Plan Review Details - Permit 01040876
Plan Review Stops For Permit 01040876
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-04-23 Cont ID  
Sent By jwitmer Date 2001-04-23 Time 12:06 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-26 Cont ID  
Sent By dpalmer Date 2001-04-26 Time 20:50 Rev Time 0.00
Received By dpalmer Date 2001-04-26 Time 20:50 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-05-08 Cont ID  
Sent By pkrauss Date 2001-05-08 Time 11:08 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-04-20 Cont ID  
Sent By mcarsill Date 2001-04-20 Time 09:56 Rev Time 0.00
Received By mcarsill Date 2001-04-20 Time 09:56 Sent To  
Notes
2001-04-20 00:00:001) INTERIOR FINISH ON WALLS AND CEILING
 MUST BE AT LEAST A CLASS C FLAME
 SPREAD.
 2) THE C LABELED FIRE DOORS ARE TO BE
 EQUIPPED WITH SELF-CLOSING DEVICES THAT
 POSITIVELY LATCH WHEN CLOSED.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER REMODEL.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM REMODEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-07 Cont ID  
Sent By pkrauss Date 2001-08-07 Time 16:37 Rev Time 0.40
Received By pkrauss Date 2001-08-07 Time 16:36 Sent To  
Notes
2001-08-07 00:00:00AS BUILDT DRAWINGS MECH PERMIT 01060471

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-05-08 Cont ID  
Sent By pkrauss Date 2001-05-08 Time 09:56 Rev Time 0.50
Received By pkrauss Date 2001-05-08 Time 09:55 Sent To  
Notes
2001-05-08 00:00:00********************PROVISO*************
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION:
  
 1.MANUFACTURE DATA ON HOT GAS REHEAT
 FOR HEAT PUMPS.
  
 2.DRAWING M-3, HEAT PUMP DETAIL
 INDICATES THE CONDENSATE IS SHOWN
 ON P-1.NO CONDENSATE LINE IS
 SHOWN ON THAT DRAWING.PLEASE
 DIPICT CONDENSATEON PLAN.
  
 NOTE:EMERGENCY DRAIN LINE FROM
 AUXILLIARY DRAIN PAN MUST
 TERMINATE AT A CONSPICUOUS
 AREA TO SERVE AS AN ALARM
 THAT REGULAR CONDENSATE
 DRAIN LINE IS CONSTRICTED.
 (1997 SMC 304.8.6)
  
 3.PLEASE SPECIFY WHAT MATERIAL THE
 CONDENSER WATER PIPING IS GOING
 TO BE (COPPER, STEEL?).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-03 Cont ID  
Sent By kstevens Date 2001-05-03 Time 11:21 Rev Time 1.50
Received By kstevens Date 2001-05-03 Time 14:14 Sent To  
Notes
2001-05-03 00:00:00REVIEW NOTES.PASSED
 ****PROVISO****
 SHOW T & P (RELIEF VALVE) DISCHARGE
 AND HEATER PAN DRAIN LINES PER SPC-94
 507.8.3 & 507.8.4IF RELIEF DISCHARGE
 AND PAN DRAIN ARE DRAINING INTO FLOOR
 DRAIN THAN FLOOR SINK IN REQUIRED.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-05-08 Cont ID  
Sent By pkrauss Date 2001-05-08 Time 11:11 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***