Plan Review Details - Permit 01041416
Plan Review Stops For Permit 01041416
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-10 Cont ID  
Sent By btrobaug Date 2002-09-10 Time 14:37 Rev Time 0.50
Received By btrobaug Date 2002-09-04 Time 16:36 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-14 Cont ID  
Sent By jleahy Date 2001-12-14 Time 12:50 Rev Time 1.00
Received By jleahy Date 2001-12-14 Time 12:24 Sent To  
Notes
2001-12-14 00:00:001.LOAD CALCULATION IS NOT COMPLETE
 SHOW EXISTIBNG LOADS AND NEW LOADS
 PER THE NEC.
  
 2.PANEL SCHEDULE IS NOT COMPLETE.YOU
 NEED TO SHOW EXISTING AND NEW LOADS
 ALSO!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
  
 3.NEED TO SHOW LIGHT SWITCH FOR KITCHE
 LIGHTING WHEN YOU ENTER FROM THE
 ENTERTAINMENT AREA!!!!!!!!!!!!!!!
  
 4.OUTLET SPACING IS NOT TO LOCAL CODE.
  
 5.ON THE PANEL SCHEDULE YOU NEED TO
 DISTINGUISH BETWEEN NEW AND OLD
 CIRCUITS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-14 Cont ID  
Sent By dpalmer Date 2001-05-14 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2001-05-14 Time 17:25 Sent To  
Notes
2001-05-14 00:00:00*************UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 AND CALCULATIONS DO NOT CORRELATE WITH
 PLANS OR PERMIT APPLICATION.
 WHERE IS EXISTING ELEC ON PANEL
 SCHEDULE? PLEASE PROVIDE CLARIFICATION
 ON LOADS NOW SHOWN AND EXISTING. SQ FT
 CALCS DO
 NOT MATCH, PERMIT APP SAYS ADDING 2ND
 KITCHEN AND LOAD CALCS AND PANEL
 SCHEDULE SHOWS ONLY ONE??? SERVICE
 RISER AND
 CALCULATIONS NEED TO BE DONE TO ALL
 NEC CALCULATION METHODS. 215-5 AND 220
  
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATINGS OF BRANCH BRKRS ARE
 SUBMITTED BUT NOTHING FOR MAIN?
  
 3)NOTE: PLEASE NOTE MEANS OF EGRESS
 LIGHTING FROM 2ND KITCHEN INTO
 ENTERAINMENT AREA.
  
 4)N0TE:PLEASE NOTE RISER SHOWING 23 POLE
 PANEL?? THERE IS NO SUCH # EITHER24,30,
 36. ETC
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6. ALL OUTLETS IN PREP
 AREA.
  
 6) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 7)NOTE: PLEASE CLARIFY A/C BEING SHOWN
 ON PANEL SCHEDULE?? IS THIS NEW OR
 EXSITING?? IF NEW SHOW A/C LOCATIONS
 WITH DISC 440-11 AND OUTLET PER 309.1.
  
 8) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 SMOKE DETECTOR REQ`D IN COMMON AREA.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-12-14 Cont ID  
Sent By pkrauss Date 2001-12-14 Time 14:38 Rev Time 0.30
Received By pkrauss Date 2001-12-14 Time 14:35 Sent To  
Notes
2001-12-14 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-12 Cont ID  
Sent By hmoser Date 2001-05-12 Time 06:40 Rev Time 0.33
Received By hmoser Date 2001-05-12 Time 06:39 Sent To  
Notes
2001-05-12 00:00:00DENIED
  
 NO A/C PLANS OR ENERGY CALKS.SUBMIT FOR
 REVIEW

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-12-14 Cont ID  
Sent By btrobaug Date 2002-10-09 Time 14:38 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-14 00:00:00REVISED ISOMETRIC,OK. W/M EX.PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-07 Cont ID  
Sent By kstevens Date 2001-05-07 Time 15:03 Rev Time 0.33
Received By kstevens Date 2001-05-07 Time 15:03 Sent To  
Notes
2001-05-07 00:00:00REVIEW NOTES.FAILED
  
 SUBMIT SANITARY RISER DIAGRAM THAT
 REFLECTS FLOOR PLAN OF ADDITION.
 NO WASHMACHINE SHOWN ON FLOOR PLAN,
 AND ONLY ONE 1/2 BATH ON FLOOR PLAN
 NOT TWO FULL BATHS.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-12-17 Cont ID  
Sent By jgomez Date 2001-12-17 Time 11:43 Rev Time 2.50
Received By jgomez Date 2001-12-15 Time 15:54 Sent To  
Notes
2001-12-17 00:00:00SECOND CHECKLIST:
 1-SOIL TEST REPORT TO HAVE EMBOSSED SEAL
 AND ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 2-ENGINEER OF RECORD TO REVIEW THE SOIL
 TEST REPORT. RECOMMENDATIONS FOR
 PILING FOUNDATION WAS IGNORED.
 -ENGINEER TO PROVIDE CALCULATIONS FOR
 PILING FOUNDATION DESIGN.
 -PROVIDE COMPLETE PLANS, DETAILS AND
 SPECIFICATIONS FOR PILING SYSTEM TO BE
 USED, INCLUDING PILING INSTALLATION
 METHOD AS REQUIRED. SEE CHAPTER 18 OF
 SBC 1997 AND SEC. 104.2.2 OF CITY
 AMENDMENTS TO SBC 1997.
 3-PLOT PLAN DOESN'T MATCH FLOOR PLAN AND
 FOUNDATION PLANS. REVISE AS REQUIRED.
 4-PROVIDE COMPLETE ROOF FRAMING PLAN
 SHOWING UPLIFT CALCULATIONS AND ANCHOR
 SCHEDULE. INCLUDE FRAMING OVER EXIST'G
 ROOF. NOTE THAT NEW ROOF IS HIGHER
 THAN EXISTING ONE.
 -CLEARLY IDENTIFY BEARING WALL FOR NEW
 ROOF TRUSSES. SEE ENGINEERED TRUSS
 DRAWINGS FOR LOCATION OF BEARING
 POINTS FOR EACH TRUSS.
 5-SPECIFY DESIGN PRESSURES CALCULATED
 AT EACH EXTERIOR OPENING AS REQUIRED
 BY SECTION 1606 SBC 1997.
 6-PROVIDE GABLE END WALL SECTION AND
 CLEARLY SPECIFY ALL FASTENERS.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 7-SHOW LEFT SIDE EXTERIOR ELEVATION.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 8-NEED ADDITIONAL DEEPER BORINGS AS
 REQUIRED ON THE SOIL TEST REPORT TO
 VERIFY DESIGN CAPACITIES OF PILING
 FOUNDATION SYSTEM. ENGINEER OF RECORD
 NEEDS THIS INFORMATION TO DESIGN PILES
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 9-EXT. DOOR PRODUCT APPROVAL EXPIRED.
 LETTER FOR PRODUCT APPROVAL RENEWAL &
 PRODUCT APPROVAL DON'T MATCH. SEE THE
 # FOR PRODUCT APPROVAL.
 10-TRUSS DRAWINGS:
 A)ENGINEER TO SIGN, SEAL AND DATE ALL
 TRUSS DRAWINGS, INCLUDING THE TRUSS
 LAYOUT AS REQUIRED BY CHAPTER 471 OF
 FLORIDA STATUTES.
 B)ENGINEER OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO SUBMITTAL TO
 THIS OFFICE. USE STANDARD REVIEW STAMP
 C)VERIFY BEARING POINTS FOR TRUSSES
 T1A AND T1B. THERE IS NOT BEARING WALL
 AT BOTH ENDS OF TRUSSES. SEE PLANS.
 C)SPECIFY CONNECTORS FOR TRUSSES V-32
 THRU V-12.
 D)DESIGN CRITERIA USED DOESN'T MATCH
 DESIGN CRITERIA USED BY ENGINEER OF
 RECORD: SBC 97 FOR 110 MPH.
 NOTE: IF USING ASCE 7, THEN UPDATE
 FOR ASCE 7-95 (NOT ASCE 7-93) FOR
 140 MPH.
 E)ENGINEERED TRUSSES NOTE FOR 8FT ABOVE
 GROUND LEVEL IS INCORRECT. THIS IS NOT
 A FLAT ROOF BUT AN SLOPED ROOF.
 THEREFORE, THE MEAN ROOF HEIGHT SHALL
 BE TAKEN FROM GRADE TO THE AVERAGE
 POINT OF THE ROOF. REVISE AS REQUIRED.
 11-BRING PAID RECEIPT FOR IMPACT FEES.
 12-CLARIFY WHAT IS THE TRUSS GIRDER
 NOTE SHOWN ON FLOOR PLAN SHEET 3 OF 8.
 13-ENGINEER OF RECORD TO HAVE ALL HIS
 INFORMATION ON ALL DRAWINGS AS REQ'D
 BY CHAPTER 471 OF FLORIDA STATUTES.
 14-SEE COMMENTS BY ZONING AND BY THE
 OTHER TRADES.
 15-PROVIDE ENERGY CALCULATIONS ON FORM
 600-97. AS REQUIRED BY FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 16-PROVIDE RECORDED NOTICE OF
 COMMENCEMENT.
 17-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR SEPARATE
 PERMIT.
 18-VALUE DECLARED FOR CONSTRUCTION IS
 TOO LOW. OWES $928.97 FOR UPDATED
 VALUE AND RADON FEES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-06-01 Cont ID  
Sent By jgomez Date 2001-06-01 Time 14:07 Rev Time 2.50
Received By jgomez Date 2001-06-01 Time 14:07 Sent To  
Notes
2001-06-01 00:00:00CHECKLIST:
 1-DESIGNER IS NOT A REGISTERED ARCHITECT
 OR ENGINEER. DESIGNER SHALL USE THE
 PRESCRIPTIVE STANDARD SSTD 10-97 TO
 DESIGN THIS STRUCTURE. SEC. 104.2.3
 OF CITY AMENDMENTS TO SBC 1997.
 -DESIGNER TO USE SSTD 10-97 CHAPTER TWO
 TO DESIGN:
 -FOOTINGS AND FOUNDATIONS.
 -WALL SYSTEMS. SHOW SHEARWALLS
 LOCATIONS AND REINFORCEMENT.
 -SHOW REINFORCEMENT AT CORNERS.
 -SHOW REINFORCEMENT AT OPENINGS.
 -SHOW RAKE BEAM SIZE & REINFORCEMENT.
 2-PROVIDE SOIL TEST REPORT.
 SECTION 1804.2.2 CITY AMENDMENTS.
 3-PROVIDE COMPLETE ROOF FRAMING PLAN AND
 ANCHOR SCHEDULE.
 SECTION 104.2.2 CITY AMENDMENTS.
 4-PROVIDE ENERGY CALCULATIONS.
 5-PROVIDE NOTICE OF COMMENCEMENT.
 6-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS:
 -KEY PLAND AND COMPLETE INSTALLATION
 SCHEDULE (SEE ATTACHED CITY SAMPLE).
 -PROVIDE STORM PANELS PRODUCT APPROVAL
 AND CIRCLE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHORS TO BE
 USED ACCORDING TO THE MEAN ROOF HEIGHT
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO (CONCRETE BLOCK).
 7-PROVIDE ATTIC ACCESS. SECTION 2309.6
 SBC 1997.
 8-SPECIFY UPLIFT ANCHOR FOR GABLE END
 ROOF TRUSS. SEC 104.2.2 CITY AMENDMENT
 9-ZONING ONLY ALLOWS ONE KITCHEN PER
 RESIDENCE. PROVIDE DRAWINGS SHOWING
 WHAT IS GOING TO BE DONE ON EXISTING
 KITCHEN.
 10-SEE COMMENTS BY THE OTHER TRADES AND
 RETURN REVIEWED SET AFTER CORRECTIONS
 ARE DONE TO THE ORIGINAL DRAWINGS IN
 ORDER TO EXPEDITE THE REVIEW PROCESS.
 11-PROVIDE CURRENT PRODUCT APPROVAL FOR:
 -EXTERIOR DOOR. (SUBMITTED ONE EXPIRED)
 12-DESIGNER CAN NOT FILL AND SIGN THE
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM. THIS IS TO BE FILLED
 AND SEALED BY A REGISTER ARCHITECT OR
 ENGINEER ONLY.
 13-VALUE DECLARED FOR CONSTRUCTION IS
 TOO LOW. OWES $928.97 FOR UPDATED
 VALUE AND RADON FEES.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-08-27 Cont ID  
Sent By sgraham Date 2002-08-27 Time 11:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-12-17 Cont ID  
Sent By sgraham Date 2001-05-01 Time 11:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-12-17 00:00:00DENIED BY ZONING, CAN NOT HAS 2-KITCHENS
 IN SF-7 DISTRICT. YOU MAY HAVE A WET BAR
 NOT A FULL KITCHEN 12-17-01
 PLOT PLAN DO NOT MATCH FLOOR PLAN,
 PLEASE CORRECT. SUBMIT A SURVEY