Plan Review Details - Permit 01041205
Plan Review Stops For Permit 01041205
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-05-10 Cont ID  
Sent By jwitmer Date 2001-05-10 Time 17:54 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-08 Cont ID  
Sent By jwitmer Date 2001-05-08 Time 18:15 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-08 00:00:00PLAN REVIEW: 01041205
 1400 NORTHPOINT PARKWAY
 SUITE # 10
 BUTTERS CONSTRUCTION
 PHONE 954/570-8111 EX.34
 FAX954/570-8844
  
 INCLUDED IS A COPY OF THE PROSIVO FOR
 THE TENANT BUILDOUT. IN THIS PROVISO
 THE ADDITIONAL INFORMATION REQUIRED
 FOR THE REMAINDER OF THE TENANT BUILDOUT
 WAS TO BE PROVIDED.
 THE PERMIT AND REQUIRED INFORMATION FOR
 THE DECK AS WELL AS THE 500 GAL NITROGEN
 TANK.
  
 THE ITEMS LISTED BELOW ARE THE SAME
 ITEMS THAT WERE LISTED ON THE REVIEW OF
 4/27/01 (BROUGHT IN AS A REVISION).
  
 1)- HOW WILL THE TANK BE FASTENED TO THE
 SLAB TO RESIST OVERTURNING IN A CASE OF
 A HURRICANE? IS THERE A SAFETY FACTOR
 FIGURED IN TO THE FORMULA?
  
 2)- THE AREA NEXT TO THE NITROGEN TANK
 IS TO BE USED FOR A LOUNGE AREA, WHAT
 SAFETY FEATURES ARE TO BE CONSIDERED FOR
 GAS LEAKS, THE CONCERN IS SIMPLE
 ASPHYXIATION.
  
 3)- THE INTERIOR BUILD OUT HAD THE 2
 DOORS LEADING INTO THE SCREEN ENCLOSURE
 AS EXIT DOORS, SHOW PATH OF TRAVEL, AND
 OCCUPANT LOAD TAKEN BY THE REMAINING
 DOORS.
  
 4)- ITEM #5 OF THE PROVISO: THE
 ARCHITECT WILL CORRECT THE FLOOR DRAIN
 SHOWN IN THE ISOMETRIC FOR THE CONTAIN-
 MENT ROOM, NOT CORRECTED AS OF PLANS SUB
 MITTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-05-11 Cont ID  
Sent By mcarsill Date 2001-05-11 Time 08:30 Rev Time 0.00
Received By mcarsill Date 2001-05-11 Time 08:30 Sent To  
Notes
2001-05-11 00:00:001) PROVIDE MORE DETAILS ON CHEMICAL
 HOOD(S) PLANNED FOR USE.
 2) ALL APPROPRIATE WARNING SIGNAGE IS
 TO BE PROVIDED THROUGHOUT THE BUILDING.
 THESE INCLUDE "NO SMOKING","FLAMMABLE
 GAS", "ENTRY BY AUTHORIZED PERSONNEL
 ONLY" AND OTHER APPROPRIATE SIGNAGE.
 3) COMPLIANCE WITH CITY HAZARDOUS
 MATERIALS ORDINANCE IS REQUIRED.
 4) ALL WORK AND CHEMICAL STORAGE SUBJECT
 TO FIELD INSPECTOR'S APPROVAL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-09 Cont ID  
Sent By mcarsill Date 2001-05-09 Time 11:14 Rev Time 0.00
Received By mcarsill Date 2001-05-09 Time 11:14 Sent To  
Notes
2001-05-09 00:00:001) NO MATERIAL SAFETY DATA SHEETS
 PROVIDED WITH PLANS. NO INFORMATION
 SHEETS PROVIDED FOR THE ARGON, HELIUM,
 NITROGEN, HYDROGEN, AND METHANE.
 2) ACCORDING TO THE LETTER PROVIDED
 WITH THE PLANS, A SEPARATE PERMIT WILL
 COVER THE INSTALLATION OF THE NITROGEN
 TANK. THE NITROGEN TANK IS NOT TO BE
 INSTALLED UNTIL THE PROPOSED PERMIT
 IS APPROVED BY THE CITY.
 3) THE PLANS OR LETTER DOES NOT REFLECT
 COMPLIANCE WITH THE HAZARDOUS MATERIALS
 ORDINANCE, CITY CODE 3206-99.
 4) ONLY ONE CONTINGENCY PLAN HAS BEEN
 SUBMITTED TO THE CITY.
 5) ALL OF THE REQUIREMENTS OF NFPA 99
 THAT ARE APPLICABLE SHALL BE MET.
 6) ALL OF THE APPLICABLE REQUIREMENTS OF
 NFPA 45 ARE TO BE MET.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-06-30 Cont ID  
Sent By jleech Date 2001-06-30 Time 07:16 Rev Time 1.50
Received By jleech Date 2001-06-30 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-05-10 Cont ID  
Sent By pschmitz Date 2001-05-10 Time 15:39 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-10 00:00:00PLUMBING PLAN REVIEWPROVISO
 AIR CHAMBERS TO COMPLY W/SPC 94
 SEC 607.8.3,TO BE ACCESSIBLE,
 RECHARGEABLE. END OF COMMENTS
 QUESTIONS561-659-8096 X 8233
 4TIMES FEE DUE, VALUE $ 17,500.00

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-05-08 Cont ID  
Sent By pschmitz Date 2001-05-08 Time 17:29 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-08 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) FIRE PROTECTION OF RATED ASSEMBLIES,
 SPC 94 SEC 104.2.4
 (2) MSDS SHTS FOR CHEMICALS & GAS THAT
 WILL BE STORED & USED,SPC 94 SEC 104.2.6
 (3) RM #155 FLOOR DRAIN, IS PROHIBITED
 FROM BEING CONNECTED TO SANITARY SYSTEM,
 SPS 94 SEC 701.5
 (4) AIR CHAMBERS TO COMPLY WITH SPC 94
 SEC 607.8.3 ACCESSIBLE,RECHARGEABLE.
 (5) PROVIDE INFORMATION FOR THE VALUE
 OF PIPING INSTALLATION & EQUIPMENT.
 THIS IS NEEDED TO CALCULATE PERMIT FEE,
 4 TIMES THE FEE IS DUE BEFORE PERMIT IS
 ISSUED.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 2 Status F Date   Cont ID  
Sent By pschmitz Date 2001-05-08 Time 10:57 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-03 Cont ID  
Sent By pschmitz Date 2001-05-03 Time 10:28 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-03 00:00:00PLUMBING PLAN REVIEW, DENIED
 (1) THIS PLAN IS BEING REIEWED FOR
 COMPLIANCE WITH STD BLDG,MECH, PLBG AND
 NFPA 45,99 LABORATORIES, NFPA 70.
 ALL INFORMATIONTO BE PROVIDE ON
 PLANS OR MFG. CUT SHTS.
 COMBINE ALL SYSTEMS ON ONE PACKAGE FOR
 PLAN REVIEW THIS INC. BLDG, MECH. VENTS
 ELECTRICAL, PLUMBING GAS PIPING.
 PLANS AS SUBMITTED ARE VAGUE AND
 MISLEADING.
 END OF COMMENTS PAUL SCHMITZ