| Plan Review Stops For Permit 01050105 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-17 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-01 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-01 00:00:00 | RE: THE BUTLER MFG. LETTER FROM J. E. | | | LAMB.WHAT IS THE REFERENCE TO | | | CLIMATIC DATA AND MBMA?WIND PRESSURE | | | DESIGN MUST BE FROM ASCE 7-95 OR SBC | | | 1606.1.1. | | | | | | PROVIDE A SKETCH DEPICTING THE PRESSURE | | | ZONES FOR THE COMPONENTS AND CLADDING | | | THAT CORRELATE TO THE BUTLER SPECIFIC | | | REACTION DRAWINGS. | | | | | | THE MIAMI DADE NOA #99-0318.03 IS | | | MISSING THE DRAWING REFEREDCED IN | | | SPECIFIC CONDITION #2. AND 6.1.2. | | | | | | NOA #00-0315.03 IS MOSTLY ILLEGIBLE AND | | | HAS MISSING PAGES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-05-21 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-21 00:00:00 | WHAT IS THE CONSTRUCTION TYPE OF THE | | | EXISTING BUILDING?SEE SBC 601.2. | | | | | | TYPE IV BUILDINGS INSIDE THE FIRE | | | DISTRICT ARE REQUIRED TO HAVE 2 HR | | | RATRED WALLS.SEE SBC F102.2.6. | | | | | | WHAT KIND AND QUANTITIES OF MATERIALS | | | WILL BE STORED AND / OR USED IN THIS | | | BUILDING?WHAT KIND OF MANUFACTURING | | | PROCES SES ARE INTENDED? | | | | | | WHERE WILL THE DESIGN LOADS CALLED OUT | | | ON S1 BE APPLIED TO THIS BUILDING? | | | | | | PROVIDE A SKETCH OR NOTES SHOWING THE | | | WIND PRESSURE ZONES FOR THIS BUILDING | | | | | | PLEASE PROVIDE A PROPERTY SURVEY | | | | | | SHOW HOW THE GLAZED OPENINGS WILL COMPLY | | | WITH THE CITY'S HURRICANE MISSILE | | | IMPACT RESISTANCE POLICY. | | | | | | IMPACT FEES MUST BE PAID TO THE COUNTY. | | | CALL 233-5025 FOR MORE INFORMATION. | | | | | | PROVIDE THE PRODUCT EVALUATION REPORTS | | | FOR THE DOORS WINDOWS AND ROOF | | | COVERINGS TO BE USED ON THIS BUILDING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-20 |
Time |
22:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-20 |
Time |
22:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-01 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-01 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2001-08-01 00:00:00 | ****************** UNSAT *************** | | | | | | PLEASE NOTE THAT NOT ALL NOTES FROM | | | FIRST REVIEW WERE ADDRESSED. | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-15 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-15 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CLARIFY SERVICE ON PANEL | | | SCHEUDULE. SHOWS,, MAIN 800 AMP ? | | | TYPE-O? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | RISER DIAGRAM SHOWS 200A AND 400K? | | | PLEASE CLARIFY. | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125% (LIGHTING ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-07-12 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-12 |
Time |
11:21 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-07-12 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2001-07-12 00:00:00 | PASSED : | | | | | | ***NOTE*** | | | PLEASE REVISE LANDSCAPING SHEETS TO | | | COMPLY WITH CIVIL SHEETS. | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-05-15 |
Time |
14:06 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-05-15 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | FAILED: | | | 1. PLEASE PROVIDE STORM WATER | | | CALCULATION FOR OUR REVIEW IF YOU HAVE | | | NOT SUBMITTED TO JOSE DEL RIO, STORM | | | WATER ENGINEER AT 1000 45TH STREET WEST | | | PALM BEACH, FL 33407.PLEASE SEE | | | ATTACHED | | | 2. ANY WORK WITHIN PUBLIC R.O.W REQUIRES | | | A SEPARATE PERMIT THROUGH OFFICE OF CITY | | | ENGINEER AT 1000 45TH STREET WEST PALM | | | BEACH FL 33407. | | | 3. ANY NEW CONNECTION TO CITY UTILITY | | | SERVICES REQUIRES A SEPARATE PERMIT | | | THROUGH PUBLIC UTILITIES ENGINEERING | | | SERVICES DEPARTMENT AT 1000 45TH STREET | | | WEST PALM BEACH, FL 33407. | | | 4. PLEASE CLEARLY SHOW THE APPROACH | | | DRIVEWAY TO THE FACILITY, ALSO SHOW TYPE | | | , SIZE, SIDEWALK CURB / GUTTER, ETC. | | | SEE ATTACHED | | | 5. PLEASE SHOW UNDERGROUND UTILITY WORKS | | | 6. SHOW LOCATION OF BACKFLOW PREVENTERS | | | AND LOCATION OF CONNECTION TO CITY | | | SERVICES. | | | 7. PROVIDE POLLUTION PREVENTION PLANS, | | | PALNS SHOULD BE INSTALLED IN FIELD PRIOR | | | TO ANY CONSTRUCTION WORK.IT SHOULD BE | | | KEPT ON CONSTROCTION SITE DURING THE | | | CONSTRUCTION. | | | 8. A CLEAN-OUT WILL NEED TO BE INSTALLED | | | IN THE SANITARY SEWER LATERAL, ON | | | PROPERTY, AT THE BACK OF THE SIDEWALK IF | | | NOT ALREADY INSTALLED. | | | 9. IS THERE ANY IRRIGATION SYS. BEING | | | PLANED? IF SO A SEPARATE BACKFLOW | | | PREVENTER SHOULD BE INSTALLED IN THIS | | | LINE. | | | 10. PLEASE SPECIFIED THE THE TYPE OF | | | PAVEMENTS, DETAILS, THICKNESS, ETC.. | | | 11. PLEASE PROVIDE PERVIOUS AND IMPERVIO | | | US CALCULATION FOR ENTIRE SITE.PLEASE | | | NOTE THAT THE TOTAL MUST ADD UP TO 100% | | | OF TOTAL SITE AREA.PROVIDE THIS | | | INFORMATION ON A 8 1/2 X 11 SHEET, | | | SIGNED AND SEALED BY THE DESIGN ENGINEER | | | PLEASE INCLUDE PROPERTY CONTROL NUMBER, | | | NAME AND ADDRESS.THIS DATA WILL BE | | | USED TO COMPUTE NEW STORM WATER CHARGES | | | THAT MY APPLY. | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-07-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-31 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-31 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2001-07-31 00:00:00 | 1) OPENING IN CHAIN LINK FENCE THAT | | | PROVIDES FOR EXITING MUST BE AT LEAST | | | 32 INCHES WIDE. THE GATE MUST NEVER | | | BE LOCKED TO PREVENT MOVEMENT FROM | | | ONE AREA TO ANOTHER. | | | 2) EXIT DISCHARGE FROM THE WAREHOUSE | | | AND TECH AREA MUST BE OBVIOUS AND | | | DIRECT ONCE PERSONS HAVE LEFT THROUGH | | | THE EXIT DOORS. | | | 3) FUTURE PROVISIONS FOR FIRE AND | | | PARAMEDICAL ACCESS WILL BE REQUIRED FOR | | | FUTURE ELECTRIC GATE. | | | 4) WHAT IS THE SMOKE DETECTOR IN THE | | | OFFICE CONNECTED TO? | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-05-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-14 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-14 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2001-05-14 00:00:00 | 1) PLEASE INDICATE WHAT ACTIVITIES WILL | | | OCCUR IN THE COVERED WORK AREA, | | | WAREHOUSE, AND TECH AREA. | | | 2) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS AND A LIFE SAFETY PLAN | | | FOR THE NEW BUILDING. | | | 3) PLEASE EXPLAIN NEW GATES. THESE GATES | | | MUST PROVIDE AT LEAST 20 FEET IN CLEAR | | | WIDTH FOR FIRE RESCUE ACCESS. WILL THE | | | GATES BE MANUAL OR ELECTRICALLY | | | OPERATED. | | | 4) PLEASE EXPLAIN EXITING RATIONALE FOR | | | THE NEW BUILDING. IT APPEARS THAT THE | | | CHAIN LINK FENCE LIMITS EXITING FROM | | | CERTAIN AREAS OF THE BUILDING. | | | 5) IS THE EXISTING BUILDING AND NEW | | | BUILDING GOING TO BE THE SAME TENANT. | | | 6) OPERABLE WINDOWS ARE TO BE PROVIDED | | | SO THE BUILDING WILL NOT BE CLASSIFIED | | | AS WINDOWLESS AND BE REQUIRED TO BE FIRE | | | SPRINKLER PROTECTED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-24 |
Time |
08:43 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-05-24 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | *******************DENIED*************** | | | | | | | | | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW, PLEASE SUBMIT PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-08-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-08-22 |
Time |
16:43 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2001-08-22 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-07-29 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-29 |
Time |
08:05 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-07-29 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2001-07-29 00:00:00 | DENIED; | | | | | | 1.BOTTLED WATER DISPENSOR IS NOT A | | | PLUMBING FIXTURE. SEE SPC CHAPTER 2 | | | DEFINITIONS, PLUMBING FIXTURE. SEE | | | TABLE 407 MISCELLANEOUS FIXTURES. NOTE | | | AT BOTTOM OF PLUMBING FIXTURE SCHEDULE | | | DOES ALTER MINIMUM FIXTURE REQUIREMENT | | | DRINKING FOUNTAIN TO COMPLY WITH FACBC | | | SEC. 4.1.3(10) AND 4.15. | | | 2.SHOW LOCATION AND ACCESSIBILITY OF | | | EXISTING BATHROOMS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-05-11 |
Time |
11:04 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-05-11 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2001-05-11 00:00:00 | DENIED; | | | | | | 1.SHOW BUILDING OCCUPANCY,(COVERED WORK | | | AREA AND TECH AREA) LIGHT OR HEAVY | | | MANUFACTURING. SHOW OCCUPANT CONTENT | | | PER SHIFT TO DETERMINE MINIMUM | | | PLUMBING FACILITYS REQUIRED. USE TABLE | | | 407 OF THE 94 SPC. | | | | | | 2.DRINKING FOUNTAIN IS REQUIRED PER SPC | | | TABLE 407. | | | | | | 3.PAGE A-3 (INTERIOR ELEVATIONS) USE | | | THE 97 FACBC FORMESSUREMENTS. | | | | | | 4.WHERE DOES RAIN WATER FROM ROOF AND | | | PARKING LOT DRAIN? | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-05-10 |
Time |
12:53 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|