
 MUST SUPPLY A SURVEY OF PROPERTY TO SHOW
 ALL PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2001-05-23 Cont ID  
Sent By sgraham Date 2001-05-23 Time 08:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-05-23 00:00:00EQUIPMENT MUST BE SCREENED IN DMP