Plan Review Details - Permit 01041406
Plan Review Stops For Permit 01041406
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-20 Cont ID  
Sent By jwitmer Date 2001-07-20 Time 07:47 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-20 00:00:00PROVISO: STORM SHUTTERS UNDER SEPERATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-17 Cont ID  
Sent By jwitmer Date 2001-05-17 Time 10:36 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-17 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01041406
 117 GREGORY RD.
 J. L. HAWKINS CONST.
 966- 6383
  
 1)- OWNER WILL NEED TO APPLY TO MAKE
 APPLICATION TO THE CONSTRUCTION BOARD
 OF ADJUSTMENT & APPEAL TO OBTAIN A
 VARIANCE. THE MINIMUM FLOOR HEIGHT IN A
 A-5 FLOOD ZONE IS 7'-6" BY CITY CODE
 CHAPTER 12 FLOOD PREVENTION & CONTROL.
 SECTION 12-22.3(1) A COPY OF CHAPTER 12
 IS ATTACHED AN A COPY OF AN APPLICATION
 FOR THE CONSTRUCTION BOARD OF
 ADJUSTMENT & APPEALS. A COPY OF ASSESED
 MAKET VALUE OF THE STRUCTURE IS ALSO
 INCLUDED. THIRD IS A COPY OF THE CITY
 ADMINISTRATIVE CODE THAT DEALS WITH
 THE ESTABLISHMENT OF THE BOARD OF ADJUST
 MENT & APPEAL ESTABLISHED BY THIS ORDINA
 NCE.
  
 ONCE APPROVED BY THE BOARD OF ADJUSTMENT
 & APPEAL AND ALL CORRECTIONS THAT ARE
 REQUIRED BY THE SUB TRADES, THE CONTRACT
 OR WILL TAKE THE PLANS TO THE COUNTY
 BUILDING DEPARTMENT TO BE ASSESED FOR
 COUNTY IMPACT FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX.8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2001-05-14 Time 22:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-20 Cont ID  
Sent By jleech Date 2001-07-20 Time 14:50 Rev Time 0.33
Received By jleech Date 2001-07-20 Time 14:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-14 Cont ID  
Sent By hmoser Date 2001-05-14 Time 18:13 Rev Time 0.33
Received By hmoser Date 2001-05-14 Time 18:13 Sent To  
Notes
2001-05-14 00:00:00NO ENGINEER SEAL ON PLANS

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-20 Cont ID  
Sent By jleech Date 2001-07-20 Time 14:50 Rev Time 0.33
Received By jleech Date 2001-07-20 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-12 Cont ID  
Sent By kstevens Date 2001-05-12 Time 13:48 Rev Time 0.25
Received By kstevens Date 2001-05-12 Time 13:48 Sent To  
Notes
2001-05-12 00:00:00REVIEW NOTES. ...FAILED...
  
 1) HORIZONTAL DRY VENTS ARE NOT ALLOWED
 PER SPC-94 SECTION 906.2.1. SUBMIT
 SANITARY RISER DIAGRAM WITH PLUMBING
 PERMIT APPLICATION.
  
 2) TEMP./PRESSURE RELIEF LINE FROM WATER
 HEATER SHALL COMPLY WITH SPC-94 SECT.
 507.8.4
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-30 Cont ID  
Sent By sgraham Date 2001-04-30 Time 15:03 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***