Plan Review Details - Permit 01050040
Plan Review Stops For Permit 01050040
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-24 Cont ID  
Sent By dpalmer Date 2001-06-24 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2001-06-24 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-10 Cont ID  
Sent By dpalmer Date 2001-05-10 Time 16:17 Rev Time 0.00
Received By dpalmer Date 2001-05-10 Time 16:17 Sent To  
Notes
2001-05-10 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING FOR LIVING ROOM PER 210-70.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-02-08 Cont ID  
Sent By pkrauss Date 2002-02-08 Time 13:06 Rev Time 0.35
Received By pkrauss Date 2002-02-08 Time 13:06 Sent To  
Notes
2002-02-08 00:00:00 
 MECH PERMIT 01050069

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2001-11-21 Time 10:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-05-07 Cont ID  
Sent By hmoser Date 2001-05-07 Time 19:07 Rev Time 0.33
Received By hmoser Date 2001-05-07 Time 19:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-25 Cont ID  
Sent By kstevens Date 2001-06-25 Time 10:06 Rev Time 0.25
Received By kstevens Date 2001-06-25 Time 10:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-02 Cont ID  
Sent By kstevens Date 2001-05-02 Time 11:49 Rev Time 0.33
Received By kstevens Date 2001-05-02 Time 11:49 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-07-03 Cont ID  
Sent By lsmith Date 2001-07-03 Time 10:24 Rev Time 2.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-05-29 Cont ID  
Sent By lsmith Date 2001-05-29 Time 13:15 Rev Time 3.00
Received By lsmith Date   Time   Sent To  
Notes
2001-05-29 00:00:00LEA SMITH, PLAN REVIEWER
 659-8096 EXT 8394
  
 1. BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALMBEACH CO.,THE PERMIT PLANS STAMPED
 BY THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 2. NEED PRODUCT APPROVAL FOR FRONT DOOR
 WITH SIDE LITES.
 3. DETAILS ON PRIVACY WALL NOT SHOWN ON
 SITE PLAN AS PER NOTED ON A-2.NOTE:
 PRIVACY WALL FOOTER CAN NOT ENCROACH ON
 ADJOINING PROPERTY (ZERO LOT LINE)
 4. A NOTICE OF COMMENCMENT MUST BE
 FILED AT PBC AND A COPY SUBMITTED
 BEFORE PERMIT IS ISSUED.
 5. NEED DESIGN CERTIFICATION FORM
 COMPLETED.
 6. PLANS SHOWS OPTIONAL BBQ.NEED MFGR
 SPECS ON UNIT AND UL LISTING.
 7. RADON FEES OF $42.24 PER ATTACHED BZ
 REC.#185701 TO BE PAID.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 LEA AT THE EXTENSION SHOWN ABOVE

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By lsmith Date 2001-05-22 Time 14:15 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-05-22 00:00:00PER SG 5/22/01