| Plan Review Stops For Permit 01041099 |
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-04-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-24 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-24 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FS |
|
| Rev No |
1 |
Status |
P |
Date |
2001-04-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-24 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-24 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2001-04-24 00:00:00 | 1) A SPARE HEAD BOX IS TO BE PROVIDED. | | | 2) UNDERGOUND FIRE MAINS TO BE | | | INSTALLED IN ACCORDANCE WITH NFPA 24. | | | 3) HOW IS THE FIRE MAIN BEING | | | RESTRAINED. | | | 4) EXISTING BACKFLOW DEVICE IS TO BE | | | CHAINED AND LOCKED AND TAMPER SWITCHES | | | INSTALLED SINCE NO INDICATING VALVES ARE | | | SHOWN NEAR THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|