Plan Review Details - Permit 01040899
Plan Review Stops For Permit 01040899
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-14 Cont ID  
Sent By dpalmer Date 2001-06-14 Time 19:39 Rev Time 0.00
Received By dpalmer Date 2001-06-14 Time 19:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-30 Cont ID  
Sent By dpalmer Date 2001-04-30 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2001-04-30 Time 19:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-08 Cont ID  
Sent By hmoser Date 2001-10-08 Time 11:53 Rev Time 0.30
Received By hmoser Date 2001-10-08 Time 11:52 Sent To  
Notes
2001-10-08 00:00:00CALLED FOR PICKUP 10/8/01 BOX AH.M.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-05-01 Cont ID  
Sent By hmoser Date 2001-05-01 Time 07:31 Rev Time 0.33
Received By hmoser Date 2001-04-28 Time 12:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-27 Cont ID  
Sent By jleech Date 2001-11-27 Time 20:13 Rev Time 0.00
Received By jleech Date 2001-11-27 Time 20:13 Sent To  
Notes
2001-11-27 00:00:00REVISED RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-27 Cont ID  
Sent By kstevens Date 2001-04-27 Time 15:19 Rev Time 0.33
Received By kstevens Date 2001-04-27 Time 15:19 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-06-18 Cont ID  
Sent By rmcdouga Date 2001-06-18 Time 15:55 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-18 00:00:00************BUILDING PROVISO************
  
 1) THE DOOR TO ALTERNATE BEDROOM (DEN)
 ON SHEET A-1.0 MUST COMPLY WITH THE
 FAIR HOUSING ACT AND PROVIDE A 32" CLEAR
 OPENING, IF THIS OPTION IS USED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIALS USED ON FLAT ROOF
 AREAS.
  
 3) PROVIDE KEY PLAN FOR STORM PANELS
 PRIOR TO INSTALLATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-05-23 Cont ID  
Sent By rmcdouga Date 2001-05-23 Time 15:21 Rev Time 6.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-05-23 00:00:00*************BUILDING UNSAT*************
  
 1) PROVIDE ATTIC ACCESS IF CLEAR HEIGHT
 OF ATTIC IS 24" OR MORE PER 2309.6 OF
 THE 97 STANDARD BUILDING CODE. PLEASE
 INDICATE LOCATION AND SIZE ON PLANS IF
 REQUIRED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIAL FOR FLAT ROOF
  
 3) SHEET S1 DOES NOT INDICATE ADEQUATE
 CONNECTORS FOR TRUSS TG1 (1457#S UPLIFT)
 PLEASE REVIEW TURRET DIMENSIONS AND
 CORRECT PLANS.
  
 4) SHOW COMPLIANCE WITH FAIR HOUSING:
 A) USABLE DOORS- DOOR TO MASTER BATH
 ROOM, DOOR TO WALK-IN CLOSET AND DOOR TO
 TOILET ALCOVE ARE REQUIRED TO HAVE A
 NOMINAL 32" CLEAR OPENING. BOTH LEAFS OF
 DOUBLE LEAF DOOR AT DEN MUST BE ACTIVE
 OR IF ONLY ONE LEAF IS ACTIVE IT MUST
 HAVE NOMINAL 32" CLEAR OPENING.
  
 B) INDICATE COMPLIANCE WITH LOCATION OF
 LIGHT SWITCHES, ELECTRICAL OUTLETS,
 THERMOSTATS AND OTHER ENVIRONMENTAL
 CONTROLS ON PLANS.
  
 C) PROVIDE REINFORCING DETAILS FOR GRAB
 BARS IN BOTH BATH ROOMS.
  
 D) INDICATE WHICH OF THE TWO SETS OF
 DESIGN SPECIFICATIONS(SPECIFICATION A OR
 SPECIFICATION B) IS BEING USED. SEE
 ATTACHMENT.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-24 Cont ID  
Sent By sgraham Date 2001-04-24 Time 11:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***