Plan Review Details - Permit 01050059
Plan Review Stops For Permit 01050059
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-07-09 Cont ID  
Sent By jwitmer Date 2001-07-09 Time 08:42 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-18 Cont ID  
Sent By lmartine Date 2001-06-18 Time 14:27 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-06-18 00:00:00BUILDING COMMENTS
 2ND REVIEW
 ------------
 1]
 DCA LETTER REQUESTED STILL NOT PROVIDED.
 2]
 GENERAL STATEMENTS [LATEST EDITION IS
 NOT ACCEPTABLE],PLEASE BE SPECIFIC.ASCE
 7-93 IS NOT ACCEPTABLE.ALL STRUCTURAL
 CALCULATIONS AND COMPUTATIONS SHALL BE
 AS PER ASCE 7-95.
 3]
 PROJECT IS LOCATED ON CONGRESS AVE.
 EXPLAIN REFERENCE TO AUSTRALIA AVE.?
 4]
 COMMUTATIONS SUBMITTED ARE ACCORDING TO
 UBC 1997 AND ASCE 7-93,PLEASE REVISE AND
 SUBMIT CALCULATIONS AS PER ASCE 7-95.
 5]
 YOUR ON SITE ENGINEER/INSPECTOR SHALL BE
 APPROVED BY THE ASS. BUILD. OFFICIAL
 PRIOR TO PERMIT ISSUE.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-09 Cont ID  
Sent By jwitmer Date 2001-05-09 Time 14:37 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-09 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01050059
 1700 PALM BEACH LAKES /ROOF
 REGENCY TELECOMMUNICATIONS
 954-485-8600
  
 1)- THIS EQUIPMENT CABINET FALLS UNDER
 FLORIDA MANUFACTURED BUILDINGS, PROVIDE
 THE DCA APPROVAL,(DEPARTMENT OF COMMUN-
 ITY AFFAIRS).
 2)- FRAMING PLAN : STRUCTURAL DESIGN
 CRITERIA, WRONG CODE EDITION AND ASCE.
 THE CITY USES THE STANDARD BUILDING CODE
 1997 EDITION, STRUCTURES >= 60"-0"
 CONFORM TO ASCE 7-95, AS WELL AS THE
 ENGINEERS LETTER WRONG CRITERIA.
 3)- THE PERMIT APPLICATION IS FOR ONE
 ADDRESS AND THE PLANS CALL THE PROJECT
 FOR AUSTRALIA AVENUE.PLEASE CORRECT
 DOCUMENTS.
 4)- ENGINEER TO CERTIFY THE EXISTING
 STEEL WILL TAKE THE LOADS IMPOSED, WHAT
 TYPE OF CONNECTION WILL HOLD THE NEW
 STRUCTURE TO THE EXISTING STEEL, & WILL
 THIS HOLD THE MOMENT OF OVERTURNING?
 5)- THE ENGINEER THAT WOULD LIKE TO IN-
 SPECT THE PROJECT WILL NEED TO SIGN THE
 FORMS FOR RESIDENT INSPECTOR PROGRAM AS
 WELL AS THE AFFIDAVIT FOR CRTIFICATE OF
 CODE CONFORMANCE.
  
 JIMWITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-09 Cont ID  
Sent By dpalmer Date 2001-05-09 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2001-05-09 Time 09:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-07 Cont ID  
Sent By sgraham Date 2001-05-07 Time 10:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***