| Plan Review Stops For Permit 01041205 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-10 |
Time |
17:54 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-08 |
Time |
18:15 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-08 00:00:00 | PLAN REVIEW: 01041205 | | | 1400 NORTHPOINT PARKWAY | | | SUITE # 10 | | | BUTTERS CONSTRUCTION | | | PHONE 954/570-8111 EX.34 | | | FAX954/570-8844 | | | | | | INCLUDED IS A COPY OF THE PROSIVO FOR | | | THE TENANT BUILDOUT. IN THIS PROVISO | | | THE ADDITIONAL INFORMATION REQUIRED | | | FOR THE REMAINDER OF THE TENANT BUILDOUT | | | WAS TO BE PROVIDED. | | | THE PERMIT AND REQUIRED INFORMATION FOR | | | THE DECK AS WELL AS THE 500 GAL NITROGEN | | | TANK. | | | | | | THE ITEMS LISTED BELOW ARE THE SAME | | | ITEMS THAT WERE LISTED ON THE REVIEW OF | | | 4/27/01 (BROUGHT IN AS A REVISION). | | | | | | 1)- HOW WILL THE TANK BE FASTENED TO THE | | | SLAB TO RESIST OVERTURNING IN A CASE OF | | | A HURRICANE? IS THERE A SAFETY FACTOR | | | FIGURED IN TO THE FORMULA? | | | | | | 2)- THE AREA NEXT TO THE NITROGEN TANK | | | IS TO BE USED FOR A LOUNGE AREA, WHAT | | | SAFETY FEATURES ARE TO BE CONSIDERED FOR | | | GAS LEAKS, THE CONCERN IS SIMPLE | | | ASPHYXIATION. | | | | | | 3)- THE INTERIOR BUILD OUT HAD THE 2 | | | DOORS LEADING INTO THE SCREEN ENCLOSURE | | | AS EXIT DOORS, SHOW PATH OF TRAVEL, AND | | | OCCUPANT LOAD TAKEN BY THE REMAINING | | | DOORS. | | | | | | 4)- ITEM #5 OF THE PROVISO: THE | | | ARCHITECT WILL CORRECT THE FLOOR DRAIN | | | SHOWN IN THE ISOMETRIC FOR THE CONTAIN- | | | MENT ROOM, NOT CORRECTED AS OF PLANS SUB | | | MITTED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-05-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-11 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-11 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2001-05-11 00:00:00 | 1) PROVIDE MORE DETAILS ON CHEMICAL | | | HOOD(S) PLANNED FOR USE. | | | 2) ALL APPROPRIATE WARNING SIGNAGE IS | | | TO BE PROVIDED THROUGHOUT THE BUILDING. | | | THESE INCLUDE "NO SMOKING","FLAMMABLE | | | GAS", "ENTRY BY AUTHORIZED PERSONNEL | | | ONLY" AND OTHER APPROPRIATE SIGNAGE. | | | 3) COMPLIANCE WITH CITY HAZARDOUS | | | MATERIALS ORDINANCE IS REQUIRED. | | | 4) ALL WORK AND CHEMICAL STORAGE SUBJECT | | | TO FIELD INSPECTOR'S APPROVAL. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-09 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-09 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2001-05-09 00:00:00 | 1) NO MATERIAL SAFETY DATA SHEETS | | | PROVIDED WITH PLANS. NO INFORMATION | | | SHEETS PROVIDED FOR THE ARGON, HELIUM, | | | NITROGEN, HYDROGEN, AND METHANE. | | | 2) ACCORDING TO THE LETTER PROVIDED | | | WITH THE PLANS, A SEPARATE PERMIT WILL | | | COVER THE INSTALLATION OF THE NITROGEN | | | TANK. THE NITROGEN TANK IS NOT TO BE | | | INSTALLED UNTIL THE PROPOSED PERMIT | | | IS APPROVED BY THE CITY. | | | 3) THE PLANS OR LETTER DOES NOT REFLECT | | | COMPLIANCE WITH THE HAZARDOUS MATERIALS | | | ORDINANCE, CITY CODE 3206-99. | | | 4) ONLY ONE CONTINGENCY PLAN HAS BEEN | | | SUBMITTED TO THE CITY. | | | 5) ALL OF THE REQUIREMENTS OF NFPA 99 | | | THAT ARE APPLICABLE SHALL BE MET. | | | 6) ALL OF THE APPLICABLE REQUIREMENTS OF | | | NFPA 45 ARE TO BE MET. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-06-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-06-30 |
Time |
07:16 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-06-30 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-10 |
Time |
15:39 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-10 00:00:00 | PLUMBING PLAN REVIEWPROVISO | | | AIR CHAMBERS TO COMPLY W/SPC 94 | | | SEC 607.8.3,TO BE ACCESSIBLE, | | | RECHARGEABLE. END OF COMMENTS | | | QUESTIONS561-659-8096 X 8233 | | | 4TIMES FEE DUE, VALUE $ 17,500.00 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-05-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-08 |
Time |
17:29 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-08 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1) FIRE PROTECTION OF RATED ASSEMBLIES, | | | SPC 94 SEC 104.2.4 | | | (2) MSDS SHTS FOR CHEMICALS & GAS THAT | | | WILL BE STORED & USED,SPC 94 SEC 104.2.6 | | | (3) RM #155 FLOOR DRAIN, IS PROHIBITED | | | FROM BEING CONNECTED TO SANITARY SYSTEM, | | | SPS 94 SEC 701.5 | | | (4) AIR CHAMBERS TO COMPLY WITH SPC 94 | | | SEC 607.8.3 ACCESSIBLE,RECHARGEABLE. | | | (5) PROVIDE INFORMATION FOR THE VALUE | | | OF PIPING INSTALLATION & EQUIPMENT. | | | THIS IS NEEDED TO CALCULATE PERMIT FEE, | | | 4 TIMES THE FEE IS DUE BEFORE PERMIT IS | | | ISSUED. | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-08 |
Time |
10:57 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-03 |
Time |
10:28 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-03 00:00:00 | PLUMBING PLAN REVIEW, DENIED | | | (1) THIS PLAN IS BEING REIEWED FOR | | | COMPLIANCE WITH STD BLDG,MECH, PLBG AND | | | NFPA 45,99 LABORATORIES, NFPA 70. | | | ALL INFORMATIONTO BE PROVIDE ON | | | PLANS OR MFG. CUT SHTS. | | | COMBINE ALL SYSTEMS ON ONE PACKAGE FOR | | | PLAN REVIEW THIS INC. BLDG, MECH. VENTS | | | ELECTRICAL, PLUMBING GAS PIPING. | | | PLANS AS SUBMITTED ARE VAGUE AND | | | MISLEADING. | | | END OF COMMENTS PAUL SCHMITZ | | | 561-659-8096 X 8233 |
|
|