Plan Review Details - Permit 01041427
Plan Review Stops For Permit 01041427
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-09-27 Cont ID  
Sent By lmartine Date 2001-09-27 Time 11:58 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-09-27 00:00:00 
 BUILDING COMMENTS
 -----------------
  
 NEW BATHROOM REVISION:
  
 COUNTY IMPACT FEES ARE REQUIRED.
 SUBMIT WALL SECTION FOR NEW ADDTION ON
 SECOND FLOOR.
 PROVIDE WIND LOAD COMPLIANCE FOR
 WINDOWS.
  
  
 L. MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-06-22 Cont ID  
Sent By lmartine Date 2001-06-22 Time 14:52 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-15 Cont ID  
Sent By jwitmer Date 2001-06-15 Time 09:55 Rev Time 0.33
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-15 00:00:00NO CHANGE IN PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-11 Cont ID  
Sent By jwitmer Date 2001-05-11 Time 06:29 Rev Time 1.25
Received By jwitmer Date 2001-05-11 Time 06:30 Sent To  
Notes
2001-05-11 00:00:00PERMIT # 01041427
 901 35TH STREET
 O/B ROSSELLA MAZZITELLI
 H 366-0026
 O 805-6150 X 2208
  
 1)- PLANS THAT ARE DESIGNED BY ARCHITECT
 OR ENGINEERS ARE REQUIRED TO BE SIGNED
 DATED & SEALED BY THE DESIGN PROFESSION-
 AL 471.025 / 481.221.
  
 2)- GENERAL NOTE # 10,ENGINEER'S SEAL
 IS FOR APPROVAL OF STRUCTURAL DESIGN
 ONLY, --NO SEAL--
  
 3)- FLORIDA ROOM, REMOVAL OF WALL
 SECTIONS, WHAT TYPE OF CONSTRUCTION ARE
 WE DEALING WITH, FRAME OR CBS? WHAT TYPE
 OF SUPPORT IS HOLDING UP THE SSECOND
 FLOOR, IS THE SECOND FLOOR LOAD TRANSFER
 ED TO THIS WALL SYSTEM.
  
 4)- SBC 104.2.2 ADDITIONAL INFORMATION:
 KITCHEN SHOW ELEVATIONS OF CABINETRY
  
 5)- REMODELED BATH IS THERE A EXHAUST
 FAN OR A WINDOW WITH A OPEN AREA OF
 AT LEAST 3'-0" SQUARE FEET.
  
 6)- ROOFING, WHAT TYPE OF ROOF, WHAT IS
 THE PITCH OF THE ROOF AND WHAT TYPE OF
 MATERIALS ARE GOING TO BE REPLACED?
 ROOFING PRODUCT APPROVAL WILL BE
 REQUIRED EITHER SBCCI OR DADE COUNTY
 PRODUCT APPROVAL REPORTS ACCEPTTED.
  
 7)- ARE THERE GOING TO HAVE ANY WINDOWS
 REPLACED, IF SO, OVER 50% REPLACEMENT
 WILL REQUIRE LARGE MISSLE IMPACT TESTING
 OR APPROVED STORM SHUTTERS. THE CITY
 ACCEPTS SBCCI OR DADE COUNTY REPORTS.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-09-17 Cont ID  
Sent By dpalmer Date 2001-09-17 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2001-09-17 Time 19:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-06-29 Cont ID  
Sent By dpalmer Date 2001-06-29 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2001-06-29 Time 12:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-12 Cont ID  
Sent By dpalmer Date 2001-06-12 Time 18:48 Rev Time 0.00
Received By dpalmer Date 2001-06-12 Time 18:48 Sent To  
Notes
2001-06-12 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NOT DONE TO CODE. PLEASE SEE ART 220
 OF THE NEC.
 HEAT STRIPS FOR AHU`S ARE DERATED AT 40%
 W/ OTHER LOADS.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
 PLEASE NOTE THAT ONLY ONE AHU IS SHOWN
 AND NO COND UNIT`S ARE SHOWN??PLEASE
 SHOW.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 6)NOTE: PLEASE CLARIFY LIGHTING FOR
 HABITABLE ROOMS PER 210-70. TOWER RM AND
 FLORIDA ROOM
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 8)NOTE: PLEASE NOTE OUTLET REQ`D FOR UP-
 -STAIRS HALL PER 210-52H
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-10 Cont ID  
Sent By dpalmer Date 2001-05-10 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2001-05-10 Time 16:34 Sent To  
Notes
2001-05-10 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOT ETHAT PLANS THAT ARE
 DONE BY AN ARCH/ENGINEER, NEED TO BE
 SIGNED AND SEALED BY THAT ARCH/ENG OF
 RECORD. 471.025 481.221
  
 2)NOTE: PLEASE NOTE THAT NOT ENOUGH
 ELECTRICAL DEATIL WAS SUBMITTED FOR
 PROPER REVIEW OF PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-24 Cont ID  
Sent By pkrauss Date 2001-09-19 Time 09:38 Rev Time 0.40
Received By pkrauss Date 2001-09-19 Time 09:38 Sent To  
Notes
2001-09-19 00:00:00MECHANICAL PERMIT ISSUED WITHOUT PLANS
 BEING REVIEWED.THIS STOP IS NOT A
 REVISION IT IS A NEW SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-05-07 Cont ID  
Sent By jleech Date 2001-05-07 Time 20:01 Rev Time 0.33
Received By jleech Date 2001-05-07 Time 20:01 Sent To  
Notes
2001-05-07 00:00:00NOT ENOUGH INFORMATION;
  
 SUBMIT A/C PLANS WITH A/C APPLICATION.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-06-29 Cont ID  
Sent By kstevens Date 2001-06-29 Time 12:19 Rev Time 0.25
Received By kstevens Date 2001-06-29 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-12 Cont ID  
Sent By kstevens Date 2001-06-12 Time 12:33 Rev Time 0.33
Received By kstevens Date 2001-06-12 Time 12:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-07 Cont ID  
Sent By kstevens Date 2001-05-07 Time 12:36 Rev Time 0.33
Received By kstevens Date 2001-05-07 Time 12:36 Sent To  
Notes
2001-05-07 00:00:00REVIEW NOTES.FAILED
  
 (1) PLANS TO BE SIGNED AND SEALED.
  
 (2) SANITARY RISER DIAGRAM REQUIRED.
  
 REVIEW BY KEN STEVENS (561) 569-8096
 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2001-05-11 Cont ID  
Sent By jwitmer Date 2001-05-11 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2001-05-11 Time 07:28 Sent To  
Notes
***NONE***