Plan Review Details - Permit 01041017
Plan Review Stops For Permit 01041017
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-05-10 Cont ID  
Sent By lmartine Date 2001-05-10 Time 14:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-05 Cont ID  
Sent By dpalmer Date 2001-07-05 Time 13:43 Rev Time 0.00
Received By dpalmer Date 2001-07-05 Time 13:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-10 Cont ID  
Sent By dpalmer Date 2001-05-10 Time 13:13 Rev Time 0.00
Received By dpalmer Date 2001-05-10 Time 13:13 Sent To  
Notes
2001-05-10 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE NOTE PER COUNTY-WIDE AND
 CITY-WIDE ADMINISTRATIVE CODE 104.7.5
 VALUE OF WORK IS TO INCLUDE ALL LABOR
 AND MATERIALS FOR SCOPE OF WORK BEING
 DONE.
  
 2)NOTE: PLEASE NOTE SIZE OF GENERATOR
 IS NOT SHOWN.
  
 3)NOTE: PLEASE CLARIFY THE GROUPING
 OF MAINS PER 230-72. ALSO PLEASE NOTE
 230-76 AND 230-79 FOR SHUNT TRIPS BEING
 USED FOR MEANS OF DISCONNECT.PLEASE
 CLARIFY THE NEWMAIN LOCATION WITH
 THE NEW DISCONNECT SHOWN FOR THE
 GENERATOR.
  
 4)NOTE: PLEASE SHOW MORE DETAIL FOR
 GROUNDING ELECTRODE SYSTEM PER 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THE VALUE OF JOB
 MAY BE INCREASED AND ADDITIONAL FEES
 MAY BE DUE.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-28 Cont ID  
Sent By mcarsill Date 2001-06-28 Time 09:01 Rev Time 0.00
Received By mcarsill Date 2001-06-28 Time 09:01 Sent To  
Notes
2001-06-28 00:00:001) VENT PIPE REQUIRED OF AT LEAST 1 1/4
 12' ABOVE THE GROUND.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-11 Cont ID  
Sent By mcarsill Date 2001-05-11 Time 10:00 Rev Time 0.00
Received By mcarsill Date 2001-05-11 Time 10:00 Sent To  
Notes
2001-05-11 00:00:001) PROVIDE CUT SHEETS ON GENERATOR AND
 FUEL TANK. PLEASE SHOW UL OR FM
 APPROVALS.
 2) PLEASE INDICATE SETBACKS FROM
 PROPERTY LINES, ADJACANT PROPERTIES,
 THE BUILDING LOCATED NEAR THE TANK,
 DOOR OPENINGS, ETC.
 3) PLEASE INDICATE IDENTIFICATION
 LABELS OR SIGNS AND BARRIER PROTECTION.
 4) PLEASE INDICATE CAPACITY OF TANK.
 5) PLEASE INDICATE COMPLIANCE WITH
 NFPA 30.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-10 Cont ID  
Sent By sgraham Date 2001-05-10 Time 11:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***