Review Stop P PLUMBING
Rev No 4 Status F Date 2001-07-31 Cont ID  
Sent By pschmitz Date 2001-07-31 Time 08:57 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-31 00:00:00PLUMBING PLAN REVIEWDENIED.
 (1) SEE PREVIOUS NOTES DATED, 07-17-01.
 (2) COPY OF CONTRACT W/PLUMBING CONTR.
 NOTE #5 GAS PIPING BY PLBG CONTRACTOR.
 (3) COPY OF WELDER CERTIFICATION
 (4) FL PUBLIC UTILITIES DELIVERY PSI.
 12" TO 14" W/C. NOTE #7.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096X8233

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-07-17 Cont ID  
Sent By jleech Date 2001-07-17 Time 18:33 Rev Time 1.00
Received By pschmitz Date 2001-07-17 Time 18:33 Sent To  
Notes
2001-07-17 00:00:00DENIED;
  
 (ROTISSERIES) AUTOMATIC SHUTOFF VALVE
 REQUIRED ON GAS LINE AT HOOD AND ANSUL
 SYSTEM. SHUTOFF VALVE SHOULD BE UP
 STREAM OF ASV WITH A UNION DOWN STREAM
 SO ASV CAN BE CHANGED OUT IF NEEDED.
 SEE 97 SMC SEC. 507.1
  
 GAS PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT 8369

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-06-19 Cont ID  
Sent By kstevens Date 2001-06-19 Time 15:01 Rev Time 0.75
Received By pschmitz Date 2001-06-19 Time 15:01 Sent To  
Notes
2001-06-19 00:00:00REVIEW NOTES:DENIED
  
 1) MORE INFORMATION REQUIRED. SEE GAS
 PERMIT APPLICATION REQUIREMENTS SHEET
 RETURNED WITH APPLICATION. ALL AREAS
 WITH RED PEN MARKINGS TO BE ADDRESSED
 FOR PLAN REVIEW.
  
 2) SPECIFY IF PIPE IS TO BE WELDED OR
 THREADED.
  
 3) IF WELD PIPE TO BE INSTALLED, WELDER
 SHALL SUBMIT AN UP TO DATE CERTIFICATION
 WITH A PICTURE I.D.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-05 Cont ID  
Sent By pschmitz Date 2001-05-05 Time 13:57 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-05 00:00:00NO GAS PLANS ON FILE WITH PRIMARY PERMIT
 00021256, PLANS REQ.W/APPLICATION.
 QUESTION ON TYPE OF GAS NAT OR L-P ?
 IF NAT GAS,LICENSED PLUMBER TO MAKE
 APPLICATION.
 PES