| Plan Review Stops For Permit 01041427 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-09-27 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | | | | BUILDING COMMENTS | | | ----------------- | | | | | | NEW BATHROOM REVISION: | | | | | | COUNTY IMPACT FEES ARE REQUIRED. | | | SUBMIT WALL SECTION FOR NEW ADDTION ON | | | SECOND FLOOR. | | | PROVIDE WIND LOAD COMPLIANCE FOR | | | WINDOWS. | | | | | | | | | L. MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-06-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-06-22 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-06-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-06-15 |
Time |
09:55 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-15 00:00:00 | NO CHANGE IN PLANS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-11 |
Time |
06:29 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2001-05-11 |
Time |
06:30 |
Sent To |
|
|
| Notes |
| 2001-05-11 00:00:00 | PERMIT # 01041427 | | | 901 35TH STREET | | | O/B ROSSELLA MAZZITELLI | | | H 366-0026 | | | O 805-6150 X 2208 | | | | | | 1)- PLANS THAT ARE DESIGNED BY ARCHITECT | | | OR ENGINEERS ARE REQUIRED TO BE SIGNED | | | DATED & SEALED BY THE DESIGN PROFESSION- | | | AL 471.025 / 481.221. | | | | | | 2)- GENERAL NOTE # 10,ENGINEER'S SEAL | | | IS FOR APPROVAL OF STRUCTURAL DESIGN | | | ONLY, --NO SEAL-- | | | | | | 3)- FLORIDA ROOM, REMOVAL OF WALL | | | SECTIONS, WHAT TYPE OF CONSTRUCTION ARE | | | WE DEALING WITH, FRAME OR CBS? WHAT TYPE | | | OF SUPPORT IS HOLDING UP THE SSECOND | | | FLOOR, IS THE SECOND FLOOR LOAD TRANSFER | | | ED TO THIS WALL SYSTEM. | | | | | | 4)- SBC 104.2.2 ADDITIONAL INFORMATION: | | | KITCHEN SHOW ELEVATIONS OF CABINETRY | | | | | | 5)- REMODELED BATH IS THERE A EXHAUST | | | FAN OR A WINDOW WITH A OPEN AREA OF | | | AT LEAST 3'-0" SQUARE FEET. | | | | | | 6)- ROOFING, WHAT TYPE OF ROOF, WHAT IS | | | THE PITCH OF THE ROOF AND WHAT TYPE OF | | | MATERIALS ARE GOING TO BE REPLACED? | | | ROOFING PRODUCT APPROVAL WILL BE | | | REQUIRED EITHER SBCCI OR DADE COUNTY | | | PRODUCT APPROVAL REPORTS ACCEPTTED. | | | | | | 7)- ARE THERE GOING TO HAVE ANY WINDOWS | | | REPLACED, IF SO, OVER 50% REPLACEMENT | | | WILL REQUIRE LARGE MISSLE IMPACT TESTING | | | OR APPROVED STORM SHUTTERS. THE CITY | | | ACCEPTS SBCCI OR DADE COUNTY REPORTS. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-17 |
Time |
19:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-17 |
Time |
19:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-06-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-29 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-29 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-12 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-12 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2001-06-12 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | NOT DONE TO CODE. PLEASE SEE ART 220 | | | OF THE NEC. | | | HEAT STRIPS FOR AHU`S ARE DERATED AT 40% | | | W/ OTHER LOADS. | | | | | | 2) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | PLEASE NOTE THAT ONLY ONE AHU IS SHOWN | | | AND NO COND UNIT`S ARE SHOWN??PLEASE | | | SHOW. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 6)NOTE: PLEASE CLARIFY LIGHTING FOR | | | HABITABLE ROOMS PER 210-70. TOWER RM AND | | | FLORIDA ROOM | | | | | | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | 8)NOTE: PLEASE NOTE OUTLET REQ`D FOR UP- | | | -STAIRS HALL PER 210-52H | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-10 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-10 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2001-05-10 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOT ETHAT PLANS THAT ARE | | | DONE BY AN ARCH/ENGINEER, NEED TO BE | | | SIGNED AND SEALED BY THAT ARCH/ENG OF | | | RECORD. 471.025 481.221 | | | | | | 2)NOTE: PLEASE NOTE THAT NOT ENOUGH | | | ELECTRICAL DEATIL WAS SUBMITTED FOR | | | PROPER REVIEW OF PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-19 |
Time |
09:38 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-09-19 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2001-09-19 00:00:00 | MECHANICAL PERMIT ISSUED WITHOUT PLANS | | | BEING REVIEWED.THIS STOP IS NOT A | | | REVISION IT IS A NEW SUBMITTAL. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-05-07 |
Time |
20:01 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-05-07 |
Time |
20:01 |
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | NOT ENOUGH INFORMATION; | | | | | | SUBMIT A/C PLANS WITH A/C APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-06-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-29 |
Time |
12:19 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2001-06-29 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-12 |
Time |
12:33 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-06-12 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-07 |
Time |
12:36 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-05-07 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | REVIEW NOTES.FAILED | | | | | | (1) PLANS TO BE SIGNED AND SEALED. | | | | | | (2) SANITARY RISER DIAGRAM REQUIRED. | | | | | | REVIEW BY KEN STEVENS (561) 569-8096 | | | EXT. 8377 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2001-05-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-11 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-05-11 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|