| Plan Review Stops For Permit 01041279 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-10 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-10 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-04-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-27 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-27 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2001-04-27 00:00:00 | 1) FIRE ALARM NOTES INDICATES THAT | | | CLASS B, STYLE C FIRE ALARM CIRCUITS | | | WILL BE INSTALLED. ONLY CLASS A, STYLE | | | D FIRE ALARM CIRCUITS WILL BE | | | ACCEPTABLE. | | | 2) FIRE ALARM NOTES INDICATES THAT DUCT | | | SMOKE DETECTORS WILL CAUSE A SUPERVISORY | | | SIGNAL ONLY. DUCT SMOKE DETECTORS WHEN | | | ACTVIATED ARE TO CAUSE AIR HANDLING | | | EQUIPMENT TO SHUT DOWN AND CAUSE THE | | | FIRE ALARM SYSTEM TO ACTIVATE. | | | 3) PULL STATIONS ARE NOT REQUIRED IN | | | MERCANTILE OCCUPANCIES WHEN THE BUILDING | | | IS COMPLETELY FIRE SPRINKLER PROTECTED. | | | 4) VALUE OF JOB LISTED ON PERMIT | | | APPLICATION APPEARS TO BE LOW. PLEASE | | | PROVIDE COPY OF CONTRACT FOR | | | VERIFICATION PURPOSES. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|