Plan Review Details - Permit 01041080
Plan Review Stops For Permit 01041080
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-08-02 Cont ID  
Sent By hpiskura Date 2001-08-02 Time 13:36 Rev Time 0.00
Received By hpiskura Date 2001-08-02 Time 10:34 Sent To  
Notes
2001-08-02 00:00:00PROVISO:MUST HAVE PRODUCT AND OR TEST
 REPORTS FOR ROOF COVERING SYSTEM,
 WINDOWS AND HURRICANE MISSILE IMPACT
 FOR THE GLAZING.
  
 PAY IMPACT FEES TO THE COUNTY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-14 Cont ID  
Sent By dpalmer Date 2001-08-14 Time 21:06 Rev Time 0.00
Received By dpalmer Date 2001-08-14 Time 20:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-14 Cont ID  
Sent By dpalmer Date 2001-05-14 Time 16:41 Rev Time 0.00
Received By dpalmer Date 2001-05-14 Time 16:41 Sent To  
Notes
2001-05-14 00:00:00NOTES ON BLDG"A" #01041075

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-05-02 Cont ID  
Sent By mamini Date 2002-05-02 Time 14:19 Rev Time 4.00
Received By mamini Date 2002-05-02 Time 14:19 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-08-15 Cont ID  
Sent By mamini Date 2001-08-15 Time 12:11 Rev Time 1.00
Received By mamini Date 2001-08-15 Time 12:10 Sent To  
Notes
2001-08-15 00:00:00FAILED :
 1. SEE PERMIT #01041075
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-11-28 Cont ID  
Sent By mcarsill Date 2001-11-28 Time 16:32 Rev Time 0.00
Received By mcarsill Date 2001-11-28 Time 16:32 Sent To  
Notes
2001-11-28 00:00:00ON 11.28.01 RECEIVED A LETTER INDICATING
 THAT THE TRANSFORMER LOCATED NEAR
 AN EXIT DOOR HAS BEEN RELOCATED SO AS
 NOT TO INTERFERE WITH EXITING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-11-16 Cont ID  
Sent By mcarsill Date 2001-11-16 Time 08:36 Rev Time 0.00
Received By mcarsill Date 2001-11-16 Time 08:36 Sent To  
Notes
2001-11-16 00:00:001) FIRE SPRINKLER DRAWINGS LOCATED WITH
 D PLANS DO NOT SHOW INTERIOR OF D
 BUILDING, BUT B AND C.
 2) SITE PLAN FOR RETAIL D INDICATES
 A TRANSFORMER NEAR THE EXIT DOOR. PLEASE
 EXPLAIN RELATIONSHIP OF THIS AREA TO
 EXIT DOOR. NO ITEMS ARE TO BE NEAR
 EXIT DOOR TO INTERFERE WITH EXIT
 DISCHARGE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-20 Cont ID  
Sent By mcarsill Date 2001-08-20 Time 10:42 Rev Time 0.00
Received By mcarsill Date 2001-08-20 Time 10:42 Sent To  
Notes
2001-08-20 00:00:001) IT APPEARS THAT AN EXIT DOOR (C)
 DISCHARGES INTO AN AREA USED FOR A
 DUMPSTER ENCLOSURE WITH GATES. THIS
 ARRANGEMENT IS NOT PERMITTED. THIS EXIT
 IS REQUIRED SINCE THE OTHER TWO EXITS
 DO NOT MEET THE 1/2 THE LENGTH OF THE
 AREA OR ROOM SERVED.
 2) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PLEASE SUBMIT FIRE
 SPRINKLER DRAWINGS AND HYDRAULIC
 CALCULATIONS. THE FIRE DEPARTMENT
 CONNECTION IS TO BE WITHIN 150 FEET OF
 A FIRE HYDRANT.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SPRINKLER TRANSMITTER
 PLANNED FOR USE. THE FIRE SPRINKLER
 SYSTEM IS REQUIRED TO BE MONITORED BY
 A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-24 Cont ID  
Sent By pkrauss Date 2001-10-24 Time 13:53 Rev Time 0.40
Received By pkrauss Date 2001-10-24 Time 13:33 Sent To  
Notes
2001-10-24 00:00:00BUILDING "D"
  
 PROVISO:DUCT SMOKE DETECTOR TO ALARM/
 STROBE IN NORMALLY OCCUPIED
 AREAS. (NFPA 90A 4-4.4.3)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-24 Cont ID  
Sent By pkrauss Date 2001-05-24 Time 08:30 Rev Time 2.00
Received By pkrauss Date 2001-05-24 Time 08:30 Sent To  
Notes
2001-05-24 00:00:00NOTES UNDER PERMIT 01041075.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-15 Cont ID  
Sent By pschmitz Date 2001-08-15 Time 14:48 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-08-15 00:00:00PLUMBING PLAN REVIEW, PROVISO.
 RETAIL "D" ONLY. PAUL SCHMITZ

Review Stop Z ZONING
Rev No 1 Status P Date 2001-08-29 Cont ID  
Sent By sgraham Date 2001-08-29 Time 15:24 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-29 00:00:00APPROVED BY MS