Review Stop FS  
Rev No 1 Status P Date 2001-04-24 Cont ID  
Sent By mcarsill Date 2001-04-24 Time 13:41 Rev Time 0.00
Received By mcarsill Date 2001-04-24 Time 13:41 Sent To  
Notes
2001-04-24 00:00:001) A SPARE HEAD BOX IS TO BE PROVIDED.
 2) UNDERGOUND FIRE MAINS TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 24.
 3) HOW IS THE FIRE MAIN BEING
 RESTRAINED.
 4) EXISTING BACKFLOW DEVICE IS TO BE
 CHAINED AND LOCKED AND TAMPER SWITCHES
 INSTALLED SINCE NO INDICATING VALVES ARE
 SHOWN NEAR THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910